Murphy CE-05171N PID Setup ENTER-SUBMENU More Menus, PID Setup Screen, 00004, PID 1 Setup Screen

Page 30

6.3.11 PID Setup

 

C

TM

 

 

 

PID SETUP

 

 

PID 1

 

PID 2

 

 

PID 3

 

 

PID 4

 

___________________________________

PID 1

 

 

___________________________________

▼▲

ENTER-SUBMENU

 

 

▼ ▼

MORE MENUS

 

 

 

 

 

 

PID Setup Screen

 

 

C

TM

 

 

 

 

PID 1 SETUP

 

 

OVERRIDE RAMP TIME

 

OVERRIDE RAMP AMOUNT

 

 

RAMP TIME

MAX % OF CHANGE

SETPOINT

___________________________________

 

00004

___________________________________

▼▲

ENTER-EDIT

 

 

ESC-EXIT THIS MENU

 

PID 1 Setup Screen

h)Assign value to Decrease Changeover Off Time. (Set fixed off-time for single pulse on direction change for Decrease).

For more on Control Output, please refer to the Centurion Configurable Controller Programming Manual.

Users may view and edit up to four (4) MConfigPro software con- figured Proportional Integral Derivative (PID) calculation loops.

A PID provides a constant feed back loop, in which the PID can correct for a measured process variable against a desired set point, output the corrective action to the process and wait for and recalculate the next measurement.

The ultimate goal of the PID is to reduce the error to zero.

During the time a PID is enabled, the PID always overrides a control output. Recall that PID 1 is assigned its control from control output 1, PID 2 from control output 2, and so on.

To View and Edit PID Settings:

1)Over Ride Ramp Time: Assign a time interval value to wait before making the next adjustment.

2)Over Rid Ramp Amount: Determine the increments in a given direction (positive or negative) that the set point should be altered to regain balanced processes. In the example of the discharge and suction pressure application, this value would indicate how much the PID should resist its goal in reaching the set point.

3)Ramp Time: Assign a time interval for the PID to calculate error.

4)Over Ride Max Change: Assign a maximum allowed change. This represents the total amount of change allowed into or out of the ramp amount from the set point. The maximum change value should be large enough to effect change.

5)Set Point: Assign the desired goal—the target feedback base value.

6)DeadBand: Assign a value around the set point during which the PID will not calculate error.

7)Minimum Output: Assign a percentage as minimum output.

8)Maximum Output: Assign a percentage as maximum output.

9)Proportional: Adjust the output by a value that is propor- tional to the change of error.

10)Integral: To prevent the PID from oscillating or over- shooting the set point, assign a value to “reset” the system to produce zero error, or nudge the process variable to the set point. This value is typically set to zero.

11)Derivative: Assign a value to the rate of change of error. This value is typically set to zero.

12)Max Override Change: Assign a percentage rate of change over which would cause harm to the system.

For more on PID, please refer to the Centurion Configurable Controller Programming Manual.

CE-05171N page 30 of 44

Image 30
Contents Centuriontm Warranty Table of Contents Communications Basic Components and Key Features of the C3TM Series OverviewOptional Components Input/Output Types Digital Inputs DIAnalog Inputs AI Thermocouple Inputs TCMagnetic Pickup MPU Digital Outputs doC3-1-A Hazardous Area Operation Analog Outputs AOMounting the Centurion Controller Hardware Installation and WiringPower Supply Wiring Power Centurion C3-1 I/O Module Mounting the Centurion C3-3 DisplayWiring the Centurion C3-3 Display Wiring the Centurion C3-1/C3-2 TTD-98055N page 14 Features Home ESC ACK Fn Function KeyRUN Stop RUN/STOP Test Operational/Process Information Area Status AreaDisplay VER Mconfig PRO VEROperational Screens Controller VersionCooler Temperature Event History Panel ESD Panel Reset LOW Suct PressDISC. Temperature Shutdown History Panel ESDOIL PRS WTR Temp PSI Battery ENG SpeedAmbient Temperature VDCSetup Screens and Menus Enter PasswordENTER-ACCEPT ESC-CANCEL Digital Inputs Digital Outputs SetupAnalog Inputs Setup Digital InputAnalog Output 1 Setup Screen Analog Input 1 Setup ScreenAnalog Outputs Setup ANOUT01 ENTER-SUBMENU More Menus ESC Exit this MenuThermocouple 1 Setup Thermocouple Offset Thermocouple SetupThermocouple 1 Setup Type Offset Thermocouple00060 General Timer SetupGeneral Timer Setup Screen More MenuMaintenance Timer Setup Time Remaining Change OIL Maintenance Timer SetupMaintenance Timer Setup Screen RESET-RESET Timer ESC-EXIT this MenuControl Output 1 Setup Setpoints Setup ENTER-SUBMENU More MenusSetpoints Setup LO Suct PRS Control Output Throttle ENTER-MENU More MenuPID 1 Setup Screen PID Setup ENTER-SUBMENU More MenusPID Setup Screen 00004Port Response Delay Port 1 Baud Rate NO-FLOW Input # 1 Setup Cycle Time SEC Total Cycles Cycle Timer SEC More MenusLube NO-FLOW Status Cycle TIME-INPUT # Prev 28% YESSuper User Menu Screen Diagnostico-Digital Inputs Screen Digital Input Status =CLOSEDMust be in Test Mode ESC-CANCEL Analog Output Status AI 1 ENG SpeedENTER-EDIT More Menus PID Diagnostics ENTER-SUBMENU More MenusCommunication Status Modbus Register Suction PID ESC-EXITAdditional Navigational Aids Remote Mode Commands Reset and RUN/STOPCommunications Communication PortsPort 2 USB Firmware Update Mode Power and COM Link Must be Maintained Firmware Download ScreenInvalid Configuration Press Setup to Access Download Menu Configuration Fault ScreenComm Fail Screen Modbus Protocol Glossary Terminal EmulatorAppendices Back Panel LED DescriptionHow To Order