AEG Thyro-P - page 63

Page 63

63

The thyristors are set to full scale

•Was the set point set via motor potentiometer function? Check value using the LBA.

•Check the control characteric (STA, STE, ADD).

•Controller feedback signal available? Check current transformer and voltage transformer connections at the terminal blocks X7.1 and X7.2.

•Parameters TSMI and H_IE, Urms min, Irms min, Pmin are larger than 0.

•Controller parameters Ti and Kp are set too small.

•Parameters IEMA, UEMA, PMA are set too large or the load current is too small.

•Possibly thyristor short-circuit

REMARK

In case the load current is too small (connection of a test load), the device must be parameterized for U, U2 control or ”without control“. The regulation limits continue to remain active. Connection of a minimal load (e.g. 100W lightbulb) is necessary.

Measures in case of other malfunction

•Evaluation of incident register (data logger) with LBA or Thyro-Tool

•Comparison of actual parameters of Thyro-P with parameters in type list.

•Comparison of actual parameters of Thyro-P with the system dependent parameters stored in the PC.

•Correct number of controlled phases ((parameters)

•With activated trouble signal relay Evaluation which faults led to a response, eliminate the fault.