4.10 CURRENT TRANSFORMER
ATTENTION
By standard, each power section of the Power Controller has a current transformer. When using external current transformers, for instance on the secondary side of a transformer, these must be connected to the terminals X7.1 and X7.2 and terminated using a burden resistor! The burden resistor must be designed so that at nominal current a voltage drop of 1.0Vrms occurs at the bur- den resistance. For connection, take care to have the respective correct phase angle.
The internal current transformers may not be shunted, because the burden resistor R 40 is on the control cards. If load current monitoring of the phase 2 (not controlled) is desired for
CURRENT TRANSFORMER TERMINAL X7.2 | TERMINAL X7.1 | |
phase L1 | .11(k) | .12(l) |
phase L2 | .21(k) | .22(l) |
phase L3 | .31(k) | .32(l) |
TAB. 15 | CURRENT TRANSFORMER |
|
The following parameters must be checked or adjusted:
HARDWARE PARAMETER
current transformer | xxxxx | UE_I | |
type | current | xxxxx | I_TYP |
burden resistance | xxx,xx | R_BUERDE_I | |
LIMITATIONS |
|
| |
Irms | maxI1 | xxxx | A IEMA |
REMARK
Current measuring in
Although phase 2 is not controlled in
As only phase 1 is controlled with
The measuring values given do not influence the controller and are available for Bus interfaces, display and analog outputs. Parameter values must not be changed.
4.11 VOLTAGE TRANSFORMER
As standard, each power section is fitted with a voltage transformer for recording the load voltage. It is possible to measure voltages of up to 690V. The voltage transformers are wired to the control device A70 by the works.
LOAD VOLTAGE | TERMINAL X7.2 | TERMINAL X7.1 |
phase L1 | .15 | .16 |
phase L2 | .25 | .26 |
phase L3 | .35 | .36 |
TAB. 16 VOLTAGE TRANSFORMER