AEG Thyro-P Parameters Main menu, = Main menu (appears after plugging in the LBA)

Page 30

30

Main menu

Parameters

= Main menu (appears after plugging in the LBA)

 

Submenu

 

Menu

 

next submenu

Default

User

Remarks

 

 

 

 

 

 

 

 

 

 

 

 

Value

Value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

Temperature

 

 

 

 

 

 

 

 

PT1000,PT100,NTC

 

 

PT1000

Sensor used

 

 

 

Ch.curve no.

X

 

 

type

Type-dependent, see chapter type overview

 

 

Temperature

xxx°C

 

 

 

Display actual

temperature (relative value)

 

 

Lev.wire br.

 

*

 

 

 

 

 

 

Lev. sh-circ.

 

*

 

 

 

 

 

 

Comp.val.DAC

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

No.,DaLo,K1,K2,K3

 

 

 

Status- / fault name

 

 

1

 

 

 

 

 

 

 

Communication with RS 232 active

 

 

2

 

 

 

 

 

 

 

Communication with fibre optic active

 

 

3

 

 

 

 

 

 

 

Power value negative

 

 

4

 

 

 

 

 

 

 

Communication fault RS 232 or fibre optic

 

 

5

 

 

 

 

 

 

 

Synchr. interfaces failure (e.g. Profibus)

 

 

6

 

 

 

 

 

 

 

External processor on the SSC signals fault

 

 

7

 

 

 

 

 

 

 

K3 after RESET

 

 

 

8

 

 

 

 

 

 

 

RESET active

 

 

 

9

 

 

 

 

 

 

 

Data in EEPROM invalid (reload parameters)

 

 

10

 

 

 

 

 

 

 

Internal message

 

 

11

 

 

x

 

 

 

K2

Limiting value

is exceed

 

 

12

 

 

 

 

 

 

 

Excess device temperature is present

 

 

13

 

 

 

 

 

 

 

Instant current interruption has responded

 

 

14

 

 

 

 

 

 

 

Internal message

 

 

15

 

 

 

 

 

 

 

Fault exists in load circuit-collective fault 16,17

 

 

16

 

 

 

 

 

 

 

Undercurrent exists in the load circuit

 

 

17

 

 

 

 

 

 

 

Overcurrent exists in the load circuit

 

 

18

 

 

 

 

 

 

 

Internal message

 

 

19

x

 

 

 

 

 

Dalo

Circuit OK

 

 

 

20

 

 

 

 

 

 

 

Undervoltage exists in the power section

 

 

21

 

 

 

 

 

 

 

Overvoltage in the power section

 

 

22

 

 

 

 

 

 

 

Internal message

 

 

23

 

 

 

 

 

 

 

Internal message

 

 

24

 

x

 

 

 

 

K1

Synchronization

fault

 

 

25

 

 

 

 

 

 

 

Collective fault 4,6,9,10,11,12,14-24

 

 

 

 

 

 

 

 

 

 

(each fault leads to switching)

 

 

26

 

 

 

 

 

 

 

Internal message

 

 

27

 

 

 

 

 

 

 

Internal message

 

 

28

 

 

 

 

 

 

 

Internal message

 

 

29

 

 

 

 

 

 

 

Internal message

 

 

30

 

 

 

 

 

 

 

Power Controller is in peak current limitation

 

 

 

 

 

 

 

 

 

 

(only for operating mode MOSI)

 

 

31

 

 

 

 

 

 

 

Temperature sensor, short circuit or sensor break

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

Parameterization control characteristic

 

 

Uload^2

UxU

 

 

UxU

Selection control characteristic Uload2

 

 

Uload

rms

U

 

 

 

Selection control characteristic Uload

 

 

Iload^2

IxI

 

 

 

Selection control characteristic Iload2

 

 

Iload

rms

I

 

 

 

Selection control characteristic Iload

 

 

Active power

P

 

 

 

Selection control characteristic effective load, P

 

 

No

control

 

 

 

 

Selection set operation (phase-angle control angle)

 

 

PID

factors

 

8

 

 

Parameterization controller parameters, password prot.

 

 

 

 

 

 

 

 

 

 

 

 

8

PID factors

 

 

 

 

 

 

 

 

Sta.-Regl. OFF,ON

 

 

ON

With standard control OFF the control parameters

 

 

 

 

 

 

 

 

 

 

can be stipulated

 

 

P - part

 

 

 

type

Controller parameters, P-part

 

 

I - part

 

 

 

type

Controller parameters, I-part

 

 

D - part

 

 

 

type

Controller parameters, D-part

 

 

 

 

 

 

 

 

 

 

 

 

* password protection

Image 30