Eaton Electrical 9130 manual Frequency Converter Enabled Disabled

Page 49

OPERATION

Table 3. User Settings (continued)

Description

Available Settings

Default Setting

 

 

 

Frequency Converter

[Enabled] [Disabled]

Disabled

 

If Enabled, the UPS operates as a frequency

 

 

converter, with bypass operation and all

 

 

bypass-related alarms disabled.

 

 

 

 

Overload Alarm Level

[10%] [20%] [30%] ... [100%]

100%

 

These values affect alarm level only, not UPS

Generates the Output Overload

 

operation such as transfers or shutdown.

alarm at the set level.

 

 

 

Transfer to Bypass When Overload*

[Immediate] [After Delay]

Immediate

 

If Immediate, transfer occurs at load >102%.

 

 

If After Delay, transfer occurs according to

 

 

Table 19 on page 84.

 

 

 

 

Power Strategy

[Normal] [High Efficiency]

Normal

 

See “Setting Power Strategy” on page 48.

 

 

 

 

Automatic Start Delay

[Disabled] [No Delay] [1s] [2s]...[32767s]

Load Segment 1: No Delay

 

If Disabled, automatic restart is not allowed.

Load Segment 2: No Delay

 

See “Configuring Load Segments” on page 49.

 

 

 

 

Automatic on Battery Shutdown

[Disabled] [No Delay] [1s] [2s]...[32767s]

Load Segment 1: Disabled

 

Shutdown cancels if utility returns before the

Load Segment 2: Disabled

 

delay expires. See “Configuring Load

 

 

Segments” on page 49.

 

 

 

 

Start on Battery

NOTE Utility must be present and output enabled at initial UPS startup.

[Enabled] [Disabled]

Enabled

After initial startup, battery voltage must

 

exceed 2.10 volts per cell to start on battery.

 

Energy Saving Mode

[Disabled] [50W] [100W] ... [1000W]

Disabled

 

UPS output is turned off if the UPS is on

 

 

battery and output power is below the

 

 

selected level.

 

 

 

 

Remote Shutdown Delay

[No Delay] [1s] [2s]...[10800s]

No Delay

 

 

 

Delayed Shutdown Delay

[No Delay] [1s] [2s]...[10800s]

120s

 

 

 

Behavior on Rectifier Input Loss

NOTE Available only in >3000 VA UPSs with separate supply sources for the rectifier and bypass inputs.

[Prefer Battery] [Prefer Bypass]

Prefer Battery

If Prefer Bypass, upon loss the UPS will

 

transfer to bypass in 3 seconds and remain as

 

long as bypass is available.

 

On Battery Notice Delay

[0] [1s] [2s]...[99s]

5s

 

 

 

* See “Configuring Bypass Settings” on page 48.

