Thomas & Betts Limitorque MX Device Net Field Unit manual Checking the Normal Display

Page 37

Limitorque MX DeviceNet Field Unit  FCD LMENIM2328-00 – 11/05

The device has not completed the self test yet.

The device may not be powered, look at Module Status Display.

"ONLINE" = Device is on-line but has no connections in the established state.

The device has passed the SELF test, is on-line, bus has no established connections to other nodes.

For a Group 2 Only device it means that this device is not allocated to a master.

For a UCMM capable device it means that the device has no established connections.

"CONNECTED" = The device is on-line and has connections in the established state.

For a Group 2 Only device it means that the device is allocated to a Master.

For a UCMM capable device it means that the device has one or more established connections.

"CONN TIMEOUT" = One or more I/O Connections are in the Timed-Out state.

"COMM FAULT" = Failed communication device. The device has detected an error that has rendered it incapable of communicating on the network (Duplicate MAC ID, or Bus-off).

"ID COM FLT REQ" = A specific Communication Faulted device. The device has detected a Network Access error and is in the Communication Faulted state. The device has subsequently received and accepted an Identify Communication Faulted Request Long Protocol message.

5.1Checking the Normal Display

Place the selector switch in “LOCAL” or “REMOTE” position. The valve position will be indicated at the top of the LCD. “STATUS OK” or “DNET COMM LOSS” should be indicated at the bottom of the LCD display.

If “STATUS OK” is displayed, the DNFU is communicating with the DeviceNet network.

If “DNET COMM LOSS” is displayed, no communication is occurring. This could be due to a number of factors, including problems with the host DeviceNet system and/or network. Check all local connections and configurations. Confirm that the host is connected, configured for baud rate, protocol to match DeviceNet, and operational. See also Section 7, Troubleshooting.

Figure 5.2

Remote

 

Remote

 

or

100% OPEN

or

100% OPEN

 

STATUS OK

 

DNET COMM LOSS

Local

 

Local

 

37

flowserve.com

Image 37
Contents User Instructions Disclaimer Contents EDS File Declaration of DeviceNet Conformance Odva Certification Declaration of Conformity to the DeviceNet SpecificationAbbreviations User Safety Purpose How to Use this ManualIntroduction General Specifications DeviceNet System Capabilities and FeaturesUser Knowledge MX Field Unit Specifications Network specificationsIntroduction System ComponentsHardware Limitorque MXDeviceNet Field Unit DeviceNet Field UnitHardware interface Belden Cable SpecificationsNetwork Cable Site and Network Cable Preparation Installation and ConfigurationSite Preparation Network Cable PreparationCable Preparation Network Cabling Installation Verification Installation VerificationDnfu Installation Verification Assembly Objects Object Model DiagramOutput Assembly Instance Output Assembly InstancesClass Instance Attribute Data Name Type Input Assembly Instance 11 Input Assembly Instance 10 Input Assembly InstanceDIPositionChan DIPositionandBusModeChan14 Possible values of DIPositionChan DIActuatorAlarmsChan DIActuatorFaults2Chan16 Possible values of DIActuatorFaults1Chan 18 Possible values of DIActuatorFaults2ChanDIDiscUserInputChan 20 Possible values of DIActuatorAlarmsChanDIReadDiscOutputChan DOPositionChanDIAlarms2Chan DIActuatorFaults3ChanDORelayChan CtrlStatusChanChannel Interface Object Bit 7 Bit Reserved Low BatteryName Data Description Type AttributeName Data Type Description Semantics of Value Transducer Block ObjectName Data Type Description Semantics of Value Bit 7 33 Transducer Attribute Scaled values attribute35 Identity Object Instance Attributes Identity Object Instance AttributesBit 15 Bit 10 Description Semantics of Value Attribute36 Behavior BehaviorEvent Source Description 37 DeviceNet Object Instance Attributes DeviceNet Object Instance AttributesName Data Description Semantics of Value Type Attribute 38 Discrete Input Point Object Discrete Input Point Object Class ID 8 08hexInstance ID Channel Interface Object Source Analog Input Point Object Class ID 10 0Ahex Discrete Output Point Object Class ID 9 09hexAnalog Output Point Object Class ID 11 0Bhex 39 Discrete Output Point ObjectMAC ID Network ManagementBaud Rate Offline Connection Set Device Heartbeat MessageDevice Shutdown Message Configuration ConfirmationChecking Connections 43 Format of the Device Shutdown MessageView DeviceNet Status View SettingsChecking the Normal Display Access Path to Object TroubleshootingAssociated Documents EDS FileWorkmanship Regulatory Information How to Order PartsWiring Diagram Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 11/05 Flowserve.com Flowserve.com