TROUBLESHOOTING

To check the Event Log for a history of conditions:

1.Press any button on the front panel display to activate the menu options.

2.Press the

button until EVENT LOG displays.

3.Press the Enter button to display the list of conditions.

You can also retrieve the entire Event Log in ASCII format. See “Retrieving the Event Log” on page 47.

The following table describes typical alarms and conditions.

Alarm or Condition

Possible Cause

Action

 

 

 

On Battery

A utility failure has occurred and

 

 

 

 

 

the UPS is in Battery mode.

LED is on.

1 beep every 5 seconds.

The UPS is powering the equipment with battery power. Prepare your equipment for shutdown.

Battery Low

The UPS is in Battery mode and

This warning is approximate, and the actual time to

 

the battery is running low.

shutdown may vary significantly. Depending on the

 

 

UPS load and number of Extended Battery Modules

LED is flashing slowly.

 

(EBMs), the “Battery Low” warning may occur

 

before the batteries reach 25% capacity. See

 

 

1 beep every second.

 

Table 23 on page 88 for estimated runtimes.

 

 

 

On Bypass

The UPS is in Bypass mode.

The equipment transferred to bypass utility power.

 

 

Battery mode is not available and your equipment

 

 

is not protected; however, the utility power

LED is on.

 

continues to be passively filtered by the UPS.

 

Check for one of the following alarms:

 

 

1 beep every 5 seconds.

 

overtemperature, overload, or UPS failure.

 

 

 

On Bypass

The UPS is on bypass while

The equipment transferred to bypass utility power

 

operating on the High Efficiency

as a normal function of High Efficiency operation.

 

setting.

Battery mode is available and your equipment is

LED is on.

 

protected.

 

 

No beeping.

 

 

 

 

 

Batteries Disconnected

The UPS does not recognize the

If the condition persists, contact your service

 

internal batteries.

representative.

 

 

 

 

The batteries are disconnected.

Verify that all batteries are properly connected. If

LED is on.

 

the condition persists, contact your service

1 beep every second.

 

representative.

 

 

 

