Thomas & Betts Limitorque MX Device Net Field Unit manual Network specifications

Page 9

Limitorque MX DeviceNet Field Unit  FCD LMENIM2328-00 – 11/05

Table 1.1 – Network specifications

Network Size

Up to 63 Nodes

 

 

Network Length

Selectable end-to-end network distance varies with speed

 

125 Kbps 500 m (1,640 ft)

 

250 Kbps 250 m (820 ft)

 

500 Kbps 100 m (328 ft)

Bus Topology

Linear (trunkline/dropline); power and signal on the same network cable

Bus Addressing

Multi-Master and Master/Slave special case; polled of change-of-state

 

(exception-based)

System Features

Selectable end-to-end network distance varies with speed

Termination resistor (121 ohms) must be used at each end of the network

1.5.1.2MX Field Unit Specifications

CIP Generic Device Profile (Device Type = 00hex) extended to DNFU requirements

Group 2 Server

UCMM capable device

Predefined Master/Slave Connection Set supporting

Explicit Connection

Polled I/O Connection

Bit-Strobed I/O Connection

Change of State / Cyclic I/O Connection

Full support of fragmentation protocol

Device Heartbeat Message

Device Shutdown Message

Offline Connection Set

Galvanical Isolation: The isolation voltage for the DNFU is up to 1,500 VRMS for 1 minute (1,800 VRMS for 1 second

Power Supply: The DNFU Interface will be powered from the DeviceNet bus. A switching regulator is

used to generate the internal supply voltage: VCC nominal 5.0 V ± 5 %

Surge Suppression: The DNFU Interface is equipped with surge suppression for the DeviceNet network data and power lines. Surge suppression is compliant with IEC 61000-6-2:2001.

Environmental conditions

The DNFU environmental parameters are within the same environmental constraints as the actuator.



flowserve.com

Image 9
Contents User Instructions Disclaimer Contents EDS File Declaration of DeviceNet Conformance Odva Certification Declaration of Conformity to the DeviceNet SpecificationAbbreviations Purpose How to Use this Manual User SafetyIntroduction DeviceNet System Capabilities and Features General SpecificationsUser Knowledge MX Field Unit Specifications Network specificationsIntroduction System ComponentsHardware Limitorque MXDeviceNet Field Unit DeviceNet Field UnitBelden Cable Specifications Hardware interfaceNetwork Cable Site and Network Cable Preparation Installation and ConfigurationSite Preparation Network Cable PreparationCable Preparation Installation Verification Network Cabling Installation VerificationDnfu Installation Verification Assembly Objects Object Model DiagramOutput Assembly Instance Output Assembly InstancesClass Instance Attribute Data Name Type Input Assembly Instance 11 Input Assembly Instance 10 Input Assembly InstanceDIPositionandBusModeChan DIPositionChan14 Possible values of DIPositionChan DIActuatorAlarmsChan DIActuatorFaults2Chan16 Possible values of DIActuatorFaults1Chan 18 Possible values of DIActuatorFaults2ChanDIDiscUserInputChan 20 Possible values of DIActuatorAlarmsChanDIReadDiscOutputChan DOPositionChanDIAlarms2Chan DIActuatorFaults3ChanDORelayChan CtrlStatusChanChannel Interface Object Bit 7 Bit Reserved Low BatteryName Data Description Type AttributeName Data Type Description Semantics of Value Transducer Block ObjectName Data Type Description Semantics of Value Bit 7 33 Transducer Attribute Scaled values attribute35 Identity Object Instance Attributes Identity Object Instance AttributesBit 15 Bit 10 Description Semantics of Value AttributeBehavior 36 BehaviorEvent Source Description DeviceNet Object Instance Attributes 37 DeviceNet Object Instance AttributesName Data Description Semantics of Value Type Attribute Discrete Input Point Object Class ID 8 08hex 38 Discrete Input Point ObjectInstance ID Channel Interface Object Source Analog Input Point Object Class ID 10 0Ahex Discrete Output Point Object Class ID 9 09hexAnalog Output Point Object Class ID 11 0Bhex 39 Discrete Output Point ObjectMAC ID Network ManagementBaud Rate Offline Connection Set Device Heartbeat MessageDevice Shutdown Message Configuration ConfirmationChecking Connections 43 Format of the Device Shutdown MessageView DeviceNet Status View SettingsChecking the Normal Display Access Path to Object TroubleshootingAssociated Documents EDS FileWorkmanship Regulatory Information How to Order PartsWiring Diagram Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 11/05 Flowserve.com Flowserve.com