UPS MAINTENANCE
2.Remove and retain the two screws holding the internal battery connector. Disconnect the internal battery connector. See Figure 26.
Internal | Battery Cover Plate |
Battery |
|
Connector |
|
Battery Tray Handle
Figure 26. Replacing the UPS Internal Batteries
3.Remove and retain the two screws holding the battery cover plate. Grasp an edge of the battery cover plate and pull it forward gently. Remove and retain the battery cover plate.
4.Carefully pull the handle on the battery tray and slide the battery package slowly out onto a flat, stable surface; use two hands to support the battery package. See “Recycling the Used Battery or UPS” on page 73 for proper disposal.
NOTE Verify that the replacement batteries have the same rating as the batteries being replaced.
5.Slide the new battery package into the cabinet. Push the battery package in firmly.
Eaton® 9130 UPS | 67 |