Eaton Electrical 9130 manual Repo Connections

Page 65

COMMUNICATION

NOTE For Europe, the emergency switch requirements are detailed in Harmonized document HD-384-48 S1, “Electrical Installation of the Buildings, Part 4: Protection for Safety, Chapter 46: Isolation and Switching.”

REPO Connections

Wire Function

Terminal Wire Size Rating

Suggested Wire Size

 

 

 

 

REPO

L1

4–0.32 mm2 (12–22 AWG)

0.82 mm2 (18 AWG)

 

 

 

L2

 

 

 

 

 

 

 

NOTE Leave the REPO connector installed in the REPO port on the UPS even if the REPO function is not needed.

See Figure 18 on page 53 for REPO location. Figure 21 shows a schematic of the REPO connector contacts.

1+ Polarity

2 – Polarity

REPO

Figure 21. REPO Connections

You can set the REPO polarity. See the “REPO Input Polarity” setting in “User Settings” on page 40.

NOTE Depending on user configuration, the pins must be shorted or open to keep the UPS running. To restart the UPS, reconnect (re-open) the REPO connector pins and turn on the UPS manually. Maximum resistance in the shorted loop is 10 ohm.

NOTE The following models have the REPO port configured for “Force to Bypass” function: rack models PW9130G1000R-XL2UAU, PW9130G1500R-XL2UAU, PW9130G2000R-XL2UAU, PW9130G3000R-XL2UAU and tower models PW9130G700T-XLAU, PW9130G1000T-XLAU, PW9130G1500T-XLAU, PW9130G2000T-XLAU, PW9130G3000T-XLAU. In the “Force to Bypass” state, the UPS transfers to Bypass model in every condition except frequency converter and generator mode.

NOTE Always test the REPO function before applying your critical load to avoid accidental load loss.

Eaton® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com

57

Image 65
Contents Eaton 9130 UPS 700-3000 VA Users Guide FCC Part ICES-003 Class a EMC Statements Low Voltage Models over 1500 VAClass B EMC Statements Requesting a Declaration of Conformity Special SymbolsTable of Contents Specifications UPS MaintenanceTroubleshooting 101107 WarrantyTable of Contents Chapter Introduction Shows the Eaton 9130 tower UPS and optional EBM R N I N G N G E RR E U T I O NSikkerhedsanvisninger Belangrijke Veiligheidsinstructies V a R S E LV a a R A R S C H U W I N GTarkeita Turvaohjeita G E L E TA R a R O I T U SConsignes de sécurité R OR N U N G SicherheitswarnungenAvvisi di sicurezza H T U N GT E N Z I O N E R I C O L OV E R T E N Z a R S I K T I G Viktig SikkerhetsinformasionR L I G I D a D O Regulamentos de SegurançaV E R T Ê N C I a R I G OÏðåäóïðåæäåíèå ÏàñíîAdvertencias de Seguridad ÎñòîðîæíîL I G R O V E R T E N C I aR a E C a U C I Ó NSäkerhetsföreskrifter K T I G T ÊInspecting the Equipment Chapter InstallationÊUnpacking the Cabinet ÊChecking the Accessory KitTools Required ÊRackmount InstallationChecking the Rail Kit Accessories Assembling the Rails Rackmount SetupSecuring the Rails Installing the Mounting Brackets Forward Position Shown Installing the UPS ÊRackmount Wiring InstallationRemoving the UPS Right Front Cover Connecting the UPS Internal Batteries Removing the EBM Cable Knockout Connecting the EBMsRemoving the EBM Front Cover Typical EBM Installation ÊTower Installation Removing the UPS Front Cover ÊTower Wiring InstallationConnecting the UPS Internal Batteries Connecting the EBMs Connecting the EBMs To start up the UPS Êups Initial StartupInstallation Installation Eaton 9130 Control Panel ÊControl Panel FunctionsIndicator Status Description Indicator DescriptionsChanging the Language Display FunctionsMain Menu Submenu Display Information or Menu Function Menu Map for Display FunctionsUser Settings Description Available Settings Default Setting User SettingsFrequency Converter Enabled Disabled When in Spec ÊOperating Modes Normal ModeBattery Mode Bypass Mode Starting the UPS Standby ModeÊups Startup and Shutdown Starting the UPS on Battery UPS Shutdown ÊTransferring the UPS Between ModesÊRetrieving the Event Log ÊConfiguring Bypass Settings ÊSetting Power StrategyÊConfiguring Load Segments Operation All UPS and EBM Cabinets ÊConfiguring Battery SettingsConfiguring the UPS for EBMs Configuring Automatic Restart Running Automatic Battery TestsCommunication ÊCommunication Options ÊInstalling Communication Options and Control Terminals RS-232 and USB Communication Ports Independent Multiplexed Communication BayGND Pin Number Signal Name Function Direction from the UPSConnectivity Cards Remote Emergency Power-offRepo Connections Relay Output Contacts Relay Output Configuration OptionsSignal Description Programmable Signal Inputs Programmable Signal InputsPolarity Options Input DescriptionÊModem Operation ÊPowerware LanSafe Power Management SoftwareÊups and Battery Care UPS MaintenanceÊReplacing Batteries ÊWhen to Replace BatteriesÊStoring the UPS and Batteries Replacing Rackmount UPS Internal Batteries Disconnecting the UPS Internal Batteries Shown without EBMs U T I O N Replacing Tower UPS Internal Batteries Replacing the UPS Internal Batteries U T I O N Replacing Rackmount EBMs UPS Maintenance Replacing Tower EBMs ÊTesting New Batteries ÊUpdating the UPS Firmware ÊRecycling the Used Battery or UPSUPS Maintenance Communication Options All Models ÊModel SpecificationsExtended Battery Module Model List UPS Model List Rackmount Models Model Power Level Rear Panel DiagramUPS Model List Tower Models Model Rackmount EBM Weights and Dimensions Rackmount ModelsModel Rackmount UPS Dimensions H W D Weight Electrical Input All Models Weights and Dimensions Tower ModelsElectrical Input Rackmount Models Model Default Input Selectable Input Voltage RangeElectrical Input Tower Models Model Input Connection Input Cable Electrical Input Connections Rackmount ModelsElectrical Input Connections Tower Models Electrical Output All Models Model Output Connections Output Cables Electrical Output Connections Rackmount ModelsElectrical Output Connections Tower Models Environmental and Safety All Models Model Internal Batteries + 1 EBM + 2 EBMs + 3 EBMs + 4 EBMs Battery Runtimes in Minutes at 100% Load Rack ModelsBattery Runtimes in Minutes at 100% Load Tower Models Internal Batteries EBMs BatteryModels PW9130L700R-XL2U, PW9130L1000R-XL2U ÊRear PanelsModel PW9130G1000R-XL2UAU Model PW9130L2000R-XL2U Models PW9130L2500R-XL2U, PW9130L3000R-XL2U Model PW9130L1500T-XL Model PW9130G2000T-XL Model PW9130i1500T-XL Model PW9130G1000T-XLAU Model PW9130G2000T-XLAU 100 ÊTypical Alarms and Conditions TroubleshootingBattery is running low Alarm or Condition Possible Cause ActionLED is on Beep every second Models Only. Ground wireUPS does not start ÊService and Support ÊSilencing the Alarm106 ÊTwo-Year Limited Warranty US and Canada Chapter WarrantyWarranty ÊTen-Year Pro-Rated Limited Warranty US and Canada 110 ÊLoad Protection Guarantee US and Canada 112