Delta Electronics VFD-XXXE quick start Specifications, Voltage Class 115V Class

Page 2

Specifications

 

 

 

Voltage Class

 

 

 

 

 

 

 

115V Class

 

 

 

 

 

 

 

 

 

 

Model Number VFD-XXXE

 

 

002

 

 

004

 

 

 

 

007

 

 

 

 

 

Max. Applicable Motor Output (kW)

 

 

0.2

 

 

0.4

 

 

 

 

0.75

 

 

 

 

 

Max. Applicable Motor Output (hp)

 

 

0.25

 

 

0.5

 

 

 

 

1.0

 

 

 

 

 

Rating

Rated Output Capacity (kVA)

 

 

0.6

 

 

1.0

 

 

 

 

1.6

 

 

 

 

 

Rated Output Current (A)

 

 

1.6

 

 

2.5

 

 

 

 

4.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

Maximum Output Voltage (V)

 

 

 

3-Phase

Proportional to Twice the Input Voltage

 

 

 

 

Carrier Frequency (kHz)

 

 

 

 

 

 

1-15

 

 

 

 

 

 

 

 

 

 

 

Output Frequency (Hz)

 

 

 

 

 

 

 

0.1~600 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rating

Rated Input Current (A)

 

 

 

 

 

 

 

Single-phase

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

9

 

 

 

 

 

18

 

 

 

 

 

Rated Voltage/Frequency

 

 

 

 

Single phase, 100-120V, 50/60Hz

 

 

 

 

 

 

Input

Voltage Tolerance

 

 

 

 

 

 

 

± 10%(90~132 V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency Tolerance

 

 

 

 

 

 

 

± 5%(47~63 Hz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling Method

 

 

 

Natural Cooling

 

 

 

 

Fan Cooling

 

 

 

 

Weight (kg)

 

 

1.2

 

 

1.2

 

 

 

 

1.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Class

 

 

 

 

 

 

 

230V Class

 

 

 

 

 

 

 

 

 

 

Model Number VFD-XXXE

 

002

 

004

007

015

 

022

 

037

055

 

075

 

 

 

Max. Applicable Motor Output (kW)

 

0.2

 

0.4

0.75

1.5

 

2.2

 

3.7

5.5

 

7.5

 

 

 

Max. Applicable Motor Output (hp)

 

0.25

 

0.5

1.0

2.0

 

3.0

 

5.0

7.5

 

10

 

 

 

Rating

Rated Output Capacity (kVA)

 

0.6

 

1.0

1.6

2.9

 

4.2

 

6.5

9.5

 

12.5

 

 

 

Rated Output Current (A)

 

1.6

 

2.5

4.2

7.5

 

11.0

 

17

25

 

33

 

 

 

 

 

 

 

 

 

 

 

 

Output

Maximum Output Voltage (V)

 

 

 

 

3-Phase Proportional to Input Voltage

 

 

 

 

 

 

Output Frequency (Hz)

 

 

 

 

 

 

 

0.1~600 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Carrier Frequency (kHz)

 

 

 

 

 

 

1-15

 

 

 

 

 

 

 

 

 

Rating

Rated Input Current (A)

 

 

 

Single/3-phase

 

 

 

 

3-phase

 

 

 

 

 

4.9/1.9

 

6.5/2.7

9.5/5.1

15.7/9

 

24/15

 

20.6

26

 

34

 

 

 

 

 

 

 

 

 

 

 

 

Rated Voltage/Frequency

 

 

 

Single/3-phase

 

 

 

 

3-phase

 

 

 

 

Input

 

 

 

200-240 V, 50/60Hz

 

 

 

200-240V, 50/60Hz

 

 

 

 

 

 

 

 

 

 

 

Voltage Tolerance

 

 

 

 

 

 

± 10%(180~264

V)

 

 

 

 

 

 

 

Frequency Tolerance

 

 

 

 

 

 

 

± 5%(47~63 Hz)

 

 

 

 

 

 

Cooling Method

 

Natural Cooling

 

 

 

 

Fan Cooling

 

 

 

 

Weight (kg)

 

1.1

 

1.1

1.1

 

*1.2/1.9

 

1.9

 

1.9

3.5

 

3.5

 

*NOTE: the weight for VFD015E23P is 1.2kg.

