Murphy CE-05171N Comm Fail Screen, Invalid Configuration Press Setup to Access Download Menu

Page 40

7.2.6 Error Messages

There may be occasion when an invalid configuration error might display because the configuration between the Centurion controller and its devices are out of synch--that is to say the checksums do not match. In fact, the invalid configuration screen will appear briefly after downloading configurations until comparisons are made.

Field testers may decide to ignore the message, if the user knows that the changes are not critical. The user may direct the error message to be ignored through a setting at the super user (password protected) menu. At CONFIG FAIL DISABLE, the user would select Yes to ignore the data mismatch.

The setting is temporary as once power is cycled on the Display, the error message will continue until comparisons between the devices yield no configuration mismatch.

However, if the user knows of changes that might have resulted from changes made fine tuning in the field and wants to synchronize the data, he may choose to do so and there are a couple of options available.

A super user could choose to also download the configuration from the super user menu on C3-3 Display.

A user who without access to the super user menu could activate the download through the Special Jump Code 35.

C TM

CONTROLLER COM FAIL!

PRESS SETUP IF COM

PORT SETTINGS NEED

TO BE MODIFIED.

Comm Fail Screen

This screen indicates that the controller is not responding to poll requests. There are only two ways to exit this screen, either by normal responses resuming or if the SETUP/ENTER key is pressed.

This screen will be displayed when a configuration fault is detected.

Possible sources of the fault include a corrupt or missing con- figuration in the display, a corrupt or missing configuration in the controller or a mismatch of configurations in the display and controller.

C TM

INVALID CONFIGURATION

PRESS SETUP TO ACCESS

DOWNLOAD MENU

Note that this error message does not always indicate a prob- lem, but may only signify that initial comparisons between devices do not match. This screen will appear briefly after configuration downloads and may appear briefly after initial communication is established until comparisons are com- plete.

The fault can be resolved by downloading the proper configu- ration to one or both devices.

Configuration Fault Screen

CE-05171N page 40 of 44

Image 40
Contents Centuriontm Warranty Table of Contents Communications Overview Basic Components and Key Features of the C3TM SeriesOptional Components Input/Output Types Digital Inputs DIAnalog Inputs AI Thermocouple Inputs TCMagnetic Pickup MPU Digital Outputs doC3-1-A Hazardous Area Operation Analog Outputs AOHardware Installation and Wiring Power Supply Wiring Power Centurion C3-1 I/O ModuleMounting the Centurion Controller Mounting the Centurion C3-3 DisplayWiring the Centurion C3-3 Display Wiring the Centurion C3-1/C3-2 TTD-98055N page 14 Features Home ESC ACK Fn Function KeyRUN Stop RUN/STOP Test Operational/Process Information Area Status AreaMconfig PRO VER Operational ScreensDisplay VER Controller VersionEvent History Panel ESD Panel Reset LOW Suct Press DISC. TemperatureCooler Temperature Shutdown History Panel ESDBattery ENG Speed Ambient TemperatureOIL PRS WTR Temp PSI VDCEnter Password Setup Screens and MenusENTER-ACCEPT ESC-CANCEL Digital Outputs Setup Analog Inputs SetupDigital Inputs Digital InputAnalog Input 1 Setup Screen Analog Outputs Setup ANOUT01 ENTER-SUBMENU More MenusAnalog Output 1 Setup Screen ESC Exit this MenuThermocouple Setup Thermocouple 1 Setup Type OffsetThermocouple 1 Setup Thermocouple Offset ThermocoupleGeneral Timer Setup General Timer Setup Screen00060 More MenuMaintenance Timer Setup Maintenance Timer Setup ScreenMaintenance Timer Setup Time Remaining Change OIL RESET-RESET Timer ESC-EXIT this MenuSetpoints Setup ENTER-SUBMENU More Menus Setpoints Setup LO Suct PRSControl Output 1 Setup Control Output Throttle ENTER-MENU More MenuPID Setup ENTER-SUBMENU More Menus PID Setup ScreenPID 1 Setup Screen 00004Port Response Delay Port 1 Baud Rate Cycle Timer SEC More Menus NO-FLOW Input # 1 Setup Cycle Time SEC Total CyclesLube NO-FLOW Status Cycle TIME-INPUT # Prev YES 28%Super User Menu Screen Diagnostico-Digital Inputs Screen Digital Input Status =CLOSEDMust be in Test Mode ESC-CANCEL Analog Output Status AI 1 ENG SpeedPID Diagnostics ENTER-SUBMENU More Menus Communication Status Modbus RegisterENTER-EDIT More Menus Suction PID ESC-EXITRemote Mode Commands Reset and RUN/STOP CommunicationsAdditional Navigational Aids Communication PortsPort 2 USB Firmware Update Mode Power and COM Link Must be Maintained Firmware Download ScreenConfiguration Fault Screen Invalid Configuration Press Setup to Access Download MenuComm Fail Screen Modbus Protocol Glossary Terminal EmulatorAppendices Back Panel LED DescriptionHow To Order