Delta Electronics VFD-XXXE Over current, Over voltage, Overheating, Overload, Rated current for a

Page 31

 

Fault

Fault Descriptions

 

Corrective Actions

 

 

Name

 

 

 

 

 

 

 

 

 

Low voltage

1.

Check whether the input voltage falls within

 

 

The AC motor drive detects

 

the AC motor drive rated input voltage range.

 

 

that the DC bus voltage has

2.

Check whether the motor has sudden load.

 

 

fallen below its minimum

3.

Check for correct wiring of input power to R-S-

 

 

value.

 

T (for 3-phase models) without phase loss.

 

 

 

1.

Check if motor power corresponds with the AC

 

 

 

 

motor drive output power.

 

 

 

2.

Check the wiring connections to U/T1, V/T2,

 

 

 

 

W/T3 for possible short circuits.

 

 

 

3.

Check the wiring connections between the AC

 

 

 

 

motor drive and motor for possible short

 

 

 

 

circuits, also to ground.

 

 

Over current

4.

Check for loose contacts between AC motor

 

 

 

drive and motor.

 

 

Abnormal increase in current.

 

 

 

5.

Increase the Acceleration Time.

 

 

 

 

 

 

6.

Check for possible excessive loading

 

 

 

 

conditions at the motor.

 

 

 

7.

If there are still any abnormal conditions when

 

 

 

 

operating the AC motor drive after a short-

 

 

 

 

circuit is removed and the other points above

 

 

 

 

are checked, it should be sent back to

 

 

 

 

manufacturer.

 

 

 

1.

Check if the input voltage falls within the rated

 

 

 

 

AC motor drive input voltage range.

 

 

Over voltage

2.

Check for possible voltage transients.

 

 

3.

DC-bus over-voltage may also be caused by

 

 

The DC bus voltage has

 

 

 

motor regeneration. Either increase the Decel.

 

 

exceeded its maximum

 

 

 

 

Time or add an optional brake resistor (and

 

 

allowable value.

 

 

 

 

brake unit).

 

 

 

 

 

 

 

4.

Check whether the required brake power is

 

 

 

 

within the specified limits.

 

 

 

1.

Ensure that the ambient temperature falls

 

 

 

 

within the specified temperature range.

 

 

 

2.

Make sure that the ventilation holes are not

 

 

Overheating

 

obstructed.

 

 

3.

Remove any foreign objects from the

 

 

Heat sink temperature too high

 

heatsinks and check for possible dirty heat

 

 

 

 

sink fins.

 

 

 

4.

Check the fan and clean it.

 

 

 

5.

Provide enough spacing for adequate

 

 

 

 

ventilation.

 

 

Overload

 

 

 

 

 

The AC motor drive detects

1.

Check whether the motor is overloaded.

 

 

excessive drive output current.

2.

Reduce torque compensation setting in

 

 

NOTE: The AC motor drive

 

Pr.07.02.

 

 

can withstand up to 150% of

3. Take the next higher power AC motor drive

 

 

the rated current for a

 

model.

 

 

maximum of 60 seconds.

 

 

 

 

 

 

1.

Check for possible motor overload.

 

 

 

2.

Check electronic thermal overload setting.

 

 

Overload 1

3.

Use a higher power motor.

 

 

Internal electronic overload trip

4.

Reduce the current level so that the drive

 

 

 

 

output current does not exceed the value set by

 

 

 

 

the Motor Rated Current Pr.07.00.

English- 31

Image 31
Contents Preface Voltage Class 115V Class SpecificationsGeneral Specifications SL2 VT2 TL3 WT3 Basic Wiring Diagram+/B1 Signal Description PNP mode without external powerDescription of the Digital Keypad KPE-LE02 Optional To shift data Operation Steps of the Digital KeypadTerminal Explanations Power Terminals and Control TerminalsFrame Power Terminals Torque Wire Wire Type Terminal SymbolControl Terminals Explanations Specification for the Control TerminalsFrame Control Terminals Torque Group 0 User Parameters Summary of Parameter SettingsVFD*E*C models Explanation Settings FactoryModels Not for VFD*E*C modelsGroup 1 Basic Parameters For VFD*E*C models, the factory setting isExplanation Settings Factory AVI2 Group 2 Operation Method ParametersUP/DOWN For VFD*E*C models Explanation Settings Factory SettingGroup 3 Output Function Parameters Group 4 Input Function Parameters Not for VFD*E*CFor VFD*E*C For VFD*E*C models Models, the factory Quick Stop Only for VFD*E*C models Setting is 23.Bit5=1MI6 used by PLC Group 6 Protection Parameters Group 5 Multi-Step Speeds ParametersExplanation Settings Factory FLA Group 7 Motor ParametersSetting Group 8 Special Parameters Group 9 Communication Parameters Group 10 PID Control Parameters Address only for VFD*E*C modelsOnly for VFD*E*C Only for VFD*E*C ModelsParameters for Extension Card MO5/RA5 MO2/RA2MO3/RA3 MO4/RA4Explanation Settings Quick Stop Only for VFD*E*C models Group 13 PG function Parameters for Extension Card Fault CodesPLC not for VFD*E*C models Overload Over currentOver voltage OverheatingOC hardware error Fault Fault Descriptions Corrective Actions Name OverloadCC current clamp OV hardware error GFF hardware errorPID feedback signal error Fault Fault Descriptions Corrective Actions NamePhase error Temperature sensor errorFrame Dimensions are in mm inchH1 H Frame C Unit mm inch