Delta Electronics VFD-XXXE quick start Group 2 Operation Method Parameters, AVI2

Page 14

 

 

Pr.

Explanation

Settings

Factory

NOTE

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

Mid-Point

0.10 to 600.0 Hz

 

 

 

01.40

Frequency (Fmid)

1.50

 

 

 

 

 

(Motor 3)

 

 

 

 

01.41

Mid-Point Voltage

115V/230V series: 0.1V to 255.0V

10.0

 

 

(Vmid) (Motor 3)

460V series: 0.1V to 510.0V

20.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01.42

Minimum Output

0.10 to 600.0 Hz

1.50

 

 

Frequency (Fmin)

 

 

 

 

 

(Motor 3)

 

 

 

 

01.43

Minimum Output

115V/230V series: 0.1V to 255.0V

10.0

 

 

Voltage (Vmin)

460V series: 0.1V to 510.0V

20.0

 

 

 

 

 

(Motor 3)

 

 

 

 

 

Group 2 Operation Method Parameters

 

 

 

 

 

 

 

0: Digital keypad UP/DOWN keys or Multi-

 

 

 

 

 

 

 

function Inputs UP/DOWN. Last used

 

 

 

 

 

 

 

frequency saved.

 

 

 

 

 

 

Source of First

1: 0 to +10V from AVI

 

 

 

 

 

 

2: 4 to 20mA from ACI or 0 to +10V from

1

 

 

02.00

Master Frequency

 

 

AVI2

 

 

 

 

 

 

Command

 

 

 

 

 

 

3: RS-485 (RJ-45)/USB communication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4: Digital keypad potentiometer

 

 

 

 

 

 

 

5: CANopen communication

 

 

 

 

 

 

 

For VFD*E*C models, the factory setting is

5

 

 

 

 

 

 

0: Digital keypad

 

 

 

 

 

 

 

1: External terminals. Keypad STOP/RESET

 

 

 

 

 

 

 

enabled.

 

 

 

 

 

 

 

2: External terminals. Keypad STOP/RESET

 

 

 

 

 

 

Source of First

disabled.

1

 

 

 

 

 

3: RS-485 (RJ-45)/USB communication.

 

 

02.01

Operation

 

 

Keypad STOP/RESET enabled.

 

 

 

 

 

 

Command

 

 

 

 

 

 

4: RS-485 (RJ-45)/USB communication.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Keypad STOP/RESET disabled.

 

 

 

 

 

 

 

5: CANopen communication. Keypad

 

 

 

 

 

 

 

STOP/RESET disabled.

 

 

 

 

 

 

 

For VFD*E*C models, the factory setting is

5

 

 

 

 

 

 

0: STOP: ramp to stop; E.F.: coast to stop

 

 

 

02.02

Stop Method

1: STOP: coast to stop; E.F.: coast to stop

0

 

 

2: STOP: ramp to stop; E.F.: ramp to stop

 

 

 

 

 

 

3: STOP: coast to stop; E.F.: ramp to stop

 

 

 

 

 

 

PWM Carrier

 

 

 

 

02.03

Frequency

1 to 15kHz

8

 

 

 

 

 

Selections

 

 

 

 

 

 

 

Motor Direction

0: Enable forward/reverse operation

 

 

 

02.04

1: Disable reverse operation

0

 

 

Control

 

 

 

 

 

2: Disabled forward operation

 

 

 

 

 

 

 

 

 

 

English- 14

Image 14
Contents Preface Specifications Voltage Class 115V ClassGeneral Specifications Basic Wiring Diagram SL2 VT2 TL3 WT3+/B1 Description of the Digital Keypad KPE-LE02 Optional PNP mode without external powerSignal Description Operation Steps of the Digital Keypad To shift dataTerminal Symbol Power Terminals and Control TerminalsFrame Power Terminals Torque Wire Wire Type Terminal ExplanationsFrame Control Terminals Torque Specification for the Control TerminalsControl Terminals Explanations Summary of Parameter Settings Group 0 User ParametersNot for VFD*E*C models Explanation Settings FactoryModels VFD*E*C modelsFor VFD*E*C models, the factory setting is Group 1 Basic ParametersExplanation Settings Factory Group 2 Operation Method Parameters AVI2UP/DOWN Group 3 Output Function Parameters Explanation Settings Factory SettingFor VFD*E*C models Not for VFD*E*C Group 4 Input Function ParametersQuick Stop Only for VFD*E*C models Setting is 23. For VFD*E*C For VFD*E*C models Models, the factoryBit5=1MI6 used by PLC Group 5 Multi-Step Speeds Parameters Group 6 Protection ParametersExplanation Settings Factory Group 7 Motor Parameters FLASetting Group 8 Special Parameters Group 9 Communication Parameters Only for VFD*E*C Models Address only for VFD*E*C modelsOnly for VFD*E*C Group 10 PID Control ParametersParameters for Extension Card MO4/RA4 MO2/RA2MO3/RA3 MO5/RA5Explanation Settings Quick Stop Only for VFD*E*C models PLC not for VFD*E*C models Fault CodesGroup 13 PG function Parameters for Extension Card Overheating Over currentOver voltage OverloadGFF hardware error Fault Fault Descriptions Corrective Actions Name OverloadCC current clamp OV hardware error OC hardware errorTemperature sensor error Fault Fault Descriptions Corrective Actions NamePhase error PID feedback signal errorDimensions are in mm inch FrameH1 H Frame C Unit mm inch