SPECIFICATIONS
Table 19. Electrical Output (All Models)
All Models | Normal Mode | Battery Mode |
|
|
|
Voltage Regulation | ±2% | Nominal output voltage ±3% |
|
|
|
Efficiency | >95% (High Efficiency mode), >88% | >79.5% (700 VA), |
|
| >82% |
|
| >84% |
|
|
|
Frequency Regulation | Sync with line ±3 Hz of nominal line | ±0.1 Hz of |
| frequency (outside this range: | frequency |
| ±0.1 Hz of |
|
| frequency) |
|
|
|
|
| Low Voltage Models | High Voltage Models |
|
|
|
Nominal Outputs | 100/110/120/127V | 200/208/220/230/240V |
| (voltage configurable or | (voltage configurable or |
| ||
| 1000/1500/2000/3000 VA | 1000/1500/2000/3000 VA |
| 0.9/1.35/1.8/2.7 kW | 0.9/1.35/1.8/2.7 kW |
|
| |
Frequency | 50 or 60 Hz, autosensing or configurable as a frequency converter | |
|
| |
Output Overload (Normal Mode) | ||
| ||
| ||
| >150%: Load transfers to Bypass mode after 100 ms. (Level 4) | |
| NOTE Default configuration transfers immediately to Bypass at >102%. | |
|
| |
Output Overload (Bypass Mode) | ||
| ||
| ||
| >150%: UPS shuts down after 300 ms. (Level 4) | |
|
| |
Output Overload (Battery Mode) | ||
| ||
| ||
| >150%: UPS shuts down after 100 ms. (Level 4) | |
|
|
|
Voltage Waveform |
| Sine wave |
|
| |
Harmonic Distortion | <3% THD on linear load; <5% THD on | |
|
| |
Transfer Time | Online mode: 0 ms (no break) | |
| High Efficiency mode: 5 ms maximum (due to loss of utility) | |
|
|
|
Power Factor |
| 0.9 |
|
|
|
Load Crest Factor |
| 3 to 1 |
|
|
|
84 | Eaton® 9130 UPS |