Delta Electronics VFD-XXXE quick start Specification for the Control Terminals

Page 9

The Specification for the Control Terminals

RA RB RC

The position of the control terminals

Terminals 1

 

 

 

 

 

AFM MCM MO1

 

 

 

Terminals 2

 

 

 

 

 

 

 

RS-485 port

MI1

MI2 MI3

MI4

MI5 MI6 DCM DCM 24V ACM

AVI

ACI 10V

 

Frame

Control Terminals

Torque

 

A, B, C

Terminals 1

5 kgf-cm (4.4 in-lbf)

 

Terminals 2

2 kgf-cm (2 in-lbf)

 

 

 

 

 

 

Wire

12-24 AWG (3.3-0.2mm2)

16-24 AWG (1.3-0.2mm2)

NOTE

Frame A: VFD002E11A/21A/23A, VFD004E11A/21A/23A/43A, VFD007E21A/23A/43A, VFD015E23A/43A, VFD002E11C/21C/23C, VFD004E11C/21C/23C/43C, VFD007E21C/23C/43C, VFD015E23C/43C, VFD002E11T/21T/23T, VFD004E11T/21T/23T/43T, VFD007E21T/23T/43T, VFD015E23T/43T, VFD002E11P/21P/23P, VFD004E11P/21P/23P/43P, VFD007E21P/23P/43P, VFD015E23P/43P

Frame B: VFD007E11A, VFD015E21A, VFD022E21A/23A/43A, VFD037E23A/43A

Frame C: VFD055E23A/43A, VFD075E23A/43A, VFD110E43A

Control Terminals Explanations

 

 

Terminal

Terminal Function

 

Factory Settings (NPN mode)

 

 

 

 

Symbol

 

ON: Connect to DCM

 

 

 

 

 

 

 

 

 

 

MI1

Forward-Stop command

ON:

Run in MI1 direction

 

 

 

OFF:

Stop acc. to Stop Method

 

 

 

 

 

 

 

MI2

Reverse-Stop command

ON:

Run in MI2 direction

 

 

OFF:

Stop acc. to Stop Method

 

 

 

 

 

 

 

MI3

Multi-function Input 3

Refer to Pr.04.05 to Pr.04.08 for programming the

 

 

MI4

Multi-function Input 4

 

 

Multi-function Inputs.

 

 

 

 

ON: the activation current is 5.5mA .

 

 

MI5

Multi-function Input 5

 

 

OFF: leakage current tolerance is 10μA.

 

 

MI6

Multi-function Input 6

 

 

 

 

 

 

 

 

+24V

DC Voltage Source

+24VDC, 20mA used for PNP mode.

 

 

 

RA

Multi-function Relay output

Resistive Load:

 

 

(N.O.) a

5A(N.O.)/3A(N.C.) 240VAC

 

 

 

 

 

 

 

5A(N.O.)/3A(N.C.) 24VDC

 

 

 

Multi-function Relay output

 

 

RB

Inductive Load:

 

 

(N.C.) b

 

 

 

1.5A(N.O.)/0.5A(N.C.) 240VAC

 

 

 

 

 

 

RC

Multi-function Relay common

1.5A(N.O.)/0.5A(N.C.) 24VDC

 

 

Refer to Pr.03.00 for programming

 

 

 

 

 

 

 

 

 

 

 

DCM

Digital Signal Common

Common for digital inputs and used for NPN

 

 

 

mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

English- 9

 

 

 

Image 9
Contents Preface Voltage Class 115V Class SpecificationsGeneral Specifications SL2 VT2 TL3 WT3 Basic Wiring Diagram+/B1 PNP mode without external power Signal DescriptionDescription of the Digital Keypad KPE-LE02 Optional To shift data Operation Steps of the Digital KeypadFrame Power Terminals Torque Wire Wire Type Power Terminals and Control TerminalsTerminal Symbol Terminal ExplanationsSpecification for the Control Terminals Control Terminals ExplanationsFrame Control Terminals Torque Group 0 User Parameters Summary of Parameter SettingsModels Explanation Settings FactoryNot for VFD*E*C models VFD*E*C modelsGroup 1 Basic Parameters For VFD*E*C models, the factory setting isExplanation Settings Factory AVI2 Group 2 Operation Method ParametersUP/DOWN Explanation Settings Factory Setting For VFD*E*C modelsGroup 3 Output Function Parameters Group 4 Input Function Parameters Not for VFD*E*CFor VFD*E*C For VFD*E*C models Models, the factory Quick Stop Only for VFD*E*C models Setting is 23.Bit5=1MI6 used by PLC Group 6 Protection Parameters Group 5 Multi-Step Speeds ParametersExplanation Settings Factory FLA Group 7 Motor ParametersSetting Group 8 Special Parameters Group 9 Communication Parameters Only for VFD*E*C Address only for VFD*E*C modelsOnly for VFD*E*C Models Group 10 PID Control ParametersParameters for Extension Card MO3/RA3 MO2/RA2MO4/RA4 MO5/RA5Explanation Settings Quick Stop Only for VFD*E*C models Fault Codes Group 13 PG function Parameters for Extension CardPLC not for VFD*E*C models Over voltage Over currentOverheating OverloadCC current clamp OV hardware error Fault Fault Descriptions Corrective Actions Name OverloadGFF hardware error OC hardware errorPhase error Fault Fault Descriptions Corrective Actions NameTemperature sensor error PID feedback signal errorFrame Dimensions are in mm inchH1 H Frame C Unit mm inch