When connecting to the condensed water tray, ensure that the condensed water pipe is connected to a
The height of the siphon must be designed for an under or overpressure of 800 Pa so that air is not drawn in or blown out of the waste pipe.
5.5Electrical connection
The wiring diagram is enclosed in the unit.
Make sure the server cabinet is electrically disconnected during installation. Prior to beginning installation work shut down the server cabinet, disconnect it and secure it against unauthorised switch on.
As soon as all preparations for installation have been made, you can start electrical installation.
The unit should only be connected by appropriately qualified personnel (electrician). The personnel must ensure that the server cabinet is electrically isolated for the duration of the connection work and is secured against unauthorised switch on.
Check whether voltage and frequency at installation site as well as fuse ratings match the specifications on the rating plate.
Power supply connection is done by a terminal block.
To connect the unit to the power supply:
•Correctly shut down the server cabinet.
•See the wiring diagram for information on the connections to be made.
•Connect the supply cable in the computer room.
•Check the secure connection of the earth wire.
To put the server cabinet correctly back in operation:
Switch on the fuse protected power supply.
The unit's fans will rotate clockwise.
The status indicator on the RMS viewer will go green if running.