Delta Electronics VFD-XXXE Fault Fault Descriptions Corrective Actions Name, Phase error

Page 33

 

Fault

Fault Descriptions

 

Corrective Actions

 

 

 

Name

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Check if the motor is suitable for operation by

 

 

 

Auto accel/decel failure

 

AC motor drive.

 

 

2.

Check if the regenerative energy is too large.

 

 

 

 

 

 

3.

Load may have changed suddenly.

 

 

U-phase error

 

 

 

 

 

 

 

V-phase error

 

 

 

 

 

 

 

W-phase error

Return to the factory.

 

 

OV or LV

 

 

 

 

 

 

 

 

 

Temperature sensor error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Check parameter settings (Pr.10.01) and

 

 

 

 

 

AVI/ACI wiring.

 

 

PID feedback signal error

2.

Check for possible fault between system

 

 

 

 

response time and the PID feedback signal

 

 

 

 

detection time (Pr.10.08)

 

 

 

Analog signal error

Check the wiring of ACI

 

 

Phase Loss

Check Power Source Input if all 3 input phases are

 

 

 

connected without loose contacts.

 

 

 

 

 

 

When (one of) the output terminal(s) is grounded,

 

 

 

 

short circuit current is more than 50% of AC motor

 

 

 

drive rated current, the AC motor drive power

 

 

 

module may be damaged.

 

 

Ground fault

NOTE: The short circuit protection is provided

 

 

for AC motor drive protection, not for protection

 

 

 

of the user.

 

 

 

1.

Check whether the IGBT power module is

 

 

 

 

damaged.

 

 

 

2.

Check for possible poor insulation at the output

 

 

 

 

line.

 

 

 

1.

Check the RS485 connection between the AC

 

 

 

 

 

motor drive and RS485 master for loose wires

 

 

 

 

and wiring to correct pins.

 

 

Communication Error

2.

Check if the communication protocol, address,

 

 

 

transmission speed, etc. are properly set.

 

 

 

 

 

 

 

3.

Use the correct checksum calculation.

 

 

 

4.

Please refer to group 9 in the chapter 5 for

 

 

 

 

detail information.

 

 

Auto Tuning Error

1.

Check cabling between drive and motor

 

 

 

2.

Retry again

 

 

 

 

 

Communication time-out

1.

Press RESET key to set all parameters to

 

 

 

error on the control board

 

factory setting.

 

 

or power board

2.

Return to the factory.

 

 

 

Motor overheat protection

1.

Check if the motor is overheat

 

 

2.

Check Pr.07.12 to Pr.07.17 settings

 

 

 

 

 

PG signal error

1.

Check the wiring of PG card

 

 

 

2.

Try another PG card

 

 

 

 

 

CANopen Guarding Time out

Connect to CAN bus again and reset CAN bus

 

 

 

(Only for VFDxxxExxC)

 

 

 

 

 

 

 

CANopen Heartbeat Time out

Connect to CAN bus again and reset CAN bus

 

 

 

(Only for VFDxxxExxC)

 

 

 

 

 

English- 33

Image 33
Contents Preface Voltage Class 115V Class SpecificationsGeneral Specifications SL2 VT2 TL3 WT3 Basic Wiring Diagram+/B1 PNP mode without external power Signal DescriptionDescription of the Digital Keypad KPE-LE02 Optional To shift data Operation Steps of the Digital KeypadFrame Power Terminals Torque Wire Wire Type Power Terminals and Control TerminalsTerminal Symbol Terminal ExplanationsSpecification for the Control Terminals Control Terminals ExplanationsFrame Control Terminals Torque Group 0 User Parameters Summary of Parameter SettingsModels Explanation Settings FactoryNot for VFD*E*C models VFD*E*C modelsGroup 1 Basic Parameters For VFD*E*C models, the factory setting isExplanation Settings Factory AVI2 Group 2 Operation Method ParametersUP/DOWN Explanation Settings Factory Setting For VFD*E*C modelsGroup 3 Output Function Parameters Group 4 Input Function Parameters Not for VFD*E*CFor VFD*E*C For VFD*E*C models Models, the factory Quick Stop Only for VFD*E*C models Setting is 23.Bit5=1MI6 used by PLC Group 6 Protection Parameters Group 5 Multi-Step Speeds ParametersExplanation Settings Factory FLA Group 7 Motor ParametersSetting Group 8 Special Parameters Group 9 Communication Parameters Only for VFD*E*C Address only for VFD*E*C modelsOnly for VFD*E*C Models Group 10 PID Control ParametersParameters for Extension Card MO3/RA3 MO2/RA2MO4/RA4 MO5/RA5Explanation Settings Quick Stop Only for VFD*E*C models Fault Codes Group 13 PG function Parameters for Extension CardPLC not for VFD*E*C models Over voltage Over currentOverheating OverloadCC current clamp OV hardware error Fault Fault Descriptions Corrective Actions Name OverloadGFF hardware error OC hardware errorPhase error Fault Fault Descriptions Corrective Actions NameTemperature sensor error PID feedback signal errorFrame Dimensions are in mm inchH1 H Frame C Unit mm inch