The thyristors are set to full scale
•Was the set point set via motor potentiometer function? Check value using the LBA.
•Check the control characteric (STA, STE, ADD).
•Controller feedback signal available? Check current transformer and voltage transformer connections at the terminal blocks X7.1 and X7.2.
•Parameters TSMI and H_IE, Urms min, Irms min, Pmin are larger than 0.
•Controller parameters Ti and Kp are set too small.
•Parameters IEMA, UEMA, PMA are set too large or the load current is too small.
•Possibly thyristor
REMARK
In case the load current is too small (connection of a test load), the device must be parameterized for U, U2 control or ”without control“. The regulation limits continue to remain active. Connection of a minimal load (e.g. 100W lightbulb) is necessary.
Measures in case of other malfunction
•Evaluation of incident register (data logger) with LBA or
•Comparison of actual parameters of
•Comparison of actual parameters of
•Correct number of controlled phases ((parameters)
•With activated trouble signal relay Evaluation which faults led to a response, eliminate the fault.