 

 

 

Voltage Class

 

 

 

 

 

460V Class

 

 

 

 

 

 

 

Model Number VFD-XXXE

004

 

007

 

015

022

 

037

055

075

110

 

 

 

Max. Applicable Motor Output (kW)

0.4

 

0.75

 

1.5

2.2

 

3.7

5.5

7.5

11

 

 

 

Max. Applicable Motor Output (hp)

0.5

 

1.0

 

2.0

3.0

 

5.0

7.5

10

15

 

 

 

Rating

Rated Output Capacity (kVA)

1.2

 

2.0

 

3.3

4.4

 

6.8

9.9

13.7

18.3

 

 

 

Rated Output Current (A)

1.5

 

2.5

 

4.2

5.5

 

8.2

13

18

24

 

 

 

 

 

 

 

 

 

 

Output

Maximum Output Voltage (V)

 

 

 

 

3-Phase Proportional to Input Voltage

 

 

 

 

 

Output Frequency (Hz)

 

 

 

 

 

0.1~600 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Carrier Frequency (kHz)

 

 

 

 

 

 

1-15

 

 

 

 

 

 

Rating

Rated Input Current (A)

 

 

 

 

 

3-phase

 

 

 

 

 

 

1.9

 

3.2

 

4.3

7.1

 

11.2

14

19

26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

Rated Voltage/Frequency

 

 

 

 

3-phase, 380-480V, 50/60Hz

 

 

 

 

 

Voltage Tolerance

 

 

 

 

 

± 10%(342~528V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency Tolerance

 

 

 

 

 

± 5%(47~63Hz)

 

 

 

 

 

 

Cooling Method

Natural Cooling

 

 

 

 

Fan Cooling

 

 

 

 

 

Weight (kg)

1.2

 

1.2

 

1.2

1.9

 

1.9

4.2

4.2

4.2

 

 

 

 

 

 

English-

2

 

 

 

 

 

 

 

Image 2
Contents Preface Specifications Voltage Class 115V ClassGeneral Specifications Basic Wiring Diagram SL2 VT2 TL3 WT3+/B1 Description of the Digital Keypad KPE-LE02 Optional PNP mode without external powerSignal Description Operation Steps of the Digital Keypad To shift dataTerminal Symbol Power Terminals and Control TerminalsFrame Power Terminals Torque Wire Wire Type Terminal ExplanationsFrame Control Terminals Torque Specification for the Control TerminalsControl Terminals Explanations Summary of Parameter Settings Group 0 User ParametersNot for VFD*E*C models Explanation Settings FactoryModels VFD*E*C modelsFor VFD*E*C models, the factory setting is Group 1 Basic ParametersExplanation Settings Factory Group 2 Operation Method Parameters AVI2UP/DOWN Group 3 Output Function Parameters Explanation Settings Factory SettingFor VFD*E*C models Not for VFD*E*C Group 4 Input Function ParametersQuick Stop Only for VFD*E*C models Setting is 23. For VFD*E*C For VFD*E*C models Models, the factoryBit5=1MI6 used by PLC Group 5 Multi-Step Speeds Parameters Group 6 Protection ParametersExplanation Settings Factory Group 7 Motor Parameters FLASetting Group 8 Special Parameters Group 9 Communication Parameters Only for VFD*E*C Models Address only for VFD*E*C modelsOnly for VFD*E*C Group 10 PID Control ParametersParameters for Extension Card MO4/RA4 MO2/RA2MO3/RA3 MO5/RA5Explanation Settings Quick Stop Only for VFD*E*C models PLC not for VFD*E*C models Fault CodesGroup 13 PG function Parameters for Extension Card Overheating Over currentOver voltage OverloadGFF hardware error Fault Fault Descriptions Corrective Actions Name OverloadCC current clamp OV hardware error OC hardware errorTemperature sensor error Fault Fault Descriptions Corrective Actions NamePhase error PID feedback signal errorDimensions are in mm inch FrameH1 H Frame C Unit mm inch