Thomas & Betts Limitorque MX Device Net Field Unit manual Cable Preparation

Page 14

Limitorque MX DeviceNet Field Unit  FCD LMENIM2328-00 – 11/05

Figure 3.1 – Network cable connection to terminal block

NOTE: Recommended DeviceNet cable is Belden 3084A or equal. 121 ohm, ¼ W +/-1% termination resistors must be connected at each segment end. Customer is required to connect wire between terminal 30 and chassis ground for surge protection. Preferred network wiring is to connect shield to terminal 48 for only one unit on each segment. Connect remaining individual network cable shields together to ensure proper shielding of entire network. Consult wiring diagram for exact terminal connection points as they may change.

Prepare the network cable for connection to the MX terminal block as follows.

aCAUTION: Strip stranded conductors carefully; do not damage the strands. This will weaken the conductor. Do not nick conductors or conductor insulation when stripping away the insulation. Nicking stresses the conductor and can cause the conductor to break. This type of damage may not be apparent and failure can occur later without warning.

NOTE: Excess cable should be cut, not coiled or looped, to prevent noise induction into the network and to reduce signal loss through unnecessarily long cable runs.

Cable Preparation

1.Remove two to three inches (5 to 8 cm) of the outer plastic jacket.

2.Separate the cable parts. Unbraid the shield and peel back the foil shield to the same point where the outer jacket was removed. Cut away the braided shield and the foil shield. Strip the insulation from the conductors approximately 0.4 inch (1 cm).

3.Apply heat shrink tubing to insulate the drain wire and to provide stress relief to the cable.

aCAUTION: Do not melt the insulation. NOTE: Ungrounded drain wires should be cut even with the cable sheath. The brand foil and drain wire should have heat shrink tubing applied.

4.Install ring tongue connectors. Flowserve recommends the use of Thomas & Betts #RZ22-6 for optimum results.

5.Connect the network cables to the MX terminal block as shown in Wiring Diagram #18-499-0038-3.

Table 3.1

48

15

16

1429

41

30

Shield

(Blue) DATA (-)

(White) DATA (+)

(Black) Network 0 V

(Red) Network 24V

Earth ground for surge protection circuit

Image 14
Contents User Instructions Disclaimer Contents EDS File Declaration of Conformity to the DeviceNet Specification Declaration of DeviceNet Conformance Odva CertificationAbbreviations Introduction Purpose How to Use this ManualUser Safety User Knowledge DeviceNet System Capabilities and FeaturesGeneral Specifications Network specifications MX Field Unit SpecificationsHardware System ComponentsIntroduction Limitorque MX DeviceNet Field Unit DeviceNet Field UnitNetwork Cable Belden Cable SpecificationsHardware interface Site Preparation Installation and ConfigurationSite and Network Cable Preparation Network Cable PreparationCable Preparation Dnfu Installation Verification Installation VerificationNetwork Cabling Installation Verification Object Model Diagram Assembly ObjectsOutput Assembly Instances Output Assembly InstanceClass Instance Attribute Data Name Type Input Assembly Instance 10 Input Assembly Instance 11 Input Assembly Instance14 Possible values of DIPositionChan DIPositionandBusModeChanDIPositionChan 16 Possible values of DIActuatorFaults1Chan DIActuatorFaults2ChanDIActuatorAlarmsChan 18 Possible values of DIActuatorFaults2ChanDIReadDiscOutputChan 20 Possible values of DIActuatorAlarmsChanDIDiscUserInputChan DOPositionChanDORelayChan DIActuatorFaults3ChanDIAlarms2Chan CtrlStatusChanName Data Description Bit 7 Bit Reserved Low BatteryChannel Interface Object Type AttributeTransducer Block Object Name Data Type Description Semantics of ValueName Data Type Description Semantics of Value 33 Transducer Attribute Scaled values attribute Bit 7Bit 15 Bit 10 Identity Object Instance Attributes35 Identity Object Instance Attributes Description Semantics of Value AttributeEvent Source Description Behavior36 Behavior Name Data Description Semantics of Value Type Attribute DeviceNet Object Instance Attributes37 DeviceNet Object Instance Attributes Instance ID Channel Interface Object Source Discrete Input Point Object Class ID 8 08hex38 Discrete Input Point Object Analog Output Point Object Class ID 11 0Bhex Discrete Output Point Object Class ID 9 09hexAnalog Input Point Object Class ID 10 0Ahex 39 Discrete Output Point ObjectBaud Rate Network ManagementMAC ID Offline Connection Set Device Heartbeat MessageChecking Connections Configuration ConfirmationDevice Shutdown Message 43 Format of the Device Shutdown MessageView Settings View DeviceNet StatusChecking the Normal Display Associated Documents TroubleshootingAccess Path to Object EDS FileWorkmanship How to Order Parts Regulatory InformationWiring Diagram Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 11/05 Flowserve.com Flowserve.com