Thomas & Betts Limitorque MX Device Net Field Unit manual Installation Verification

Page 15

Limitorque MX DeviceNet Field Unit  FCD LMENIM2328-00 – 11/05

NOTE: Ground each segment of the cabling at only one point to prevent ground loops, which can affect system performance. Verify the actuator is properly grounded.

6. Install jumper cable from terminal block pin 30 to earth ground or ground lug.

3.2Installation Verification

3.2.1Network Cabling Installation Verification

After installation is complete and prior to operation, inspect the network cable and its connection to each field unit for the following:

NOTE: Units should be disconnected from power. Network should be disconnected from host.

1.There should be:

No nicks in the insulation—this can cause a short between conductors or to the grounded shield.

No cut strands in a stranded conductor—this can cause a poor connection and eventually an open circuit.

2.Verify that there is data wiring on each actuator per wiring diagram.

3.Cable armor should not be shorted to the cable shield/drain wire. Cable armor may not be at ground potential and could be subject to lightning surges.

The shield/drain wire should only be grounded at one end of each cable segment (the section between adjacent actuators between the host system and an actuator) to avoid ground loop problems.

The ground/earth connection should be at true ground potential and effective at all times. See Section 3.1.1, Site Preparation.

3.2.2DNFU Installation Verification

NOTE: Connect to either 24 V DC power or mains and activate power.

Verify the field unit is installed as follows:

1.Enter the “SETUP” mode as detailed in Bulletin LMAIM1306/2306, MX Installation and Operation Manual.

2.In the “SETUP” mode, use the black control knob to select “YES” to the main menu selection “VIEW

DIAGNOSTICS?”

3.Select “YES” to the display “VIEW HARDWARE STATUS?”

4.Select “YES” to scroll through the menu selections. The LCD will read “DeviceNet (OK) – NEXT?” if installed.

NOTE: If the “DeviceNet (OK) – NEXT?” does not appear, contact Flowserve for assistance.

19. To return to the normal display, use the red knob to select either “LOCAL” or “REMOTE.”

15

flowserve.com

Image 15
Contents User Instructions Disclaimer Contents EDS File Declaration of DeviceNet Conformance Odva Certification Declaration of Conformity to the DeviceNet SpecificationAbbreviations Purpose How to Use this Manual User SafetyIntroduction DeviceNet System Capabilities and Features General SpecificationsUser Knowledge MX Field Unit Specifications Network specificationsLimitorque MX System ComponentsIntroduction HardwareDeviceNet Field Unit DeviceNet Field Unit Belden Cable Specifications Hardware interface Network Cable Network Cable Preparation Installation and ConfigurationSite and Network Cable Preparation Site PreparationCable Preparation Installation Verification Network Cabling Installation VerificationDnfu Installation Verification Assembly Objects Object Model DiagramOutput Assembly Instance Output Assembly InstancesClass Instance Attribute Data Name Type Input Assembly Instance 11 Input Assembly Instance 10 Input Assembly InstanceDIPositionandBusModeChan DIPositionChan14 Possible values of DIPositionChan 18 Possible values of DIActuatorFaults2Chan DIActuatorFaults2ChanDIActuatorAlarmsChan 16 Possible values of DIActuatorFaults1ChanDOPositionChan 20 Possible values of DIActuatorAlarmsChanDIDiscUserInputChan DIReadDiscOutputChanCtrlStatusChan DIActuatorFaults3ChanDIAlarms2Chan DORelayChanType Attribute Bit 7 Bit Reserved Low BatteryChannel Interface Object Name Data DescriptionName Data Type Description Semantics of Value Transducer Block ObjectName Data Type Description Semantics of Value Bit 7 33 Transducer Attribute Scaled values attributeDescription Semantics of Value Attribute Identity Object Instance Attributes35 Identity Object Instance Attributes Bit 15 Bit 10Behavior 36 BehaviorEvent Source Description DeviceNet Object Instance Attributes 37 DeviceNet Object Instance AttributesName Data Description Semantics of Value Type Attribute Discrete Input Point Object Class ID 8 08hex 38 Discrete Input Point ObjectInstance ID Channel Interface Object Source 39 Discrete Output Point Object Discrete Output Point Object Class ID 9 09hexAnalog Input Point Object Class ID 10 0Ahex Analog Output Point Object Class ID 11 0BhexOffline Connection Set Device Heartbeat Message Network ManagementMAC ID Baud Rate43 Format of the Device Shutdown Message Configuration ConfirmationDevice Shutdown Message Checking ConnectionsView DeviceNet Status View SettingsChecking the Normal Display EDS File TroubleshootingAccess Path to Object Associated DocumentsWorkmanship Regulatory Information How to Order PartsWiring Diagram Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 11/05 Flowserve.com Flowserve.com