Tripp Lite APSX Series owner manual Set Configuration DIP Switches, Group a DIP Switches

Page 5

Configuration

Set Configuration DIP Switches

Using a small tool, set the Configuration DIP Switches (located on the front panel of your unit, see diagram) to optimize Inverter/Charger operation depending on your application.

B4

B3

B2

B1

 

 

 

INPUT C/B

Group B Dip Switches

 

A4

A3

A2

A1

 

OUTPUT C/B 12A

 

Group A Dip Switches

Group A DIP Switches

A1 Select Battery Type—REQUIRED

CAUTION: The Battery Type DIP Switch setting must match the type of batteries you connect, or your batteries may be degraded or damaged over an extended period of time. See “Battery Selection,” for more information.

A4 A3 A2 A1

Battery Type

Switch Position

Gel Cell (Sealed) Battery

Up

Wet Cell (Vented) Battery

Down (factory setting)

 

A2

Select High AC Input Voltage Point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for Switching to Battery—OPTIONAL*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

APSX2424 models

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

Switch Position

 

278V

Up

 

259V

Down (factory setting)

.

 

 

 

 

 

 

 

 

 

 

 

 

 

A2 Charger Inhibit—OPTIONAL APSX750, APSX1250, APSX2012 models

Charger

Switch Position

Inhibit

Up

Enable

Down (factory setting)

A4 A3 Select Low AC Input Voltage Point for Switching to

Battery—OPTIONAL*

Voltage

Switch Position

201V

#A4 Up & #A3 Up

182V

#A4 Up & #A3 Down

163V

#A4 Down & #A3 Up

144V

#A4 Down & #A3 Down

 

(factory setting)

*Most of your connected appliances and equipment will perform adequately when your Inverter/Charger’s High AC Input Voltage Point is left in the factory setting and its Low AC Voltage Input Point is set to 182V. However, if the unit frequently switches to battery power due to momentary high/low line voltage swings that would have little effect on equipment operation, you may wish to adjust these settings. By increasing the High AC Voltage Point and/or decreasing the Low AC Voltage Point, you will reduce the number of times your unit switches to battery due to voltage swings.

Group B DIP Switches

B1 B2 Select Load Sharing—OPTIONAL

Your Inverter/Charger features a high-output battery charger that can draw a significant amount of AC power from your utility source or generator when charging at its maximum rate. If your unit is supplying its full AC power rating to its connected heavy electrical loads at the same time as this high charging occurs, the AC input circuit breaker could trip, resulting in the complete shut off of pass-through utility power.

To reduce the chance of tripping this breaker, Inverter/Chargers may be set to automatically limit the charger output. This keeps the sum of the unit’s AC load and charge power within the circuit breaker rating. This charger-limiting function has four settings, allowing you to reduce the charger’s draw lower and lower, as needed, if the AC input circuit breaker keeps tripping under the normal AC loads of devices you have connected downline from the unit. The figures on the next page show how to set your DIP Switches to determine how heavy the connected load can be on your Inverter/Charger before charger-limiting begins.

5A

Image 5
Contents Apsx Series DC-to-AC Inverter/Chargers ContentsLimited Warranty Important Safety InstructionsFeature Identification Indicator Lights Switch ModesOperation Flashing red Inverter ShutdownSet Configuration DIP Switches ConfigurationGroup a DIP Switches Group B DIP SwitchesSelect Battery Charger-Limiting Select Battery Type Battery SelectionMatch Battery Amp-Hour Capacity to Your Application ExampleVehicular and Non-Vehicular Horizontal Mount MountingNon-Vehicular or Vehicular Battery ConnectionAC Input/Output Connection Troubleshooting ServiceMaintenance Confiable energía de respaldo de emergencia ContenidoMejor para su equipo Mejor para sus bateríasGarantía limitada Instrucciones de seguridad importantesIdentificación de funciones Luces indicadoras OperaciónModos de conmutación Fijar conmutadores DIP de configuración ConfiguraciónConmutadores DIP Grupo a Conmutadores DIP Grupo BSeleccionar cargador de batería Configuración continuaciónOpciones de carga alta y baja de su unidad Usted prolonga la vida de sus bateríasEjemplo Selección de bateríaSeleccionar tipo de batería Montaje horizontal vehicular y no vehicular MontajeNo vehicular o Vehicular Conexión de bateríaConexión de entrada/salida de corriente alterna Mantenimiento Solución de problemasServicio Alimentation fiable en énergie de secours Table des matièresMeilleur pour votre équipement Meilleur pour vos batteriesImportantes consignes de sécurité Mise en garde concernant lemplacementGarantie limitée Mises en garde Connexion déquipementIdentification de caractéristiques Voyants lumineux FonctionnementCommutation des modes Groupe a de commutateurs DIP Réglage de la configuration des commutateurs DIPGroupe B de commutateurs DIP A1 Choix du type de batterie-EXIGÉChoix des points de limitation du Configuration suiteExemple Choix de batterieChoisir le type de batterie Montage horizontal véhiculaire et non-véhiculaire MontageHautement Efficace Délectricité Puissance nominale Branchement des batteriesVéhiculaire ou non- véhiculaire Branchement Entrée/Sortie CA Dépannage RéparationEntretien Ñîäåðæàíèå Îãðàíè÷åííàÿ ãàðàíòèÿ Âàæíûå óêàçàíèÿ ïî òåõíèêå áåçîïàñíîñòèÀÂÒÎÌÀÒÈ×ÅÑÊÈÉ Îïðåäåëåíèå ýëåìåíòîâÏåðåêëþ÷åíèå ðåæèìîâ ÔóíêöèîíèðîâàíèåÓñòàíîâêà êîíôèãóðàöèîííûõ DIP-ïåðåêëþ÷àòåëåé ÊîíôèãóðàöèÿÊîíôèãóðàöèÿ ïðîäîëæåíèå Âûáîð áàòàðåè Òîëüêî ìîäåëè 750 è ÌîíòàæÌîáèëüíûé è ñòàöèîíàðíûé ãîðèçîíòàëüíûé ìîíòàæ Ìîáèëüíîå èëè ñòàöèîíàðíîå Ïîäêëþ÷åíèå áàòàðåèÏîäêëþ÷åíèå âõîäà/âûõîäà ïåðåìåííîãî òîêà Óñòðàíåíèå íåèñïðàâíîñòåé ÎáñëóæèâàíèåÒåõíè÷åñêîå îáñëóæèâàíèå Òåõíè÷åñêèå õàðàêòåðèñòèêè SpecificationsSpécifications Especificaciones