Eaton® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com

41

Image 49
Contents Eaton 9130 UPS 700-3000 VA Users Guide FCC Part ICES-003 Class a EMC Statements Low Voltage Models over 1500 VAClass B EMC Statements Requesting a Declaration of Conformity Special SymbolsTable of Contents Specifications UPS MaintenanceTroubleshooting 101107 WarrantyTable of Contents Chapter Introduction Shows the Eaton 9130 tower UPS and optional EBM R N I N G N G E RSikkerhedsanvisninger U T I O NR E Belangrijke Veiligheidsinstructies V a R S E LV a a R A R S C H U W I N GTarkeita Turvaohjeita G E L E TA R a R O I T U SConsignes de sécurité R OR N U N G SicherheitswarnungenAvvisi di sicurezza H T U N GV E R T E N Z a R I C O L OT E N Z I O N E R L I G Viktig SikkerhetsinformasionR S I K T I G I D a D O Regulamentos de SegurançaV E R T Ê N C I a R I G OÏðåäóïðåæäåíèå ÏàñíîAdvertencias de Seguridad ÎñòîðîæíîL I G R O V E R T E N C I aSäkerhetsföreskrifter E C a U C I Ó NR a K T I G T ÊInspecting the Equipment Chapter InstallationÊUnpacking the Cabinet ÊChecking the Accessory KitChecking the Rail Kit Accessories ÊRackmount InstallationTools Required Assembling the Rails Rackmount SetupSecuring the Rails Installing the Mounting Brackets Forward Position Shown Installing the UPS ÊRackmount Wiring InstallationRemoving the UPS Right Front Cover Connecting the UPS Internal Batteries Removing the EBM Cable Knockout Connecting the EBMsRemoving the EBM Front Cover Typical EBM Installation ÊTower Installation Removing the UPS Front Cover ÊTower Wiring InstallationConnecting the UPS Internal Batteries Connecting the EBMs Connecting the EBMs To start up the UPS Êups Initial StartupInstallation Installation Eaton 9130 Control Panel ÊControl Panel Functions Indicator Status Description Indicator Descriptions Changing the Language Display FunctionsMain Menu Submenu Display Information or Menu Function Menu Map for Display FunctionsUser Settings Description Available Settings Default Setting User SettingsFrequency Converter Enabled Disabled When in Spec Battery Mode Normal ModeÊOperating Modes Bypass Mode Êups Startup and Shutdown Standby ModeStarting the UPS Starting the UPS on Battery ÊRetrieving the Event Log ÊTransferring the UPS Between ModesUPS Shutdown ÊConfiguring Bypass Settings ÊSetting Power StrategyÊConfiguring Load Segments Operation Configuring the UPS for EBMs ÊConfiguring Battery SettingsAll UPS and EBM Cabinets Configuring Automatic Restart Running Automatic Battery TestsCommunication ÊCommunication Options ÊInstalling Communication Options and Control TerminalsRS-232 and USB Communication Ports Independent Multiplexed Communication BayGND Pin Number Signal Name Function Direction from the UPSConnectivity Cards Remote Emergency Power-offRepo Connections Signal Description Relay Output Configuration OptionsRelay Output Contacts Programmable Signal Inputs Programmable Signal InputsPolarity Options Input DescriptionÊModem Operation ÊPowerware LanSafe Power Management SoftwareÊups and Battery Care UPS MaintenanceÊStoring the UPS and Batteries ÊWhen to Replace BatteriesÊReplacing Batteries Replacing Rackmount UPS Internal Batteries Disconnecting the UPS Internal Batteries Shown without EBMs U T I O N Replacing Tower UPS Internal Batteries Replacing the UPS Internal Batteries U T I O N Replacing Rackmount EBMs UPS Maintenance Replacing Tower EBMs ÊTesting New Batteries ÊUpdating the UPS Firmware ÊRecycling the Used Battery or UPSUPS Maintenance Extended Battery Module Model List ÊModel SpecificationsCommunication Options All Models UPS Model List Rackmount Models Model Power Level Rear Panel DiagramUPS Model List Tower Models Model Rackmount UPS Dimensions H W D Weight Weights and Dimensions Rackmount ModelsModel Rackmount EBM Electrical Input All Models Weights and Dimensions Tower ModelsElectrical Input Rackmount Models Model Default Input Selectable Input Voltage RangeElectrical Input Tower Models Model Input Connection Input Cable Electrical Input Connections Rackmount ModelsElectrical Input Connections Tower Models Electrical Output All Models Model Output Connections Output Cables Electrical Output Connections Rackmount ModelsElectrical Output Connections Tower Models Environmental and Safety All Models Model Internal Batteries + 1 EBM + 2 EBMs + 3 EBMs + 4 EBMs Battery Runtimes in Minutes at 100% Load Rack ModelsBattery Runtimes in Minutes at 100% Load Tower Models Internal Batteries EBMs BatteryModels PW9130L700R-XL2U, PW9130L1000R-XL2U ÊRear PanelsModel PW9130G1000R-XL2UAU Model PW9130L2000R-XL2U Models PW9130L2500R-XL2U, PW9130L3000R-XL2U Model PW9130L1500T-XL Model PW9130G2000T-XL Model PW9130i1500T-XL Model PW9130G1000T-XLAU Model PW9130G2000T-XLAU 100 ÊTypical Alarms and Conditions TroubleshootingBattery is running low Alarm or Condition Possible Cause ActionLED is on Beep every second Models Only. Ground wireUPS does not start ÊService and Support ÊSilencing the Alarm106 ÊTwo-Year Limited Warranty US and Canada Chapter WarrantyWarranty ÊTen-Year Pro-Rated Limited Warranty US and Canada 110 ÊLoad Protection Guarantee US and Canada 112