EVENT NO. 

PRESET 

 

STATUS MESSAGE

  

LOG 

RELAY

  1  

 

 

Communication RS 232 interface active

  2  

 

 

Communication fi bre optic interface active

  3  

 

 

Negative power (calculated value)

  4  

 

 

Communication fault RS 232 or fi bre optic interface

  5  

 

 

Synchronous interface fault (for instance Profi bus)

  6  

 

 

External processor on the SSC signals fault

  7  

 

K3  

after RESET - monofl op function

  8  

 

 

Controller lock is active

 9  

 

 

 

 Data in the EEPROM invalid

(then reload Thyro-P parameter memory using 

Thyro-Tool Familiy)

 10  

 

 

Internal message

 11  

 

K2  

Limiting exceeded

 12  

 

 

Device overtemperature

 13  

 

 

Quick circuit interruption has responded

 14  

 

 

Internal message

 15  

 

 

Failure in load circuit, collective failure

 16  

 

 

Undercurrent in load circuit, when activated

 17  

 

 

Overcurrent in load circuit, when activated

 18  

 

 

Internal message

 19  

DaLo  

 

Indication appears on return of supply

 20  

 

 

Undervoltage in the power section

 21  

 

 

Overvoltage in the power section

 22  

 

 

Internal message

 23  

 

 

Internal message

 24  

 

K1 

Synchronization fault

 25   

 

 

 Collective fault 

(each fault leads to switching of the output)

 26  

 

 

Internal message

 27  

 

 

Internal message

 28  

 

 

Internal message

 29  

 

 

Internal message

 30   

 

 

 For the operating mode MOSI: 

Power Controller has run into peak current limitation

 31  

 

 

Temperature sensor, short circuit or sensor break

TAB. 10   ALLOCATION OF THE MESSAGE REGISTER