21
2.5.1 LOAD MONITORING
MONITORING OF THE LOAD AND MAINS VOLTAGE
Each power section is fitted with its own transformer for creating the synchronization voltages. This also allows monitoring of the phase voltages. In the LBA menu monitoring, the limits may be set for ULine min and ULine max. If larger deviations are detected, then a fault indication is generated.
ABSOLUTE OR RELATIVE MONITORING
Relative monitoring for heating elements for Rhot/Rcold ≈ 1 and absolute monitoring for heating elements with Rhot/Rcold ≠ 1 are possible.
ABSOLUTE VALUE MONITORING CURRENT
This function allows monitoring of a freely selectable absolute current limit. The parameters for the value may be set in ampere.
i |
I < threshold |
TL |
indication 16,17 (Chap. 3.4) |
tV |
FIG. 4 ABSOLUTE VALUE MONITORING
This absolute value monitoring lends itself to one or more load resistances organized in parallel or in series. Generally, the effective current value measured is continuously compared with a preset- table absolute current limit for undercurrent or overcurrent. If these limits are undercut or exceeded an indication shows. In case of resistor elements organized in parallel, it is therefore possible, using the lower current limit, to select a partial load interruption. Using the upper current limit, in case of resistors switched in series,
RELATIVE MONITORING
This monitoring is sensible if the resistance value of the load slowly changes. Changes in resistance may for instance be caused by temperature changes or by ageing. The current (b) of the Power Controller is regarded as 100% load current (current in
FIG. 5 RELATIVE MONITORING