OPERATION
5.Check the UPS front panel display for active alarms or notices. Resolve any active alarms before continuing. See “Troubleshooting” on page 101.
If the indicator is on, do not proceed until all alarms are clear. Check the UPS status from the front panel to view the active alarms. Correct the alarms and restart if necessary.
6.Verify that the indicator illuminates solid, indicating that the UPS is operating normally and any loads are powered.
The UPS should be in Normal mode.
7.Press the ESC button until the start screen appears.
Starting the UPS on Battery
NOTE Before using this feature, the UPS must have been powered by utility power with output enabled at least once.
NOTE Battery start can be disabled. See the “Start on Battery” setting in “User Settings” on page 40.
To start the UPS on battery:
1.Press the button on the UPS front panel until the UPS front panel display illuminates and shows a status of “UPS starting...”.
The UPS cycles through Standby mode to Battery mode. The indicator illuminates solid. The UPS supplies power to your equipment.
2.Check the UPS front panel display for active alarms or notices besides the “UPS on Battery” notice and notices that indicate missing utility power. Resolve any active alarms before continuing. See “Troubleshooting” on page 101.
Check the UPS status from the front panel to view the active alarms. Correct the alarms and restart if necessary.
3.Press the ESC button until the start screen appears.
46 | Eaton® 9130 UPS |