Eaton Electrical 9130 manual Programmable Signal Inputs, Polarity Options, Input Description

Page 67

COMMUNICATION

Programmable Signal Inputs

The UPS incorporates four programmable signal inputs: one RS-232 input, two connectivity card inputs, and one REPO terminal input. See Figure 18 on page 53 for the locations of the ports. Configure the inputs with the “Signal Inputs” setting in “User Settings” on page 40.

Table 6 shows the programmable settings for the signal inputs. Table 7 shows the operation logic for the signal inputs.

Table 6. Programmable Signal Inputs

Signal

Description

 

 

Not Used

The input operates only as a serial input (RxD) or has no function.

 

 

Force Bypass

If active, the UPS is forced to static bypass operation regardless of

 

the bypass status.

 

 

Remote Shutdown

If active, the UPS output turns off after a user-defined remote

 

shutdown delay. The batteries continue charging. Inactive input

 

does not abort the shutdown countdown and does not cause the

 

UPS to start up automatically.

 

 

Delayed

If active, the UPS output turns off after a user-defined delayed

Shutdown

shutdown delay. The batteries continue charging. Inactive input

(and restart)

does not abort the shutdown countdown but will cause the UPS to

 

start up automatically if the input voltage exists.

 

 

On Generator

If active, synchronization is disabled and the UPS transfers to

 

bypass.

 

 

Building Alarm 1

If active, the UPS generates the “Building Alarm 1” alarm.

 

 

Table 7. Polarity Options

Input

Description

 

 

High

Active state on high voltage (+Udc) level

 

 

Low

Active state on low voltage (GND or -Udc) level

 

 

Eaton® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com

59

Image 67
Contents Eaton 9130 UPS 700-3000 VA Users Guide FCC Part ICES-003 Class a EMC Statements Low Voltage Models over 1500 VAClass B EMC Statements Requesting a Declaration of Conformity Special SymbolsTable of Contents 101 UPS MaintenanceSpecifications Troubleshooting107 WarrantyTable of Contents Chapter Introduction Shows the Eaton 9130 tower UPS and optional EBM R N I N G N G E RSikkerhedsanvisninger U T I O NR E A R S C H U W I N G V a R S E LBelangrijke Veiligheidsinstructies V a a RR O I T U S G E L E TTarkeita Turvaohjeita A R aConsignes de sécurité R OR N U N G SicherheitswarnungenAvvisi di sicurezza H T U N GV E R T E N Z a R I C O L OT E N Z I O N E R L I G Viktig SikkerhetsinformasionR S I K T I G R I G O Regulamentos de SegurançaI D a D O V E R T Ê N C I aÏðåäóïðåæäåíèå ÏàñíîV E R T E N C I a ÎñòîðîæíîAdvertencias de Seguridad L I G R OSäkerhetsföreskrifter E C a U C I Ó NR a K T I G T ÊInspecting the Equipment Chapter InstallationÊUnpacking the Cabinet ÊChecking the Accessory KitChecking the Rail Kit Accessories ÊRackmount InstallationTools Required Assembling the Rails Rackmount SetupSecuring the Rails Installing the Mounting Brackets Forward Position Shown Installing the UPS ÊRackmount Wiring InstallationRemoving the UPS Right Front Cover Connecting the UPS Internal Batteries Removing the EBM Cable Knockout Connecting the EBMsRemoving the EBM Front Cover Typical EBM Installation ÊTower Installation Removing the UPS Front Cover ÊTower Wiring InstallationConnecting the UPS Internal Batteries Connecting the EBMs Connecting the EBMs To start up the UPS Êups Initial StartupInstallation Installation Eaton 9130 Control Panel ÊControl Panel FunctionsDisplay Functions Indicator DescriptionsIndicator Status Description Changing the LanguageMain Menu Submenu Display Information or Menu Function Menu Map for Display FunctionsUser Settings Description Available Settings Default Setting User SettingsFrequency Converter Enabled Disabled When in Spec Battery Mode Normal ModeÊOperating Modes Bypass Mode Êups Startup and Shutdown Standby ModeStarting the UPS Starting the UPS on Battery ÊRetrieving the Event Log ÊTransferring the UPS Between ModesUPS Shutdown ÊConfiguring Bypass Settings ÊSetting Power StrategyÊConfiguring Load Segments Operation Configuring the UPS for EBMs ÊConfiguring Battery SettingsAll UPS and EBM Cabinets Configuring Automatic Restart Running Automatic Battery TestsCommunication Independent Multiplexed Communication Bay ÊInstalling Communication Options and Control TerminalsÊCommunication Options RS-232 and USB Communication PortsGND Pin Number Signal Name Function Direction from the UPSConnectivity Cards Remote Emergency Power-offRepo Connections Signal Description Relay Output Configuration OptionsRelay Output Contacts Input Description Programmable Signal InputsProgrammable Signal Inputs Polarity OptionsÊModem Operation ÊPowerware LanSafe Power Management SoftwareÊups and Battery Care UPS MaintenanceÊStoring the UPS and Batteries ÊWhen to Replace BatteriesÊReplacing Batteries Replacing Rackmount UPS Internal Batteries Disconnecting the UPS Internal Batteries Shown without EBMs U T I O N Replacing Tower UPS Internal Batteries Replacing the UPS Internal Batteries U T I O N Replacing Rackmount EBMs UPS Maintenance Replacing Tower EBMs ÊTesting New Batteries ÊUpdating the UPS Firmware ÊRecycling the Used Battery or UPSUPS Maintenance Extended Battery Module Model List ÊModel SpecificationsCommunication Options All Models UPS Model List Rackmount Models Model Power Level Rear Panel DiagramUPS Model List Tower Models Model Rackmount UPS Dimensions H W D Weight Weights and Dimensions Rackmount ModelsModel Rackmount EBM Electrical Input All Models Weights and Dimensions Tower ModelsElectrical Input Rackmount Models Model Default Input Selectable Input Voltage RangeElectrical Input Tower Models Model Input Connection Input Cable Electrical Input Connections Rackmount ModelsElectrical Input Connections Tower Models Electrical Output All Models Model Output Connections Output Cables Electrical Output Connections Rackmount ModelsElectrical Output Connections Tower Models Environmental and Safety All Models Model Internal Batteries + 1 EBM + 2 EBMs + 3 EBMs + 4 EBMs Battery Runtimes in Minutes at 100% Load Rack ModelsBattery Runtimes in Minutes at 100% Load Tower Models Internal Batteries EBMs BatteryModels PW9130L700R-XL2U, PW9130L1000R-XL2U ÊRear PanelsModel PW9130G1000R-XL2UAU Model PW9130L2000R-XL2U Models PW9130L2500R-XL2U, PW9130L3000R-XL2U Model PW9130L1500T-XL Model PW9130G2000T-XL Model PW9130i1500T-XL Model PW9130G1000T-XLAU Model PW9130G2000T-XLAU 100 ÊTypical Alarms and Conditions TroubleshootingBattery is running low Alarm or Condition Possible Cause ActionLED is on Beep every second Models Only. Ground wireUPS does not start ÊService and Support ÊSilencing the Alarm106 ÊTwo-Year Limited Warranty US and Canada Chapter WarrantyWarranty ÊTen-Year Pro-Rated Limited Warranty US and Canada 110 ÊLoad Protection Guarantee US and Canada 112