Delta Electronics VFD-XXXE quick start General Specifications

Page 3

Control Characteristics

Operating Characteristics

Enviromental

Conditions

General Specifications

 

Control System

SPWM(Sinusoidal Pulse Width Modulation) control (V/f or sensorless vector

 

control)

 

 

 

 

 

Frequency Setting Resolution

0.01Hz

 

Output Frequency Resolution

0.01Hz

 

Torque Characteristics

Including the auto-torque/auto-slip compensation; starting torque can be 150%

 

at 3.0Hz

 

 

 

 

 

Overload Endurance

150% of rated current for 1 minute

 

Skip Frequency

Three zones, setting range 0.1-600Hz

 

Accel/Decel Time

0.1 to 600 seconds (2 Independent settings for Accel/Decel time)

 

Stall Prevention Level

Setting 20 to 250% of rated current

 

DC Brake

 

 

Operation frequency 0.1-600.0Hz, output 0-100% rated current

 

 

 

Start time 0-60 seconds, stop time 0-60 seconds

 

 

 

 

 

Regenerated Brake Torque

Approx. 20% (up to 125% possible with optional brake resistor or externally

 

mounted brake unit, 1-15hp (0.75-11kW) models have brake chopper built-in)

 

 

 

 

 

V/f Pattern

 

 

4-point adjustable V/f pattern

 

Frequency

 

Keypad

Setting by

 

 

 

 

 

Potentiometer-5kΩ/0.5W, 0 to +10VDC, 4 to 20mA, RS-485 interface; Multi-

 

Setting

 

External Signal

 

 

 

 

function Inputs 3 to 9 (15 steps, Jog, up/down)

 

Operation

 

Keypad

Set by RUNand STOP

 

Setting

 

External Signal

2 wires/3 wires ((MI1, MI2, MI3)), JOG operation, RS-485 serial interface

 

Signal

 

(MODBUS), programmable logic controller

 

 

 

 

Multi-function Input Signal

Multi-step selection 0 to 15, Jog, accel/decel inhibit, 2 accel/decel switches,

 

counter, , external Base Block, ACI/AVI selections, driver reset, UP/DOWN key

 

 

 

 

settings, NPN/PNP input selection

 

Multi-function Output

AC drive operating, frequency attained, zero speed, Base Block, fault indication,

 

Indication

 

 

overheat alarm, emergency stop and status selections of input terminals

 

 

 

 

Analog Output Signal

Output frequency/current

 

Alarm Output Contact

Contact will be On when drive malfunctions (1 Form C/change-over contact and

 

1 open collector output) for standard type)

 

 

 

 

 

 

 

 

Built-in PLC(NOT for CANopen models), AVR, accel/decel S-Curve, over-

 

 

 

 

voltage/over-current stall prevention, 5 fault records, reverse inhibition,

 

 

 

 

momentary power loss restart, DC brake, auto torque/slip compensation, auto

 

 

 

 

tuning, adjustable carrier frequency, output frequency limits, parameter

 

Operation Functions

lock/reset, vector control, PID control, external counter, MODBUS

 

 

 

 

communication, abnormal reset, abnormal re-start, power-saving, fan control,

 

 

 

 

sleep/wake frequency, 1st/2nd frequency source selections, 1st/2nd frequency

 

 

 

 

source combination, NPN/PNP selection, parameters for motor 0 to motor 3,

 

 

 

 

DEB and OOB (Out Of Balance Detection)(for washing machine)

 

Protection Functions

Over voltage, over current, under voltage, external fault, overload, ground fault,

 

overheating, electronic thermal, IGBT short circuit, PTC

 

 

 

 

 

 

 

 

6-key, 7-segment LED with 4-digit, 5 status LEDs, master frequency, output

 

Display Keypad (optional)

frequency, output current, custom units, parameter values for setup and lock,

 

 

 

 

faults, RUN, STOP, RESET, FWD/REV, PLC

 

 

 

 

VFD002E11T/21T/23T, VFD004E11T/21T/23T/43T,

 

 

 

 

VFD007E21T/23T/43T, VFD015E23T/43T, VFD007E11A, VFD015E21A,

 

Built-in Brake Chopper

VFD022E21A/23A/43A, VFD037E23A/43A VFD007E11C, VFD015E21C,

 

VFD022E21C/23C/43C, VFD037E23C/43C, VFD055E23A/43A,

 

 

 

 

 

 

 

 

VFD075E23A/43A, VFD110E43A, VFD055E23C/43C, VFD075E23C/43C,

 

 

 

 

VFD110E43C

 

Built-in EMI Filter

For 230V 1-phase and 460V 3-phase models.

 

Enclosure Rating

IP20

 

 

Pollution Degree

2

 

Installation Location

Altitude 1,000 m or lower, keep from corrosive gasses, liquid and dust

 

Ambient Temperature

-10oC to 50oC (40oC for side-by-side mounting) Non-Condensing and not frozen

 

 

 

 

 

English- 3

Image 3
Contents Preface Voltage Class 115V Class SpecificationsGeneral Specifications SL2 VT2 TL3 WT3 Basic Wiring Diagram+/B1 PNP mode without external power Signal DescriptionDescription of the Digital Keypad KPE-LE02 Optional To shift data Operation Steps of the Digital KeypadTerminal Explanations Power Terminals and Control TerminalsFrame Power Terminals Torque Wire Wire Type Terminal SymbolSpecification for the Control Terminals Control Terminals ExplanationsFrame Control Terminals Torque Group 0 User Parameters Summary of Parameter SettingsVFD*E*C models Explanation Settings FactoryModels Not for VFD*E*C modelsGroup 1 Basic Parameters For VFD*E*C models, the factory setting isExplanation Settings Factory AVI2 Group 2 Operation Method ParametersUP/DOWN Explanation Settings Factory Setting For VFD*E*C modelsGroup 3 Output Function Parameters Group 4 Input Function Parameters Not for VFD*E*CFor VFD*E*C For VFD*E*C models Models, the factory Quick Stop Only for VFD*E*C models Setting is 23.Bit5=1MI6 used by PLC Group 6 Protection Parameters Group 5 Multi-Step Speeds ParametersExplanation Settings Factory FLA Group 7 Motor ParametersSetting Group 8 Special Parameters Group 9 Communication Parameters Group 10 PID Control Parameters Address only for VFD*E*C modelsOnly for VFD*E*C Only for VFD*E*C ModelsParameters for Extension Card MO5/RA5 MO2/RA2MO3/RA3 MO4/RA4Explanation Settings Quick Stop Only for VFD*E*C models Fault Codes Group 13 PG function Parameters for Extension CardPLC not for VFD*E*C models Overload Over currentOver voltage OverheatingOC hardware error Fault Fault Descriptions Corrective Actions Name OverloadCC current clamp OV hardware error GFF hardware errorPID feedback signal error Fault Fault Descriptions Corrective Actions NamePhase error Temperature sensor errorFrame Dimensions are in mm inchH1 H Frame C Unit mm inch