Delta Electronics VFD-XXXE quick start Bit5=1MI6 used by PLC

Page 19

 

 

Pr.

Explanation

Settings

Factory

NOTE

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

Bit11:MI12

 

 

 

 

 

 

 

0:N.O., 1:N.C.

 

 

 

 

 

 

 

P.S.:MI1 to MI3 will be invalid when it is 3-

 

 

 

 

 

 

 

wire control.

 

 

 

 

 

 

Digital Terminal

 

 

 

 

04.10

Input Debouncing

1 to 20 (*2ms)

1

 

 

 

 

 

Time

 

 

 

 

 

04.11

Min AVI Voltage

0.0 to 10.0V

0.0

 

 

 

04.12

Min AVI Frequency

0.0 to 100.0%

0.0

 

 

 

04.13

Max AVI Voltage

0.0 to 10.0V

10.0

 

 

 

04.14

Max AVI Frequency

0.0 to 100.0%

100.0

 

 

 

04.15

Min ACI Current

0.0 to 20.0mA

4.0

 

 

 

04.16

Min ACI Frequency

0.0 to 100.0%

0.0

 

 

 

04.17

Max ACI Current

0.0 to 20.0mA

20.0

 

 

04.18

Max ACI Frequency

0.0 to 100.0%

100.0

 

 

 

 

 

 

 

 

 

 

04.19

ACI/AVI2 Selection

0: ACI

0

 

 

1: AVI2

 

 

 

 

 

 

 

 

 

04.20

Min AVI2 Voltage

0.0 to 10.0V

0.0

 

 

 

 

 

 

 

 

 

04.21

Min AVI2 Frequency

0.0 to 100.0%

0.0

 

 

 

 

 

 

 

 

 

04.22

Max AVI2 Voltage

0.0 to 10.0V

10.0

 

 

 

 

 

 

 

 

 

 

04.23

Max AVI2

0.0 to 100.0%

100.0

 

 

Frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

Read only.

 

 

 

 

 

 

 

Bit0=1:MI1 used by PLC

 

 

 

 

 

 

 

Bit1=1:MI2 used by PLC

 

 

 

 

 

 

The Digital Input

Bit2=1:MI3 used by PLC

 

 

 

 

 

 

Bit3=1:MI4 used by PLC

 

 

 

04.24

Used by PLC

Bit4=1:MI5 used by PLC

##

 

 

(NOT for VFD*E*C

Bit5=1:MI6 used by PLC

 

 

 

 

 

 

 

 

 

 

 

models)

Bit6=1: MI7 used by PLC

 

 

 

 

 

 

 

Bit7=1: MI8 used by PLC

 

 

 

 

 

 

 

Bit8=1: MI9 used by PLC

 

 

 

 

 

 

 

Bit9=1: MI10 used by PLC

 

 

 

 

 

 

 

Bit10=1: MI11 used by PLC

 

 

 

 

 

 

 

Bit11=1: MI12 used by PLC

 

 

 

 

 

 

The Analog Input

Read only.

 

 

 

 

 

 

Bit0=1:AVI used by PLC

 

 

 

 

 

 

Used by PLC

 

 

 

04.25

Bit1=1:ACI/AVI2 used by PLC

##

 

 

(NOT for VFD*E*C

 

 

 

 

 

Bit2=1: AI1 used by PLC

 

 

 

 

 

 

models)

 

 

 

 

 

 

Bit3=1: AI2 used by PLC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Read only.

 

 

 

 

 

 

 

Bit0: MI1 Status

 

 

 

 

 

 

 

Bit1: MI2 Status

 

 

 

 

 

 

Display the Status of

Bit2: MI3 Status

 

 

 

04.26

Multi-function Input

Bit3: MI4 Status

##

 

 

 

 

 

Terminal

Bit4: MI5 Status

 

 

 

 

 

 

 

Bit5: MI6 Status

 

 

 

 

 

 

 

Bit6: MI7 Status

 

 

 

 

 

 

 

Bit7: MI8 Status

 

 

 

English- 19

Image 19
Contents Preface Voltage Class 115V Class SpecificationsGeneral Specifications SL2 VT2 TL3 WT3 Basic Wiring Diagram+/B1 Signal Description PNP mode without external powerDescription of the Digital Keypad KPE-LE02 Optional To shift data Operation Steps of the Digital KeypadTerminal Explanations Power Terminals and Control TerminalsFrame Power Terminals Torque Wire Wire Type Terminal SymbolControl Terminals Explanations Specification for the Control TerminalsFrame Control Terminals Torque Group 0 User Parameters Summary of Parameter SettingsVFD*E*C models Explanation Settings FactoryModels Not for VFD*E*C modelsGroup 1 Basic Parameters For VFD*E*C models, the factory setting isExplanation Settings Factory AVI2 Group 2 Operation Method ParametersUP/DOWN For VFD*E*C models Explanation Settings Factory Setting Group 3 Output Function Parameters Group 4 Input Function Parameters Not for VFD*E*CFor VFD*E*C For VFD*E*C models Models, the factory Quick Stop Only for VFD*E*C models Setting is 23.Bit5=1MI6 used by PLC Group 6 Protection Parameters Group 5 Multi-Step Speeds ParametersExplanation Settings Factory FLA Group 7 Motor ParametersSetting Group 8 Special Parameters Group 9 Communication Parameters Group 10 PID Control Parameters Address only for VFD*E*C modelsOnly for VFD*E*C Only for VFD*E*C ModelsParameters for Extension Card MO5/RA5 MO2/RA2MO3/RA3 MO4/RA4Explanation Settings Quick Stop Only for VFD*E*C models Group 13 PG function Parameters for Extension Card Fault CodesPLC not for VFD*E*C models Overload Over currentOver voltage OverheatingOC hardware error Fault Fault Descriptions Corrective Actions Name OverloadCC current clamp OV hardware error GFF hardware errorPID feedback signal error Fault Fault Descriptions Corrective Actions NamePhase error Temperature sensor errorFrame Dimensions are in mm inchH1 H Frame C Unit mm inch