32
3.1.4 COPYING FUNCTION USING THE LBA
It is possible to load the complete
PLUG LBA INTO POWER CONTROLLER NO. 1
1.reload data (data is stored in the LBA RAM)
2.storing in the LBA
(data is copied into the
After the waiting time unplug LBA from Power Controller 1.
Plug LBA into Power Controller no. 2
3.LBA
After the waiting time data from LBA are in Power Controller 2.
4.Save
TAB. 7 COPYING FUNCTION USING THE LBA
Data from Power Controller 1 have now been copied to Power Controller 2.
ATTENTION
Only parameters of equal Power Controllers (for instance type voltage, type current, phase number) may be copied.
3.1.5 OPERATION DISPLAY
On the operation display, one, two or three actual values are optionally displayed in double digit size. An example for the operation display able to be configured using parameters is shown below:
U1
I1
456.7V
1567.9A
PG 1234.8kW
Status messages
FIG. 7 OPERATION DISPLAY
The operating data displayed are the values U, I and P (Pges for
device configuration is displayed, if no indications are waiting. Otherwise, „status messages“ is displayed. By selecting the key, the indications are displayed:
Status messages | ^v |
yyyymmdd | hhmmss |
limit | 1250kW |
yyyymmdd | hhmmss |
undervoltage | <360V |
|
|
fault type, load, Power Controller type, limitations, etc. are notified with the corresponding time of day. etc.