Pr.

Explanation

Settings

Factory

NOTE

 

 

Setting

 

 

 

 

 

 

 

 

 

 

0: Disable. Operation status is not changed

 

 

 

 

 

 

even if operation command source Pr.02.01

 

 

 

 

 

 

is changed.

 

 

 

 

 

 

1: Enable. Operation status is not changed

 

 

 

 

 

 

even if operation command source Pr.02.01

 

 

 

02.05

Line Start Lockout

is changed.

1

 

 

2: Disable. Operation status will change if

 

 

 

 

 

 

 

 

 

 

 

operation command source Pr.02.01 is

 

 

 

 

 

 

changed.

 

 

 

 

 

 

3: Enable. Operation status will change if

 

 

 

 

 

 

operation command source Pr.02.01 is

 

 

 

 

 

 

changed.

 

 

 

 

 

 

0: Decelerate to 0 Hz

 

 

 

02.06

Loss of ACI Signal

1: Coast to stop and display “AErr”

1

 

 

(4-20mA)

2: Continue operation by last frequency

 

 

 

 

 

 

 

 

 

 

command

 

 

 

 

 

 

0: by UP/DOWN Key

 

 

 

02.07

Up/Down Mode

1: Based on accel/decel time

0

 

 

2: Constant speed (Pr.02.08)

 

 

 

 

 

 

 

 

 

 

 

3: Pulse input unit (Pr.02.08)

 

 

 

 

 

 

 

 

 

 

 

 

Accel/Decel Rate of

 

 

 

 

 

 

Change of

 

 

 

 

02.08

UP/DOWN

0.01~10.00 Hz

0.01

 

 

 

 

Operation with

 

 

 

 

 

 

Constant Speed

 

 

 

 

 

 

 

0: Digital keypad UP/DOWN keys or Multi-

 

 

 

 

 

 

function Inputs UP/DOWN. Last used

 

 

 

 

 

 

frequency saved.

 

 

 

 

 

Source of Second

1: 0 to +10V from AVI

0

 

 

 

 

2: 4 to 20mA from ACI or 0 to +10V from

 

 

02.09

Frequency

 

 

AVI2

 

 

 

 

 

Command

 

 

 

 

 

3: RS-485 (RJ-45)/USB communication

 

 

 

 

 

 

 

 

 

 

 

 

4: Digital keypad potentiometer

 

 

 

 

 

 

5: CANopen communication

 

 

 

 

 

 

For VFD*E*C models, the factory setting is

5

 

 

 

 

Combination of the

0: First Master Frequency Command

 

 

 

 

 

1: First Master Frequency Command+

 

 

 

 

 

First and Second

 

 

 

02.10

Second Master Frequency Command

0

 

 

Master Frequency

 

 

 

 

2: First Master Frequency Command -

 

 

 

 

 

Command

 

 

 

 

 

Second Master Frequency Command

 

 

 

 

 

 

 

 

 

02.11

Keypad Frequency

0.00 to 600.0Hz

60.00

 

 

 

 

 

Command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication

0.00 to 600.0Hz

 

 

 

02.12

Frequency

 

60.00

 

 

 

 

Command

 

 

 

 

 

 

The Selections for

0: Save Keypad & Communication

 

 

 

 

 

Saving Keypad or

Frequency

 

 

 

02.13

Communication

1: Save Keypad Frequency only

0

 

 

 

 

Frequency

2: Save Communication Frequency only

 

 

 

 

 

Command

 

 

 

 

English- 15

Image 15
Contents Preface Voltage Class 115V Class SpecificationsGeneral Specifications SL2 VT2 TL3 WT3 Basic Wiring Diagram+/B1 PNP mode without external power Signal DescriptionDescription of the Digital Keypad KPE-LE02 Optional To shift data Operation Steps of the Digital KeypadTerminal Explanations Power Terminals and Control TerminalsFrame Power Terminals Torque Wire Wire Type Terminal SymbolSpecification for the Control Terminals Control Terminals ExplanationsFrame Control Terminals Torque Group 0 User Parameters Summary of Parameter SettingsVFD*E*C models Explanation Settings FactoryModels Not for VFD*E*C models Group 1 Basic Parameters For VFD*E*C models, the factory setting isExplanation Settings Factory AVI2 Group 2 Operation Method ParametersUP/DOWN Explanation Settings Factory Setting For VFD*E*C modelsGroup 3 Output Function Parameters Group 4 Input Function Parameters Not for VFD*E*CFor VFD*E*C For VFD*E*C models Models, the factory Quick Stop Only for VFD*E*C models Setting is 23.Bit5=1MI6 used by PLC Group 6 Protection Parameters Group 5 Multi-Step Speeds ParametersExplanation Settings Factory FLA Group 7 Motor ParametersSetting Group 8 Special Parameters Group 9 Communication Parameters Group 10 PID Control Parameters Address only for VFD*E*C modelsOnly for VFD*E*C Only for VFD*E*C ModelsParameters for Extension Card MO5/RA5 MO2/RA2MO3/RA3 MO4/RA4Explanation Settings Quick Stop Only for VFD*E*C models Fault Codes Group 13 PG function Parameters for Extension CardPLC not for VFD*E*C models Overload Over currentOver voltage OverheatingOC hardware error Fault Fault Descriptions Corrective Actions Name OverloadCC current clamp OV hardware error GFF hardware errorPID feedback signal error Fault Fault Descriptions Corrective Actions NamePhase error Temperature sensor errorFrame Dimensions are in mm inchH1 H Frame C Unit mm inch