Eaton Electrical 9130 manual LED is on Beep every second, Models Only. Ground wire

Page 111

TROUBLESHOOTING

Alarm or Condition

Possible Cause

Action

 

 

 

Overload

Power requirements exceed the

Remove some of the equipment from the UPS. The

 

UPS capacity (greater than

UPS continues to operate, but may switch to

 

100% of nominal; see page 84 for

Bypass mode or shut down if the load increases.

LED is on.

specific output overload

The alarm resets when the condition becomes

ranges).

inactive.

1 beep every second.

 

 

 

 

 

Overtemperature

The UPS internal temperature is

If the UPS transferred to Bypass mode, the UPS will

 

too high or a fan has failed.

return to normal operation when the temperature

 

At the warning level, the UPS

drops 5°C below the warning level.

LED is on.

generates the alarm but remains

If the condition persists, shut down the UPS. Clear

1 beep every second.

in the current operating state.

vents and remove any heat sources. Allow the UPS

If the temperature rises another

to cool. Ensure the airflow around the UPS is not

 

 

10°C, the UPS transfers to

restricted. Restart the UPS.

 

Bypass mode or shuts down if

If the condition continues to persist, contact your

 

bypass is unusable.

service representative.

Battery Overvoltage

The UPS battery voltage is too

 

high.

LED is on.

1 beep every second.

The UPS turns off the charger until the next power recycle. Contact your service representative.

Site Wiring Fault

LED is on.

1 beep every second.

“L” Models Only. Ground wire

Have a qualified electrician correct the wiring.

connection does not exist, or the

 

line and neutral wires are

 

reversed in the wall outlet.

 

 

 

“G” Models Only. Input is phase

Disable the Site Wiring Fault Alarm setting (see

to phase (neutral is not bonded

“User Settings” on page 40).

to ground).

 

 

 

 

“i” and “G (AU)” Models Only.

Rotate the Schuko input connector.

 

The polarity of the UPS input

 

 

power cord connector is

 

 

incorrect.

 

 

 

 

 

“i” and “G (AU)” Models Only.

Have a qualified electrician correct the wiring. If

 

The ground wire connection

the UPS is installed to input supply without ground,

 

does not exist.

disable the “Site Wiring Fault Alarm” setting (see

 

 

“User Settings” on page 40).

 

 

 

The UPS does not provide

The batteries need charging or

Apply utility power for 48 hours to charge the

the expected backup time.

service.

batteries. If the condition persists, contact your

 

 

service representative.

 

 

 

Power is not available at the

The UPS is in Standby mode.

Supply power to the connected equipment: Press

UPS output receptacles.

 

the On/Off button for at least 1 second, until the

 

 

front panel displays “UPS starting...”.

 

 

 

