8.0 Glossary

Analog Input

Terminals A18 to A29 are analog inputs on the C3-1 Centurion main I/O module. Accepts

 

voltage signals within the range of (0 to 5) VDC or (4 to 20) mA and are compared to con-

 

troller set points or events.

Boot loader

Means by which the Centurion controller communicates with C3-3 Display and MConfigPro

 

to receive and transfer new or updated configurations and firmware; and ensure data and

 

configuration synchronization.

Controller Set points User defines normal operating range for the controller to optimize the equipment. Set points can also define some other threshold, exception or event that may require action. Multiple set points are often applied to a process and they may be manipulated as needed to meet changing conditions.

Dead band

The user set range at which input may fluctuate without the controller taking any action.

 

The range may be fixed or variable.

Digital Input

Terminals 30 to 61 are the digital input channels. User selects whether digital input is nor-

 

mally open (N/O), or normally closed (N/C). Users may also associate these inputs with

 

transition times for indicating no-flow conditions on divider blocks.

Event

Defines the action required by the controller in response to any number of parameters.

 

Event actions range from simple alarm message to emergency shutdown (ESD).

Magnetic Pick Up

Terminals 64 to 65 are for magnetic pick up.

Maximum

Maximum of engineering applied scale to the Offset and Span.

Minimum

Minimum of engineering applied scale to the Offset and Span.

No-Flow

Designed to protect against compressor or engine failures, the controller monitors the cycle

 

time of lubrication system cycles and if that cycle time falls under a user assigned value, the

 

controller will activate a defined associated action.

Offset

User defined value to correct for known variance in the raw data.

Panel Ready

In States, the first logical step in start up.

Permissive

A process condition, (Digital Input or Analog Set point), that must be met in order for the

 

engine to start.

Signal

An electrical quantity of voltage or current that is used to represent or signify some other

 

physical quantity.

Span

The difference between the full scale output and the offset as raw data.

Start Delay

A time delay function to prevent premature start up.

State

Predefined parameter of logical steps needed to successfully start and maintain an engine.

Terminal Emulator

Allows a user to modify the firmware to allow upload or download of a record to either the C3-3

 

display or the controller. Always download a configuration after a firmware change.

Thermocouple

A device for measuring temperature consisting of two dissimilar metals of high purity for an

 

accurate temperature/voltage relationship. User defines whether the calibration is J or K.

 

Terminals 1 to 17 are for thermocouple inputs.

CE-05171N page 42 of 44

Image 42
Contents Centuriontm Warranty Table of Contents Communications Basic Components and Key Features of the C3TM Series OverviewOptional Components Input/Output Types Digital Inputs DIAnalog Inputs AI Thermocouple Inputs TCMagnetic Pickup MPU Digital Outputs doC3-1-A Hazardous Area Operation Analog Outputs AOMounting the Centurion Controller Hardware Installation and WiringPower Supply Wiring Power Centurion C3-1 I/O Module Mounting the Centurion C3-3 DisplayWiring the Centurion C3-3 Display Wiring the Centurion C3-1/C3-2 TTD-98055N page 14 Features Home ESC ACK Fn Function KeyRUN Stop RUN/STOP Test Operational/Process Information Area Status AreaDisplay VER Mconfig PRO VEROperational Screens Controller VersionCooler Temperature Event History Panel ESD Panel Reset LOW Suct PressDISC. Temperature Shutdown History Panel ESDOIL PRS WTR Temp PSI Battery ENG SpeedAmbient Temperature VDCSetup Screens and Menus Enter PasswordENTER-ACCEPT ESC-CANCEL Digital Inputs Digital Outputs SetupAnalog Inputs Setup Digital InputAnalog Output 1 Setup Screen Analog Input 1 Setup ScreenAnalog Outputs Setup ANOUT01 ENTER-SUBMENU More Menus ESC Exit this MenuThermocouple 1 Setup Thermocouple Offset Thermocouple SetupThermocouple 1 Setup Type Offset Thermocouple00060 General Timer SetupGeneral Timer Setup Screen More MenuMaintenance Timer Setup Time Remaining Change OIL Maintenance Timer SetupMaintenance Timer Setup Screen RESET-RESET Timer ESC-EXIT this MenuControl Output 1 Setup Setpoints Setup ENTER-SUBMENU More MenusSetpoints Setup LO Suct PRS Control Output Throttle ENTER-MENU More MenuPID 1 Setup Screen PID Setup ENTER-SUBMENU More MenusPID Setup Screen 00004Port Response Delay Port 1 Baud Rate NO-FLOW Input # 1 Setup Cycle Time SEC Total Cycles Cycle Timer SEC More MenusLube NO-FLOW Status Cycle TIME-INPUT # Prev 28% YESSuper User Menu Screen Diagnostico-Digital Inputs Screen Digital Input Status =CLOSEDMust be in Test Mode ESC-CANCEL Analog Output Status AI 1 ENG SpeedENTER-EDIT More Menus PID Diagnostics ENTER-SUBMENU More MenusCommunication Status Modbus Register Suction PID ESC-EXITAdditional Navigational Aids Remote Mode Commands Reset and RUN/STOPCommunications Communication PortsPort 2 USB Firmware Update Mode Power and COM Link Must be Maintained Firmware Download ScreenInvalid Configuration Press Setup to Access Download Menu Configuration Fault ScreenComm Fail Screen Modbus Protocol Glossary Terminal EmulatorAppendices Back Panel LED DescriptionHow To Order