Murphy CE-05171N manual 00060, More Menu, General Timer Setup Screen

Page 27

6.3.7 General Timer Setup

 

C

TM

 

 

GENERAL TIMER SETUP

 

B1

TIMER

B2

TIMER

 

C TIMER

 

S1

TIMER

 

S2

TIMER

 

(0 - 999)

00060

___________________________________

▼▲

ENTER-EDIT

 

MORE MENU

General Timer Setup Screen

User may edit all general purpose timers. Generally, global timers affect engine operation. They also help define an event.

a)B1: All event types can be associated with, and locked out by, a Bx timer. B1 is the first global timer used for delaying an event condition detection. The timer starts in a running State (10 – 13) depending on which have been marked ‘In Use’. B1 is also known as the “Lockout Timer.”

b)B2: The second global timer used for delaying an event condition detection. B2 is also known as a secondary “Lockout Timer.”

c)C: The delay allowing a clear reading before beginning testing for the arming of Class C events. The default and typical time for most applications is 2 seconds.

d)S: Users have up to five (5) options to assign additional special global timers to signals. The Sx timers begin con- currently with the Bx timers.

e)No Flow: The global delay used for delaying the triggering of a No Flow event. This global no flow timer is enabled after B1 expires, and begins timing after any of the no flow transi- tion times configured in the digital input dialog expires.

f)Test: Time given to allow for maintenance testing of end devices without triggering a fault or shutdown condition. The timer initiates when switched to test mode.

g)Ignition Off Delay: Time delay before the assigned ignition output turns off. This is typically used to burn remaining fuel vapors after the fuel valve is turned off.

h)Ignition On Delay: Time delay before the assigned ignition output turns on. This is typically used to delay ignition until engine crank rollover can occur.

i)Fuel On Delay: Time delay before the assigned fuel valve output is turns on. This is typically used to delay fuel until ignition has been turned on.

CE-05171N page 27 of 44

Image 27
Contents Centuriontm Warranty Table of Contents Communications Basic Components and Key Features of the C3TM Series OverviewOptional Components Digital Inputs DI Input/Output TypesThermocouple Inputs TC Analog Inputs AIDigital Outputs do Magnetic Pickup MPUC3-1-A Analog Outputs AO Hazardous Area OperationMounting the Centurion C3-3 Display Hardware Installation and WiringPower Supply Wiring Power Centurion C3-1 I/O Module Mounting the Centurion ControllerWiring the Centurion C3-3 Display Wiring the Centurion C3-1/C3-2 TTD-98055N page 14 Features Fn Function Key Home ESC ACKRUN Stop RUN/STOP Test Status Area Operational/Process Information AreaController Version Mconfig PRO VEROperational Screens Display VERShutdown History Panel ESD Event History Panel ESD Panel Reset LOW Suct PressDISC. Temperature Cooler TemperatureVDC Battery ENG SpeedAmbient Temperature OIL PRS WTR Temp PSISetup Screens and Menus Enter PasswordENTER-ACCEPT ESC-CANCEL Digital Input Digital Outputs SetupAnalog Inputs Setup Digital InputsESC Exit this Menu Analog Input 1 Setup ScreenAnalog Outputs Setup ANOUT01 ENTER-SUBMENU More Menus Analog Output 1 Setup ScreenThermocouple Thermocouple SetupThermocouple 1 Setup Type Offset Thermocouple 1 Setup Thermocouple OffsetMore Menu General Timer SetupGeneral Timer Setup Screen 00060RESET-RESET Timer ESC-EXIT this Menu Maintenance Timer SetupMaintenance Timer Setup Screen Maintenance Timer Setup Time Remaining Change OILControl Output Throttle ENTER-MENU More Menu Setpoints Setup ENTER-SUBMENU More MenusSetpoints Setup LO Suct PRS Control Output 1 Setup00004 PID Setup ENTER-SUBMENU More MenusPID Setup Screen PID 1 Setup ScreenPort Response Delay Port 1 Baud Rate NO-FLOW Input # 1 Setup Cycle Time SEC Total Cycles Cycle Timer SEC More MenusLube NO-FLOW Status Cycle TIME-INPUT # Prev 28% YESSuper User Menu Screen Digital Input Status =CLOSED Diagnostico-Digital Inputs ScreenAnalog Output Status AI 1 ENG Speed Must be in Test Mode ESC-CANCELSuction PID ESC-EXIT PID Diagnostics ENTER-SUBMENU More MenusCommunication Status Modbus Register ENTER-EDIT More MenusCommunication Ports Remote Mode Commands Reset and RUN/STOPCommunications Additional Navigational AidsPort 2 USB Firmware Download Screen Firmware Update Mode Power and COM Link Must be MaintainedInvalid Configuration Press Setup to Access Download Menu Configuration Fault ScreenComm Fail Screen Modbus Protocol Terminal Emulator GlossaryBack Panel LED Description AppendicesHow To Order