OPERATION

UPS Shutdown

To shut down the UPS:

1.Press the button on the front panel for three seconds.

The UPS starts to beep and shows a status of “UPS off pending...”.

The UPS then transfers to Standby mode, and the indicator turns off.

NOTE Releasing the button before three seconds returns the UPS to its original operating mode.

2.Switch off utility power where the UPS is connected.

ÊTransferring the UPS Between Modes

From Normal to Bypass Mode. Press any button to activate the menu options, then select CONTROL and GO TO BYPASS.

From Bypass to Normal Mode. Press any button to activate the menu options, then select CONTROL and GO TO NORMAL.

ÊRetrieving the Event Log

To retrieve the Event Log through the display:

1.Press any button to activate the menu options, then select

EVENT LOG.

2.Scroll through the listed events.

To retrieve the Event Log through the serial port:

1.From the communication device connected to the serial port, send one of the following command sequences: ESC-L (ASCII characters 27 and 76) or ESC-I (ASCII characters 27 and 108).

The UPS returns a header containing the UPS identification (UPS type, part number, and serial number), firmware version, and the current date and time, followed by the event history.

2.Use the connected communication device to view or print the information. The report is delivered in ASCII format.

Eaton® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com

47

Image 55
Contents Eaton 9130 UPS 700-3000 VA Users Guide FCC Part ICES-003 Class a EMC Statements Low Voltage Models over 1500 VAClass B EMC Statements Requesting a Declaration of Conformity Special SymbolsTable of Contents 101 UPS MaintenanceSpecifications Troubleshooting107 WarrantyTable of Contents Chapter Introduction Shows the Eaton 9130 tower UPS and optional EBM R N I N G N G E RSikkerhedsanvisninger U T I O NR E A R S C H U W I N G V a R S E LBelangrijke Veiligheidsinstructies V a a RR O I T U S G E L E TTarkeita Turvaohjeita A R aConsignes de sécurité R OR N U N G SicherheitswarnungenAvvisi di sicurezza H T U N GV E R T E N Z a R I C O L OT E N Z I O N E R L I G Viktig SikkerhetsinformasionR S I K T I G R I G O Regulamentos de SegurançaI D a D O V E R T Ê N C I aÏðåäóïðåæäåíèå ÏàñíîV E R T E N C I a ÎñòîðîæíîAdvertencias de Seguridad L I G R OSäkerhetsföreskrifter E C a U C I Ó NR a K T I G T ÊInspecting the Equipment Chapter InstallationÊUnpacking the Cabinet ÊChecking the Accessory KitChecking the Rail Kit Accessories ÊRackmount InstallationTools Required Assembling the Rails Rackmount SetupSecuring the Rails Installing the Mounting Brackets Forward Position Shown Installing the UPS ÊRackmount Wiring InstallationRemoving the UPS Right Front Cover Connecting the UPS Internal Batteries Removing the EBM Cable Knockout Connecting the EBMsRemoving the EBM Front Cover Typical EBM Installation ÊTower Installation Removing the UPS Front Cover ÊTower Wiring InstallationConnecting the UPS Internal Batteries Connecting the EBMs Connecting the EBMs To start up the UPS Êups Initial StartupInstallation Installation Eaton 9130 Control Panel ÊControl Panel FunctionsDisplay Functions Indicator DescriptionsIndicator Status Description Changing the LanguageMain Menu Submenu Display Information or Menu Function Menu Map for Display FunctionsUser Settings Description Available Settings Default Setting User SettingsFrequency Converter Enabled Disabled When in Spec Battery Mode Normal ModeÊOperating Modes Bypass Mode Êups Startup and Shutdown Standby ModeStarting the UPS Starting the UPS on Battery ÊRetrieving the Event Log ÊTransferring the UPS Between ModesUPS Shutdown ÊConfiguring Bypass Settings ÊSetting Power StrategyÊConfiguring Load Segments Operation Configuring the UPS for EBMs ÊConfiguring Battery SettingsAll UPS and EBM Cabinets Configuring Automatic Restart Running Automatic Battery TestsCommunication Independent Multiplexed Communication Bay ÊInstalling Communication Options and Control TerminalsÊCommunication Options RS-232 and USB Communication PortsGND Pin Number Signal Name Function Direction from the UPSConnectivity Cards Remote Emergency Power-offRepo Connections Signal Description Relay Output Configuration OptionsRelay Output Contacts Input Description Programmable Signal InputsProgrammable Signal Inputs Polarity OptionsÊModem Operation ÊPowerware LanSafe Power Management SoftwareÊups and Battery Care UPS MaintenanceÊStoring the UPS and Batteries ÊWhen to Replace BatteriesÊReplacing Batteries Replacing Rackmount UPS Internal Batteries Disconnecting the UPS Internal Batteries Shown without EBMs U T I O N Replacing Tower UPS Internal Batteries Replacing the UPS Internal Batteries U T I O N Replacing Rackmount EBMs UPS Maintenance Replacing Tower EBMs ÊTesting New Batteries ÊUpdating the UPS Firmware ÊRecycling the Used Battery or UPSUPS Maintenance Extended Battery Module Model List ÊModel SpecificationsCommunication Options All Models UPS Model List Rackmount Models Model Power Level Rear Panel DiagramUPS Model List Tower Models Model Rackmount UPS Dimensions H W D Weight Weights and Dimensions Rackmount ModelsModel Rackmount EBM Electrical Input All Models Weights and Dimensions Tower ModelsElectrical Input Rackmount Models Model Default Input Selectable Input Voltage RangeElectrical Input Tower Models Model Input Connection Input Cable Electrical Input Connections Rackmount ModelsElectrical Input Connections Tower Models Electrical Output All Models Model Output Connections Output Cables Electrical Output Connections Rackmount ModelsElectrical Output Connections Tower Models Environmental and Safety All Models Model Internal Batteries + 1 EBM + 2 EBMs + 3 EBMs + 4 EBMs Battery Runtimes in Minutes at 100% Load Rack ModelsBattery Runtimes in Minutes at 100% Load Tower Models Internal Batteries EBMs BatteryModels PW9130L700R-XL2U, PW9130L1000R-XL2U ÊRear PanelsModel PW9130G1000R-XL2UAU Model PW9130L2000R-XL2U Models PW9130L2500R-XL2U, PW9130L3000R-XL2U Model PW9130L1500T-XL Model PW9130G2000T-XL Model PW9130i1500T-XL Model PW9130G1000T-XLAU Model PW9130G2000T-XLAU 100 ÊTypical Alarms and Conditions TroubleshootingBattery is running low Alarm or Condition Possible Cause ActionLED is on Beep every second Models Only. Ground wireUPS does not start ÊService and Support ÊSilencing the Alarm106 ÊTwo-Year Limited Warranty US and Canada Chapter WarrantyWarranty ÊTen-Year Pro-Rated Limited Warranty US and Canada 110 ÊLoad Protection Guarantee US and Canada 112