Thomas & Betts Limitorque MX Device Net Field Unit manual Installation and Configuration

Page 13

Limitorque MX DeviceNet Field Unit  FCD LMENIM2328-00 – 11/05

Table 2.3 – Total cable length between repeaters or nodes:

Network Size

125 KBPS

250 KBPS

500 KBPS

 

 

 

 

Thick Trunk Length

500 m (1,640 ft)

250 m (1,640 ft)

100 m (1,640 ft)

 

 

 

 

Thin Trunk Length

100 m (328 ft)

100 m (328 ft)

100 m (328 ft)

 

 

 

 

Flat Trunk Length

380 m (1,250 ft)

200 m (656 ft)

75 m (246 ft)

 

 

 

 

Maximum Drop Length

6 m (20 ft)

6 m (20 ft)

6 m (20 ft)

 

 

 

 

Cumulative Drop Length

156 m (512 ft)

78 m (256 ft)

39 m (128 ft)

 

 

 

 

Note: Each actuator includes 0.60 meters of internal drop length.

3 Installation and Configuration

3.1Site and Network Cable Preparation

3.1.1Site Preparation

Prepare the site and associated equipment for operation of the DeviceNet controlled MX actuators as follows:

1.Prepare a detailed site plan consisting of the following:

Actuator locations, tag numbers, DeviceNet addresses

Junction boxes, terminal strip locations, and tag numbers

2.Provide free access to the MX control panel and terminal block for setup, configuration, and troubleshooting.

3.Prepare cable and label all wires. See Section 3.1.2, Network Cable Preparation.

4.Install power and control wires in separate conduits. Shielding is not sufficient to prevent induction of stray voltages onto signal leads from the power lines.

5.Install and verify earth grounds.

NOTE: Limitorque defines an effective local earth ground as a low impedance (less than 5 ohms) path to:

A ground electrode placed in close vicinity of the actuator that is free of ground loop currents. OR

A safety ground that is free of ground loop currents running from the actuator back to the system ground electrode. If the signal wiring is run on aerial cable where it may be exposed to high- energy electrostatic discharge (such as lightning), a low impedance path to ground that is capable of high current must be provided a short distance from the actuator as described above. OR

A power distribution grid identifying the impact of power isolation to a particular actuator or group of actuators should be provided.

3.1.2Network Cable Preparation

3.1.2.1Network Cable Connection to the Field Unit

The DeviceNet field unit is connected to the network via the MX terminal block. The network cable is connected to the terminal block as shown in Figure 3.1.

13

flowserve.com

Image 13
Contents User Instructions Disclaimer Contents EDS File Declaration of DeviceNet Conformance Odva Certification Declaration of Conformity to the DeviceNet SpecificationAbbreviations User Safety Purpose How to Use this ManualIntroduction General Specifications DeviceNet System Capabilities and FeaturesUser Knowledge MX Field Unit Specifications Network specificationsIntroduction System ComponentsHardware Limitorque MXDeviceNet Field Unit DeviceNet Field UnitHardware interface Belden Cable SpecificationsNetwork Cable Site and Network Cable Preparation Installation and ConfigurationSite Preparation Network Cable PreparationCable Preparation Network Cabling Installation Verification Installation VerificationDnfu Installation Verification Assembly Objects Object Model DiagramOutput Assembly Instance Output Assembly InstancesClass Instance Attribute Data Name Type Input Assembly Instance 11 Input Assembly Instance 10 Input Assembly InstanceDIPositionChan DIPositionandBusModeChan14 Possible values of DIPositionChan DIActuatorAlarmsChan DIActuatorFaults2Chan16 Possible values of DIActuatorFaults1Chan 18 Possible values of DIActuatorFaults2ChanDIDiscUserInputChan 20 Possible values of DIActuatorAlarmsChanDIReadDiscOutputChan DOPositionChanDIAlarms2Chan DIActuatorFaults3ChanDORelayChan CtrlStatusChanChannel Interface Object Bit 7 Bit Reserved Low BatteryName Data Description Type AttributeName Data Type Description Semantics of Value Transducer Block ObjectName Data Type Description Semantics of Value Bit 7 33 Transducer Attribute Scaled values attribute35 Identity Object Instance Attributes Identity Object Instance AttributesBit 15 Bit 10 Description Semantics of Value Attribute36 Behavior BehaviorEvent Source Description 37 DeviceNet Object Instance Attributes DeviceNet Object Instance AttributesName Data Description Semantics of Value Type Attribute 38 Discrete Input Point Object Discrete Input Point Object Class ID 8 08hexInstance ID Channel Interface Object Source Analog Input Point Object Class ID 10 0Ahex Discrete Output Point Object Class ID 9 09hexAnalog Output Point Object Class ID 11 0Bhex 39 Discrete Output Point ObjectMAC ID Network ManagementBaud Rate Offline Connection Set Device Heartbeat MessageDevice Shutdown Message Configuration ConfirmationChecking Connections 43 Format of the Device Shutdown MessageView DeviceNet Status View SettingsChecking the Normal Display Access Path to Object TroubleshootingAssociated Documents EDS FileWorkmanship Regulatory Information How to Order PartsWiring Diagram Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 11/05 Flowserve.com Flowserve.com