6.3Setup Screens and Menus

6.3.1Password Screen

C TM

 

ENTER PASSWORD

 

 

FOR SETUP MENUS

 

___________________________________

 

00000

▼▲

ENTER-ACCEPT

 

▼ ▼

ESC-CANCEL

 

 

 

 

Password Screen

C

TM

 

 

SUPER USER MENU

 

COM FAIL DISABLE

SETUP T/O DISABLE

 

CONFIG FAIL DISABLE

 

RESET FAULT HISTORY

 

RESET EVENT HISTORY

___________________________________

 

 

 

NO

 

___________________________________

 

 

▼▲

ENTER-EDIT

 

 

 

 

▼ ▼

MORE MENUS

 

 

 

 

 

 

 

 

 

Super User Menu Screen

 

 

 

C

TM

 

 

 

 

 

 

 

 

CONFIRATION DOWNLOAD

 

 

 

 

COM 1 CONFIG DOWNLOAD

 

 

 

COM 2 CONFIG DOWNLOAD

 

 

 

USB CONFIG DOWNLOAD

FIRMWARE DOWNLOAD

___________________________________

NO

___________________________________

▼▲ ENTER-EDIT ESC-EXIT THIS MENU

Download Only Screen

Some settings are password protected, including the setup screens. This is the first screen seen when the SETUP/ENTER key is pressed.

The password need only be entered once during any editing session. The password will reset when the editing session is exited, or is timed-out due to keyboard inactivity.

The cursor begins at the last digit on the right. The user can adjust the value of each digit with the up/down arrows while the left/right arrows are used to select the digit to edit.

Passwords are assigned using the MConfigPro software and each digit can range from zero to nine (except the first digit on the left) for a total range of 00000 to 65535 for the complete password.

The user will not be allowed to increment the selected digit if it would result in exceeding range limits.

There are three separate levels of passwords to accommodate several security needs:

“Standard” password – Allows access to every feature except the Super User menu. Valid Standard passwords can be zero or any number between 100 and 65535. If the Standard password is set to zero, the result is that anyone can have read/write access to setup menus.

“Super User” password – Adds the Super User menu to the Standard menus. Valid Super User passwords can be in the range of 100 to 65535. The Super User password can not be the same as the Standard password.

“Download Only” password – This Special 35 Jump Code allows access to a download menu and is set to a fixed value of 35. This allows a configuration to be downloaded in the event that the current passwords are lost or no initial configuration has been downloaded.

If the Standard password is not zero and a password of all zeroes is entered, the user will have “view only” access.

Inactivity Timeout: Setup procedures must be started and completed in a timely manner. Note that after 3 minutes without activity, the keypad returns the default operational screen and a password must be re-entered to return to the setup and edit menus.

CE-05171N page 23 of 44

Image 23
Contents Centuriontm Warranty Table of Contents Communications Optional Components Basic Components and Key Features of the C3TM SeriesOverview Digital Inputs DI Input/Output TypesThermocouple Inputs TC Analog Inputs AIDigital Outputs do Magnetic Pickup MPUC3-1-A Analog Outputs AO Hazardous Area OperationMounting the Centurion C3-3 Display Hardware Installation and WiringPower Supply Wiring Power Centurion C3-1 I/O Module Mounting the Centurion ControllerWiring the Centurion C3-3 Display Wiring the Centurion C3-1/C3-2 TTD-98055N page 14 Features Fn Function Key Home ESC ACKRUN Stop RUN/STOP Test Status Area Operational/Process Information AreaController Version Mconfig PRO VEROperational Screens Display VERShutdown History Panel ESD Event History Panel ESD Panel Reset LOW Suct PressDISC. Temperature Cooler TemperatureVDC Battery ENG SpeedAmbient Temperature OIL PRS WTR Temp PSIENTER-ACCEPT ESC-CANCEL Setup Screens and MenusEnter Password Digital Input Digital Outputs SetupAnalog Inputs Setup Digital InputsESC Exit this Menu Analog Input 1 Setup ScreenAnalog Outputs Setup ANOUT01 ENTER-SUBMENU More Menus Analog Output 1 Setup ScreenThermocouple Thermocouple SetupThermocouple 1 Setup Type Offset Thermocouple 1 Setup Thermocouple OffsetMore Menu General Timer SetupGeneral Timer Setup Screen 00060RESET-RESET Timer ESC-EXIT this Menu Maintenance Timer SetupMaintenance Timer Setup Screen Maintenance Timer Setup Time Remaining Change OILControl Output Throttle ENTER-MENU More Menu Setpoints Setup ENTER-SUBMENU More MenusSetpoints Setup LO Suct PRS Control Output 1 Setup00004 PID Setup ENTER-SUBMENU More MenusPID Setup Screen PID 1 Setup ScreenPort Response Delay Port 1 Baud Rate Lube NO-FLOW Status Cycle TIME-INPUT # Prev NO-FLOW Input # 1 Setup Cycle Time SEC Total CyclesCycle Timer SEC More Menus Super User Menu Screen 28%YES Digital Input Status =CLOSED Diagnostico-Digital Inputs ScreenAnalog Output Status AI 1 ENG Speed Must be in Test Mode ESC-CANCELSuction PID ESC-EXIT PID Diagnostics ENTER-SUBMENU More MenusCommunication Status Modbus Register ENTER-EDIT More MenusCommunication Ports Remote Mode Commands Reset and RUN/STOPCommunications Additional Navigational AidsPort 2 USB Firmware Download Screen Firmware Update Mode Power and COM Link Must be MaintainedComm Fail Screen Invalid Configuration Press Setup to Access Download MenuConfiguration Fault Screen Modbus Protocol Terminal Emulator GlossaryBack Panel LED Description AppendicesHow To Order