Eaton Electrical 9130 manual Disconnecting the UPS Internal Batteries Shown without EBMs

Page 72

UPS MAINTENANCE

NOTE Leave ribbon cable connected.

Figure 23. Removing the UPS Right Front Cover

2.Disconnect the internal battery connector (see Figure 24).

3.Up to 1500 VA models only. If the EBM cable is not connected to an EBM, unclip the EBM cable and move it to the left out of the way. See Figure 24.

Battery Cover Plate

Internal Battery

Connector

Battery Cover Plate

Internal Battery

Connector

EBM Cable

Up to 1500 VA Models

2000–3000 VA Models

Figure 24. Disconnecting the UPS Internal Batteries (Shown without EBMs)

4.Grasp an edge of the battery cover plate and pull it forward gently. Remove and retain the battery cover plate. See Figure 24 for the location of the battery cover plate.

64

Eaton® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com

Image 72
Contents Eaton 9130 UPS 700-3000 VA Users Guide Class a EMC Statements Low Voltage Models over 1500 VA FCC Part ICES-003Class B EMC Statements Special Symbols Requesting a Declaration of ConformityTable of Contents UPS Maintenance SpecificationsTroubleshooting 101Warranty 107Table of Contents Chapter Introduction Shows the Eaton 9130 tower UPS and optional EBM N G E R R N I N GU T I O N SikkerhedsanvisningerR E V a R S E L Belangrijke VeiligheidsinstructiesV a a R A R S C H U W I N GG E L E T Tarkeita TurvaohjeitaA R a R O I T U SR O Consignes de sécuritéSicherheitswarnungen R N U N GH T U N G Avvisi di sicurezzaR I C O L O V E R T E N Z aT E N Z I O N E Viktig Sikkerhetsinformasion R L I GR S I K T I G Regulamentos de Segurança I D a D OV E R T Ê N C I a R I G OÏàñíî ÏðåäóïðåæäåíèåÎñòîðîæíî Advertencias de SeguridadL I G R O V E R T E N C I aE C a U C I Ó N SäkerhetsföreskrifterR a K T I G T Chapter Installation ÊInspecting the EquipmentÊChecking the Accessory Kit ÊUnpacking the CabinetÊRackmount Installation Checking the Rail Kit AccessoriesTools Required Rackmount Setup Assembling the RailsSecuring the Rails Installing the Mounting Brackets Forward Position Shown ÊRackmount Wiring Installation Installing the UPSRemoving the UPS Right Front Cover Connecting the UPS Internal Batteries Connecting the EBMs Removing the EBM Cable KnockoutRemoving the EBM Front Cover Typical EBM Installation ÊTower Installation ÊTower Wiring Installation Removing the UPS Front CoverConnecting the UPS Internal Batteries Connecting the EBMs Connecting the EBMs Êups Initial Startup To start up the UPSInstallation Installation ÊControl Panel Functions Eaton 9130 Control PanelIndicator Descriptions Indicator Status DescriptionChanging the Language Display FunctionsMenu Map for Display Functions Main Menu Submenu Display Information or Menu FunctionUser Settings User Settings Description Available Settings Default SettingFrequency Converter Enabled Disabled When in Spec Normal Mode Battery ModeÊOperating Modes Bypass Mode Standby Mode Êups Startup and ShutdownStarting the UPS Starting the UPS on Battery ÊTransferring the UPS Between Modes ÊRetrieving the Event LogUPS Shutdown ÊSetting Power Strategy ÊConfiguring Bypass SettingsÊConfiguring Load Segments Operation ÊConfiguring Battery Settings Configuring the UPS for EBMsAll UPS and EBM Cabinets Running Automatic Battery Tests Configuring Automatic RestartCommunication ÊInstalling Communication Options and Control Terminals ÊCommunication OptionsRS-232 and USB Communication Ports Independent Multiplexed Communication BayPin Number Signal Name Function Direction from the UPS GNDRemote Emergency Power-off Connectivity CardsRepo Connections Relay Output Configuration Options Signal DescriptionRelay Output Contacts Programmable Signal Inputs Programmable Signal InputsPolarity Options Input DescriptionÊPowerware LanSafe Power Management Software ÊModem Operation UPS Maintenance Êups and Battery CareÊWhen to Replace Batteries ÊStoring the UPS and BatteriesÊReplacing Batteries Replacing Rackmount UPS Internal Batteries Disconnecting the UPS Internal Batteries Shown without EBMs U T I O N Replacing Tower UPS Internal Batteries Replacing the UPS Internal Batteries U T I O N Replacing Rackmount EBMs UPS Maintenance Replacing Tower EBMs ÊTesting New Batteries ÊRecycling the Used Battery or UPS ÊUpdating the UPS FirmwareUPS Maintenance ÊModel Specifications Extended Battery Module Model ListCommunication Options All Models Model Power Level Rear Panel Diagram UPS Model List Rackmount ModelsUPS Model List Tower Models Weights and Dimensions Rackmount Models Model Rackmount UPS Dimensions H W D WeightModel Rackmount EBM Weights and Dimensions Tower Models Electrical Input All ModelsModel Default Input Selectable Input Voltage Range Electrical Input Rackmount ModelsElectrical Input Tower Models Electrical Input Connections Rackmount Models Model Input Connection Input CableElectrical Input Connections Tower Models Electrical Output All Models Electrical Output Connections Rackmount Models Model Output Connections Output CablesElectrical Output Connections Tower Models Environmental and Safety All Models Battery Runtimes in Minutes at 100% Load Rack Models Model Internal Batteries + 1 EBM + 2 EBMs + 3 EBMs + 4 EBMsBattery Runtimes in Minutes at 100% Load Tower Models Battery Internal Batteries EBMsÊRear Panels Models PW9130L700R-XL2U, PW9130L1000R-XL2UModel PW9130G1000R-XL2UAU Model PW9130L2000R-XL2U Models PW9130L2500R-XL2U, PW9130L3000R-XL2U Model PW9130L1500T-XL Model PW9130G2000T-XL Model PW9130i1500T-XL Model PW9130G1000T-XLAU Model PW9130G2000T-XLAU 100 Troubleshooting ÊTypical Alarms and ConditionsAlarm or Condition Possible Cause Action Battery is running lowModels Only. Ground wire LED is on Beep every secondUPS does not start ÊSilencing the Alarm ÊService and Support106 Chapter Warranty ÊTwo-Year Limited Warranty US and CanadaWarranty ÊTen-Year Pro-Rated Limited Warranty US and Canada 110 ÊLoad Protection Guarantee US and Canada 112