Eaton® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com

103

Image 111
Contents Eaton 9130 UPS 700-3000 VA Users Guide FCC Part ICES-003 Class a EMC Statements Low Voltage Models over 1500 VAClass B EMC Statements Requesting a Declaration of Conformity Special SymbolsTable of Contents 101 UPS MaintenanceSpecifications Troubleshooting107 WarrantyTable of Contents Chapter Introduction Shows the Eaton 9130 tower UPS and optional EBM R N I N G N G E RU T I O N SikkerhedsanvisningerR E A R S C H U W I N G V a R S E LBelangrijke Veiligheidsinstructies V a a RR O I T U S G E L E TTarkeita Turvaohjeita A R aConsignes de sécurité R OR N U N G SicherheitswarnungenAvvisi di sicurezza H T U N GR I C O L O V E R T E N Z aT E N Z I O N E Viktig Sikkerhetsinformasion R L I GR S I K T I G R I G O Regulamentos de SegurançaI D a D O V E R T Ê N C I aÏðåäóïðåæäåíèå ÏàñíîV E R T E N C I a ÎñòîðîæíîAdvertencias de Seguridad L I G R OE C a U C I Ó N SäkerhetsföreskrifterR a K T I G T ÊInspecting the Equipment Chapter InstallationÊUnpacking the Cabinet ÊChecking the Accessory KitÊRackmount Installation Checking the Rail Kit AccessoriesTools Required Assembling the Rails Rackmount SetupSecuring the Rails Installing the Mounting Brackets Forward Position Shown Installing the UPS ÊRackmount Wiring InstallationRemoving the UPS Right Front Cover Connecting the UPS Internal Batteries Removing the EBM Cable Knockout Connecting the EBMsRemoving the EBM Front Cover Typical EBM Installation ÊTower Installation Removing the UPS Front Cover ÊTower Wiring InstallationConnecting the UPS Internal Batteries Connecting the EBMs Connecting the EBMs To start up the UPS Êups Initial StartupInstallation Installation Eaton 9130 Control Panel ÊControl Panel FunctionsDisplay Functions Indicator DescriptionsIndicator Status Description Changing the LanguageMain Menu Submenu Display Information or Menu Function Menu Map for Display FunctionsUser Settings Description Available Settings Default Setting User SettingsFrequency Converter Enabled Disabled When in Spec Normal Mode Battery ModeÊOperating Modes Bypass Mode Standby Mode Êups Startup and ShutdownStarting the UPS Starting the UPS on Battery ÊTransferring the UPS Between Modes ÊRetrieving the Event LogUPS Shutdown ÊConfiguring Bypass Settings ÊSetting Power StrategyÊConfiguring Load Segments Operation ÊConfiguring Battery Settings Configuring the UPS for EBMsAll UPS and EBM Cabinets Configuring Automatic Restart Running Automatic Battery TestsCommunication Independent Multiplexed Communication Bay ÊInstalling Communication Options and Control TerminalsÊCommunication Options RS-232 and USB Communication PortsGND Pin Number Signal Name Function Direction from the UPSConnectivity Cards Remote Emergency Power-offRepo Connections Relay Output Configuration Options Signal DescriptionRelay Output Contacts Input Description Programmable Signal InputsProgrammable Signal Inputs Polarity OptionsÊModem Operation ÊPowerware LanSafe Power Management SoftwareÊups and Battery Care UPS MaintenanceÊWhen to Replace Batteries ÊStoring the UPS and BatteriesÊReplacing Batteries Replacing Rackmount UPS Internal Batteries Disconnecting the UPS Internal Batteries Shown without EBMs U T I O N Replacing Tower UPS Internal Batteries Replacing the UPS Internal Batteries U T I O N Replacing Rackmount EBMs UPS Maintenance Replacing Tower EBMs ÊTesting New Batteries ÊUpdating the UPS Firmware ÊRecycling the Used Battery or UPSUPS Maintenance ÊModel Specifications Extended Battery Module Model ListCommunication Options All Models UPS Model List Rackmount Models Model Power Level Rear Panel DiagramUPS Model List Tower Models Weights and Dimensions Rackmount Models Model Rackmount UPS Dimensions H W D WeightModel Rackmount EBM Electrical Input All Models Weights and Dimensions Tower ModelsElectrical Input Rackmount Models Model Default Input Selectable Input Voltage RangeElectrical Input Tower Models Model Input Connection Input Cable Electrical Input Connections Rackmount ModelsElectrical Input Connections Tower Models Electrical Output All Models Model Output Connections Output Cables Electrical Output Connections Rackmount ModelsElectrical Output Connections Tower Models Environmental and Safety All Models Model Internal Batteries + 1 EBM + 2 EBMs + 3 EBMs + 4 EBMs Battery Runtimes in Minutes at 100% Load Rack ModelsBattery Runtimes in Minutes at 100% Load Tower Models Internal Batteries EBMs BatteryModels PW9130L700R-XL2U, PW9130L1000R-XL2U ÊRear PanelsModel PW9130G1000R-XL2UAU Model PW9130L2000R-XL2U Models PW9130L2500R-XL2U, PW9130L3000R-XL2U Model PW9130L1500T-XL Model PW9130G2000T-XL Model PW9130i1500T-XL Model PW9130G1000T-XLAU Model PW9130G2000T-XLAU 100 ÊTypical Alarms and Conditions TroubleshootingBattery is running low Alarm or Condition Possible Cause ActionLED is on Beep every second Models Only. Ground wireUPS does not start ÊService and Support ÊSilencing the Alarm106 ÊTwo-Year Limited Warranty US and Canada Chapter WarrantyWarranty ÊTen-Year Pro-Rated Limited Warranty US and Canada 110 ÊLoad Protection Guarantee US and Canada 112