UPS MAINTENANCE
6.Replace the battery cover plate into the slots at left, threading the battery connector through the access slot. Reinstall the retained screws.
C A U T I O N
A small amount of arcing may occur when connecting the internal batteries. This is normal and will not harm personnel. Connect the cables quickly and firmly.
7.Reconnect the internal battery connector. Connect red to red, and black to black. Press the two parts tightly together to ensure a proper connection.
8.Place the connector between the screw mounts and reinstall the retained screws.
9.Replace the UPS front cover.
To replace the cover, verify that the ribbon cable is protected, then insert the clips on the back of the cover into the cabinet and push firmly to snap the cover into place.
10.Continue to “Testing New Batteries” on page 72.
68 | Eaton® 9130 UPS |