Limitorque MX DeviceNet Field Unit FCD
Table 1.1 – Network specifications
Network Size | Up to 63 Nodes |
|
|
Network Length | Selectable |
| 125 Kbps 500 m (1,640 ft) |
| 250 Kbps 250 m (820 ft) |
| 500 Kbps 100 m (328 ft) |
Bus Topology | Linear (trunkline/dropline); power and signal on the same network cable |
Bus Addressing | |
| |
System Features | Selectable |
Termination resistor (121 ohms) must be used at each end of the network
1.5.1.2MX Field Unit Specifications
•CIP Generic Device Profile (Device Type = 00hex) extended to DNFU requirements
•Group 2 Server
•UCMM capable device
•Predefined Master/Slave Connection Set supporting
•Explicit Connection
•Polled I/O Connection
•
•Change of State / Cyclic I/O Connection
•Full support of fragmentation protocol
•Device Heartbeat Message
•Device Shutdown Message
•Offline Connection Set
•Galvanical Isolation: The isolation voltage for the DNFU is up to 1,500 VRMS for 1 minute (1,800 VRMS for 1 second
•Power Supply: The DNFU Interface will be powered from the DeviceNet bus. A switching regulator is
used to generate the internal supply voltage: VCC nominal 5.0 V ± 5 %
•Surge Suppression: The DNFU Interface is equipped with surge suppression for the DeviceNet network data and power lines. Surge suppression is compliant with IEC
Environmental conditions
The DNFU environmental parameters are within the same environmental constraints as the actuator.