102

Eaton® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com

Image 110
Contents Eaton 9130 UPS 700-3000 VA Users Guide Class a EMC Statements Low Voltage Models over 1500 VA FCC Part ICES-003Class B EMC Statements Special Symbols Requesting a Declaration of ConformityTable of Contents Troubleshooting UPS MaintenanceSpecifications 101Warranty 107Table of Contents Chapter Introduction Shows the Eaton 9130 tower UPS and optional EBM N G E R R N I N GR E U T I O NSikkerhedsanvisninger V a a R V a R S E LBelangrijke Veiligheidsinstructies A R S C H U W I N GA R a G E L E TTarkeita Turvaohjeita R O I T U SR O Consignes de sécuritéSicherheitswarnungen R N U N GH T U N G Avvisi di sicurezzaT E N Z I O N E R I C O L OV E R T E N Z a R S I K T I G Viktig SikkerhetsinformasionR L I G V E R T Ê N C I a Regulamentos de SegurançaI D a D O R I G OÏàñíî ÏðåäóïðåæäåíèåL I G R O ÎñòîðîæíîAdvertencias de Seguridad V E R T E N C I aR a E C a U C I Ó NSäkerhetsföreskrifter K T I G T Chapter Installation ÊInspecting the EquipmentÊChecking the Accessory Kit ÊUnpacking the CabinetTools Required ÊRackmount InstallationChecking the Rail Kit Accessories Rackmount Setup Assembling the RailsSecuring the Rails Installing the Mounting Brackets Forward Position Shown ÊRackmount Wiring Installation Installing the UPSRemoving the UPS Right Front Cover Connecting the UPS Internal Batteries Connecting the EBMs Removing the EBM Cable KnockoutRemoving the EBM Front Cover Typical EBM Installation ÊTower Installation ÊTower Wiring Installation Removing the UPS Front CoverConnecting the UPS Internal Batteries Connecting the EBMs Connecting the EBMs Êups Initial Startup To start up the UPSInstallation Installation ÊControl Panel Functions Eaton 9130 Control PanelChanging the Language Indicator DescriptionsIndicator Status Description Display FunctionsMenu Map for Display Functions Main Menu Submenu Display Information or Menu FunctionUser Settings User Settings Description Available Settings Default SettingFrequency Converter Enabled Disabled When in Spec ÊOperating Modes Normal ModeBattery Mode Bypass Mode Starting the UPS Standby ModeÊups Startup and Shutdown Starting the UPS on Battery UPS Shutdown ÊTransferring the UPS Between ModesÊRetrieving the Event Log ÊSetting Power Strategy ÊConfiguring Bypass SettingsÊConfiguring Load Segments Operation All UPS and EBM Cabinets ÊConfiguring Battery SettingsConfiguring the UPS for EBMs Running Automatic Battery Tests Configuring Automatic RestartCommunication RS-232 and USB Communication Ports ÊInstalling Communication Options and Control TerminalsÊCommunication Options Independent Multiplexed Communication BayPin Number Signal Name Function Direction from the UPS GNDRemote Emergency Power-off Connectivity CardsRepo Connections Relay Output Contacts Relay Output Configuration OptionsSignal Description Polarity Options Programmable Signal InputsProgrammable Signal Inputs Input DescriptionÊPowerware LanSafe Power Management Software ÊModem OperationUPS Maintenance Êups and Battery CareÊReplacing Batteries ÊWhen to Replace BatteriesÊStoring the UPS and Batteries Replacing Rackmount UPS Internal Batteries Disconnecting the UPS Internal Batteries Shown without EBMs U T I O N Replacing Tower UPS Internal Batteries Replacing the UPS Internal Batteries U T I O N Replacing Rackmount EBMs UPS Maintenance Replacing Tower EBMs ÊTesting New Batteries ÊRecycling the Used Battery or UPS ÊUpdating the UPS FirmwareUPS Maintenance Communication Options All Models ÊModel SpecificationsExtended Battery Module Model List Model Power Level Rear Panel Diagram UPS Model List Rackmount ModelsUPS Model List Tower Models Model Rackmount EBM Weights and Dimensions Rackmount ModelsModel Rackmount UPS Dimensions H W D Weight Weights and Dimensions Tower Models Electrical Input All ModelsModel Default Input Selectable Input Voltage Range Electrical Input Rackmount ModelsElectrical Input Tower Models Electrical Input Connections Rackmount Models Model Input Connection Input CableElectrical Input Connections Tower Models Electrical Output All Models Electrical Output Connections Rackmount Models Model Output Connections Output CablesElectrical Output Connections Tower Models Environmental and Safety All Models Battery Runtimes in Minutes at 100% Load Rack Models Model Internal Batteries + 1 EBM + 2 EBMs + 3 EBMs + 4 EBMsBattery Runtimes in Minutes at 100% Load Tower Models Battery Internal Batteries EBMsÊRear Panels Models PW9130L700R-XL2U, PW9130L1000R-XL2UModel PW9130G1000R-XL2UAU Model PW9130L2000R-XL2U Models PW9130L2500R-XL2U, PW9130L3000R-XL2U Model PW9130L1500T-XL Model PW9130G2000T-XL Model PW9130i1500T-XL Model PW9130G1000T-XLAU Model PW9130G2000T-XLAU 100 Troubleshooting ÊTypical Alarms and ConditionsAlarm or Condition Possible Cause Action Battery is running lowModels Only. Ground wire LED is on Beep every secondUPS does not start ÊSilencing the Alarm ÊService and Support106 Chapter Warranty ÊTwo-Year Limited Warranty US and CanadaWarranty ÊTen-Year Pro-Rated Limited Warranty US and Canada 110 ÊLoad Protection Guarantee US and Canada 112