Tripp Lite 20KVA Operation Normal Conditions, Initial Battery Charging, Turning the UPS on

Page 7

Installation (continued)

WIRING CONNECTION

Connect your wiring to the input and output terminal blocks located on the rear panel of your UPS (see figure below).

CAUTION!

Qualified personnel should follow all procedures prescribed by N.E.C. and other local codes for hardwiring devices to a utility source.

Ensure that cables are fitted with cable sleeves and are secured by connector clamps. Tighten connections with a torque of not less than 35 inch-pounds. Observe the appropriate cable connection regulations [e.g. National Electrical Code (NEC) in the U.S.] at all times. Using cables of improper size may damage your equipment and cause fire hazards.

G N1 R1 S1 T1

N2 T2 S2 R2 G

NOTE: when shipped from the factory, bypass input and main input wires are connected.

For equipment requiring a neutral connection to an IT power distribution system, the disconnect device shall be a four-pole device and shall disconnect all line conductors and the neutral conductor. If a disconnect device interrupts the neutral conductor, it shall simultaneously interrupt all line conductors.

INITIAL BATTERY CHARGING

Although the internal batteries are charged prior to shipping, allow the internal batteries to charge uninterrupted for 24 hours after initial installation.

OUTPUT VOLTAGE SELECTION (VIA SOFTWARE)

The UPS's output voltage is factory set at 220/380V AC. If you require output voltage of 230/400V AC or 240/415V AC, you must change the UPS's output voltage via the included software interface.

The UPS must be in electronic bypass (press the “OFF” Button) prior to selecting the UPS's output voltage.

STEP 1) Load the included software CD on a computer which is connected to the UPS power module through the computer's COMM1 serial port. Note: the computer must have Windows® 98 or above installed in order to run the software.

STEP 2) In the Utility Directory, double-click on the “onlineconfig.exe” executable file.

STEP 3) Select output voltage, either 220/380, 230/400 or 240/415. (See screen image.)

Operation (Normal Conditions)

TURNING THE UPS ON

Make sure the UPS is properly installed (see Installation section) and the Manual Bypass Switch is set to NORMAL.

Turn the AC Main Input Switch and Bypass Input Switch Circuit Breakers ON.

If your AC input is providing power normally within your selected range, your connected load will energize in Bypass. However, the UPS's inverter is not yet on. Press the front “ON” button to begin inverter operation.

If your AC input is not providing power normally, you have the option of starting from battery. (Your battery must be at least partially charged for this operation to succeed.) Press and hold both the "Battery Start" switch and the “ON” button for three seconds to start your UPS in “ON BATTERY” mode. Note that some electronic equipment may draw more amps during startup; when starting from battery, consider reducing the initial load on the UPS.

The UPS will perform a brief self-test and show the results on the LCD Display. (See Self-Testing section, for display sequence.) After a successful self-test, the UPS will provide AC power from the inverter to your load.

7

Image 7
Contents Español Français UPS Location Warnings Important Safety WarningsControl Panel Front PanelBattery Access Panel cover removed Rear Panel Rear PanelUPS Location InstallationMounting Bracket Installation UPS Input and Output Hardwire ConnectionOutput Voltage Selection VIA Software Initial Battery ChargingWiring Connection Operation Normal ConditionsLCD Display Select Button SELF-TESTINGSelf Testing Battery OK DC to DC OK Inverter Test Turning the UPS OFFOperation Under Shutdown Operation Special ConditionsOperation on BYPASS-VOLTAGE OUT of Range Inverter on WarningsCommunications Open Remote Emergency Power OFF EPODRY Contact Interface DRY Contact Interface TableAdding or Replacing Internal Batteries Do not Remove Battery SleeveBattery Packs are Heavy Check Battery Pack Voltage Before Completing InstallationInternal Battery Pack Wiring Diagram Adding or Replacing Internal Batteries Adding or Replacing Internal Batteries Adding or Replacing Internal Batteries Observe Proper Polarity ServiceWarranty Limited WarrantyModel SU20K3/3INT SpecificationsModel SU30K3/3INT Manual del Propietario Advertencias sobre la colocación y ubicación del UPS Advertencias de Seguridad ImportantesPanel DE Control Panel FrontalPanel DE Acceso a LA Bateria Tapa Removida Panel Frontal continuaciónPanel Trasero Panel TraseroConexion a Tierra InstalaciónUbicación DEL UPS Instalacion DE LOS Soportes DE MontajeEncendiendo EL UPS Operación Condiciones NormalesCarga Inicial DE LA Bateria Seleccion DEL Voltaje DE Salida VIA SoftwareBoton Select Seleccionar DE LA Pantalla LCD Operación Condiciones Normales continuaciónApagando EL UPS AUTO-PRUEBAOperacion Bajo CIERRE/PARADA Operación Condiciones EspecialesOperacion EN DERIVACION-VOLTAJE Fuera DE Rango Advertencias DEL Inversor EncendidoComunicaciones Operación Condiciones Especiales continuaciónTabla DE LA Interfaz DE Contacto Seco Comunicaciones continuaciónInterfaz DEL Contacto Seco Apagado DE Emergencia Remoto EPO¡NO Remueva LA Cubierta Protectora DE LA Bateria Añadiendo o Remplazando las Baterías Internas¡LOS Modulos DE Bateria SON Pesados Añadiendo o Remplazando las Baterías Internas continuación Diagrama DEL Cableado DEL Modulo DE Baterias InternasAñadiendo o Remplazando las Baterías Internas continuación Terminales ¡PELIGRO ¡OBSERVE LA Polaridad Correcta ServicioGarantía Garantia LimitadaModelo SU20K3/3INT EspecificacionesModelo SU30K3/3INT Especificaciones continuaciónManuel du propriétaire Mises en garde relatives à la localisation de londuleur Importantes consignes de sécuritéPanneau avant Panneau DE CommandePanneau Daccès AUX Batteries carter enlevé Panneau avant suitePanneau Arrière Panneau arrièreSélection DU Câblage IL Faut Installer Londuleur À Laide DE Brides DE FixationMises EN Garde Relatives À LA Localisation DE Londuleur Connexion DE Mise À LA TerreSélection DE LA Tension DE Sortie À Laide DUN Logiciel Installation suiteFonctionnement Conditions normales Première Charge DE LA BatterieBouton DE Sélection DE Lécran ACL Fonctionnement Conditions normales suiteArrêter Londuleur Éxécution DUN AUTO-TESTFonctionnement Pendant UN Arrêt Fonctionnement Conditions spécialesFonctionnement EN DÉRIVATION-TENSION Hors Plag Mises EN Garde Inverseur EN MarcheInterface RS-232 Commuter Londuleur EN Mode NormalFonctionnement Conditions spéciales suite Fonctionnement DU Commutateur DE Dérivation ManuelleInterface Contact SEC Ajout et remplacement des batteries internesArrêt Durgence Emergency Power OFF EPO À Distance Communications suiteSchéma DU Câblage Interne DUN Bloc DE Batterie Ajout et remplacement des batteries internes suiteAjout et remplacement des batteries internes suite Bornes Ajout et remplacement des batteries internes suite Garantie Limitée À VIE GarantieObserver LA Bonne Polarité Modèle SU20K3/3INT SpécificationsModèle SU30K3/3INT Spécifications suite