Error Code | Message Information |
|
| LCD Message | PSU redundancy degraded. Check PSU cables. |
| Details | The current power operational mode is |
|
| because of a power supply exception, a power supply |
|
| inventory change, or a system power inventory change. |
| Action | Check the event log for power supply failures. Review |
|
| system configuration and power consumption. |
PWR1001 | Message | The system performance was degraded. |
| ||
| LCD Message | System performance degraded. Check PSUs and system |
|
| configuration. |
| Details | To avoid shutdown, system performance has been degraded. |
| Action | Review system configuration and system logs for thermal or |
|
| environmental failures and warnings. |
PWR1002 | Message | The system performance degraded because of thermal |
| ||
|
| protection. |
| Details | To avoid shutdown, system performance has been degraded. |
| Action | Review system configuration and system logs for thermal or |
|
| environmental failures and warnings. |
PWR1003 | Message | The system performance degraded because cooling capacity |
| ||
|
| has changed. |
| Details | The current power supply configuration does not meet the |
|
| platform requirements to enable redundancy. If a power |
|
| supply fails the system may shutdown. |
| Action | If unintended, review system configuration and power |
|
| consumption and install power supplies accordingly. Check |
|
| power supply status for failures. |
PWR1004 | Message | The system performance degraded because power capacity |
| ||
|
| has changed. |
| Details | The system may power down or operate in a performance |
|
| degraded state. |
| Action | Check the event log for power supply failures. Review |
|
| system configuration and power consumption and upgrade |
|
| or install power supplies accordingly. |
PWR1005 | Message | The system performance degraded because the user- |
|
defined power capacity has changed.