3.5Control

The server cabinet temperature is controlled by the fan control board VR 2.2. A air temperature sensor continuously measures the temperature of the server cabinet (server feed air). The air circulation flow rate is controlled by the fan speed according to the current thermal load.

At temperatures lower than 20°C / 68°F fans rotate at 75% of maximum speed.

Between 20°C / 68°F and 23°C / 73,4°F speed increases proportional to the temperature up to 96% of maximum speed.

The failure of the temperature sensor set the fans to maximum speed.

Air temperature sensor

PDU – Box*)

*) by 12 kW rack under the roof

Status LED:

Green

System OK

Yellow

fault controller cooling/fans or rear door open

Red

fault controller cooling/fans and rear door open

Fuses for each fan and switching power supply

Space for optional equipment

Service socket and fuse

CoolTherm front view

The water flow rate is controlled by a three-wayvalve depending on thermal load. (distribution flow control) Before all a undertemperature at part load operation can be avoided.

By using a blind sieve in the bypass a hydraulic volume control could be achieved (two way valve function).

In case of failure the valve opens and the all the chilled water flows through the heat exchanger. From 16°C / 60,8°F to 19°C / 66,2°F the three-way valve controls the water flow rate from 0% to 100% of the nominal flow rate.

CoolTherm

01_998_330_0_k

page / Seite 15/83

Image 17
Contents Liebert XDK-WRack Enclosure With Integrated Liquid Cooling Page Manual CoolTherm CoolTherm ContentsAbstract Safety Work safety symbolsSafety instructions Correct use Operating conditionsDescription General function Principle of operation of cooling Bottom plate with cutouts Rear Front DimensionsFront side / Seite 10/83 Useable space for server Chilled water Technical dataGeneral data Data overview CoolTherm Table aData overview CoolTherm Table B Hydraulic Data PDU Box ControlFan control characteristic factory setting Storage and transportation 680 kg Safety instruction for crane transport 680 kgCheck unit for transport damage Installation and commissioning Preparation for installationPositioning the units Adjustable Feet Remove recirculation air duct transport lockPreparing heat exchanger for initial commissioning Chilled water connection/ Seite 22/83 Heat exchanger connection Preparations for connectingCondensed water connection Electrical connection Function Sealing of cabinetAutomatic door opening Release of Automatic Door Opening Initial Commissioning Technichal Data Manual closingManual opening General inspection on fans annually Servicing and maintenanceRegularly inspect the heat exchanger annually Fan is installed in the reverse order of removalReplacement of Heat Exchanger Dismantling and disposal Customer service, manufacturers addressAppendix Quality requirements on the water used in CoolTherm Checked performed Completed Comments Checklist for unit installationConfiguration Client/Setup siteCommissioning certificate General dataChilled water facility on site Control of statusGeneral condition Mechanical functions Function checkElectrical data / Documents Thermal checks Electrical functionsWater flow rate adjusted Yes Flow rate …………. l / min KW CoolTherm at 1.72m³/h chilled water flow rate CoolTherm Diagrams25kW-CoolTherm at 3.58m³/h chilled water flow rate Control Standard Factory SettingsSeite InhaltAllgemein Sicherheit Arbeitssicherheits SymboleSicherheitshinweis / Seite 45/83 Bestimmungsgemäße Verwendung EinsatzbedingungenBeschreibung Allgemeine Funktion Funktionsprinzip Kühlung Bodenplatte mit Öffnungen für Durchführungen Hinten Vorn AbmessungenFrontseite / Seite 51/83 Nutzbare Länge für Server / Einbauten Kühlwasser Technische DatenAllgemeine Daten Datenübersicht CoolTherm Tabelle aDatenübersicht CoolTherm Tabelle B Hydraulische Daten CoolTherm Vordersansicht RegelungKennlinie Lüfterregelung Werkseinstellung Lagerung und Transport Sicherheitshinweis für Krantransport 680 kg Gerät auf Transportschäden überprüfen Montage und Inbetriebnahme Vorbereitung zur MontageEinstellbare Füße Aufstellung der GeräteTransportsicherung der Luftumlenkung entfernen Anschluss KühlwasserZur Ventilkontrolle Kühleranschluss Vorbereitung für Anschluss Anschluss KondensatAbdichtung Gehäuse Anschluss ElektroFunktion Automatische TüröffnungAuslösung der Türöffnung Manuelles Schließen Erste InbetriebnahmeTechnische Daten Wartung und InstandhaltungManuelles Öffnen Lüfter austauschen Allgemeine Kontrollen an Ventilatoren jährlichAuswechseln des Wärmetauschers Allgemeine Kontrollen am Kühler jährlichDemontage und Entsorgung Kundendienst, Herstelleradressen / Seite 75/83 Durchgeführte Überprüfung Erledigt Checkliste zur GeräteaufstellungAllgemeine Angaben InbetriebnahmeprotokollKunde/Aufstellungsort KonfigurationKühlwasseranlage im Objekt ZustandskontrolleAllgemeiner Zustand Funktionskontrolle Mechanische Funktionen Elektrische Daten / DokumenteThermodynamische Überprüfungen Elektrische FunktionenVolumenstrom …………. l / min CoolTherm Kennlinien Werkseinstellungen der Regelung Page Page Web Site Monitoring Single-Phase UPS