Delta Electronics VFD-XXXE quick start Explanation Settings Factory

Page 21

 

 

Pr.

Explanation

Settings

Factory

NOTE

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

0: Disabled

 

 

 

 

 

 

 

1: Enabled during constant speed operation.

 

 

 

 

 

 

 

After the over-torque is detected, keep

 

 

 

 

 

 

 

running until OL1 or OL occurs.

 

 

 

 

 

 

Over-Torque

2: Enabled during constant speed operation.

 

 

 

 

 

 

After the over-torque is detected, stop

 

 

 

06.03

Detection Mode

0

 

 

running.

 

 

 

 

 

(OL2)

 

 

 

 

 

 

3: Enabled during accel. After the over-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

torque is detected, keep running until OL1 or

 

 

 

 

 

 

 

OL occurs.

 

 

 

 

 

 

 

4: Enabled during accel. After the over-

 

 

 

 

 

 

 

torque is detected, stop running.

 

 

 

06.04

Over-Torque

10 to 200%

150

 

 

Detection Level

 

 

 

 

 

 

 

 

 

06.05

Over-Torque

0.1 to 60.0 sec

0.1

 

 

Detection Time

 

 

 

 

 

 

 

 

 

 

 

 

Electronic Thermal

0: Standard motor (self cooled by fan)

 

 

 

06.06

Overload Relay

1: Special motor (forced external cooling)

2

 

 

 

 

 

Selection

2: Disabled

 

 

 

06.07

Electronic Thermal

30 to 600 sec

60

 

 

Characteristic

 

 

 

 

 

 

 

 

 

 

 

 

 

0: No fault

 

 

 

 

 

 

 

1: Over current (oc)

 

 

 

 

 

 

Present Fault

2: Over voltage (ov)

 

 

 

06.08

3: IGBT Overheat (oH1)

0

 

 

Record

 

 

 

 

 

4: Power Board Overheat (oH2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5: Overload (oL)

 

 

 

 

 

 

 

6: Overload1 (oL1)

 

 

 

 

06.09

Second Most

7: Motor over load (oL2)

 

 

 

 

 

 

Recent Fault Record

8: External fault (EF)

 

 

 

 

 

 

 

9: Current exceeds 2 times rated current

 

 

 

 

 

 

 

during accel.(ocA)

 

 

 

 

 

 

 

10: Current exceeds 2 times rated current

 

 

 

 

 

 

 

during decel.(ocd)

 

 

 

 

 

 

 

11: Current exceeds 2 times rated current

 

 

 

 

 

 

 

during steady state operation (ocn)

 

 

 

 

 

 

 

12: Ground fault (GFF)

 

 

 

 

 

 

 

13: Reserved

 

 

 

 

 

 

 

14: Phase-Loss (PHL)

 

 

 

 

 

 

 

15: Reserved

 

 

 

 

 

 

 

16: Auto Acel/Decel failure (CFA)

 

 

 

 

 

 

 

17: SW/Password protection (codE)

 

 

 

06.10

Third Most Recent

18: Power Board CPU WRITE failure (cF1.0)

 

 

 

19: Power Board CPU READ failure (cF2.0)

 

 

 

Fault Record

 

 

 

 

 

 

20: CC, OC Hardware protection failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(HPF1)

 

 

 

 

 

 

 

21: OV Hardware protection failure (HPF2)

 

 

 

 

 

 

 

22: GFF Hardware protection failure (HPF3)

 

 

 

 

 

 

 

23: OC Hardware protection failure (HPF4)

 

 

 

 

 

 

 

24: U-phase error (cF3.0)

 

 

 

 

 

 

 

25: V-phase error (cF3.1)

 

 

 

 

 

 

 

26: W-phase error (cF3.2)

 

 

 

 

 

 

 

 

 

 

 

English- 21

Image 21
Contents Preface Voltage Class 115V Class SpecificationsGeneral Specifications SL2 VT2 TL3 WT3 Basic Wiring Diagram+/B1 PNP mode without external power Signal DescriptionDescription of the Digital Keypad KPE-LE02 Optional To shift data Operation Steps of the Digital KeypadFrame Power Terminals Torque Wire Wire Type Power Terminals and Control TerminalsTerminal Symbol Terminal ExplanationsSpecification for the Control Terminals Control Terminals ExplanationsFrame Control Terminals Torque Group 0 User Parameters Summary of Parameter SettingsModels Explanation Settings FactoryNot for VFD*E*C models VFD*E*C modelsGroup 1 Basic Parameters For VFD*E*C models, the factory setting isExplanation Settings Factory AVI2 Group 2 Operation Method ParametersUP/DOWN Explanation Settings Factory Setting For VFD*E*C modelsGroup 3 Output Function Parameters Group 4 Input Function Parameters Not for VFD*E*CFor VFD*E*C For VFD*E*C models Models, the factory Quick Stop Only for VFD*E*C models Setting is 23.Bit5=1MI6 used by PLC Group 6 Protection Parameters Group 5 Multi-Step Speeds ParametersExplanation Settings Factory FLA Group 7 Motor ParametersSetting Group 8 Special Parameters Group 9 Communication Parameters Only for VFD*E*C Address only for VFD*E*C modelsOnly for VFD*E*C Models Group 10 PID Control ParametersParameters for Extension Card MO3/RA3 MO2/RA2MO4/RA4 MO5/RA5Explanation Settings Quick Stop Only for VFD*E*C models Fault Codes Group 13 PG function Parameters for Extension CardPLC not for VFD*E*C models Over voltage Over currentOverheating OverloadCC current clamp OV hardware error Fault Fault Descriptions Corrective Actions Name OverloadGFF hardware error OC hardware errorPhase error Fault Fault Descriptions Corrective Actions NameTemperature sensor error PID feedback signal errorFrame Dimensions are in mm inchH1 H Frame C Unit mm inch