Thomas & Betts Limitorque MX Device Net Field Unit manual Output Assembly Instances

Page 17

Limitorque MX DeviceNet Field Unit  FCD LMENIM2328-00 – 11/05

An output is a signal produced at the PLC and sent to the actuator via the network.

The user may select one output and one input instance.

The default assembly objects are as follows: Polled input - 105, Polled output - 100, Bitstrobe - 107,

COS - 109.

Table 4.1

Instance ID

Type

Data Component Name

Size

100

Output

Output 1 (All Control Channels)

9

101

Output

Output 2

(Analog Control and ESD only)

5

102

Output

Output 3

(Discrete Control and ESD only)

4

103

Output

Output 4

(Analog Control only)

3

104

Output

Output 5

(Discrete Control only)

3

105

Input

Input 1 (All Status Information)

16

106

Input

Input 2

(Position and Faults only)

6

107

Input

Input 3

(Position and Faults only)

8

108

Input

Input 4

(Position, User and Faults only)

11

109

Input

Input 5

(Faults and Alarms only)

6

4.2Output Assembly Instances

Table 4.2 – Output Assembly Instance 100

Assembly

Object

Instance ID

100

Data

Class

 

Instance

Attribute

 

Component

 

 

 

 

Data

ID

Name

ID

ID

Name

Name

Type

 

 

 

 

 

Output 1

100

Channel

1

20

Ctrl_Status_Chan

BYTE

 

 

Interface

 

 

 

 

 

100

Channel

1

1

AO_Ctrl_Valve_ Flow_Chan

INT

 

 

Interface

 

 

 

 

 

100

Channel

1

9

DO_Position_Chan

BYTE

 

 

Interface

 

 

 

 

 

100

Channel

1

21

DO_ESD_Poll_Cnxn

BOOL

 

 

Interface

 

 

 

 

 

100

Channel

1

11

DO_Relay_Chan

BYTE

 

 

Interface

 

 

 

 

 

100

Channel

1

18

DO_Move_Test_Chan

BOOL

 

 

Interface

 

 

 

 

 

100

Channel

1

19

AO_Analog_Output_Chan

UNIT

 

 

Interface

 

 

 

 

Table 4.3 – Output Assembly Instance 101

Assembly

Object

Instance ID

101

Data

Class

 

Instance

Attribute

 

 

Component

 

 

 

 

Data

 

ID

Name

ID

ID

Name

 

Name

Type

 

 

 

 

 

 

 

Output 2

100

Channel

1

20

Ctrl_Status_Chan

BYTE

 

 

 

Interface

 

 

 

 

 

 

100

Channel

1

1

AO_Ctrl_Valve_ Flow_Chan

INT

 

 

 

Interface

 

 

 

 

 

 

100

Channel

1

21

DO_ESD_Poll_Cnxn

BOOL

 

 

 

Interface

 

 

 

 

 

 

100

Channel

1

10

DO_Move_Test_Chan

BOOL

17

 

 

Interface

 

 

 

 

flowserve.com

Image 17
Contents User Instructions Disclaimer Contents EDS File Declaration of DeviceNet Conformance Odva Certification Declaration of Conformity to the DeviceNet SpecificationAbbreviations Introduction Purpose How to Use this ManualUser Safety User Knowledge DeviceNet System Capabilities and FeaturesGeneral Specifications MX Field Unit Specifications Network specificationsIntroduction System ComponentsHardware Limitorque MXDeviceNet Field Unit DeviceNet Field UnitNetwork Cable Belden Cable SpecificationsHardware interface Site and Network Cable Preparation Installation and ConfigurationSite Preparation Network Cable PreparationCable Preparation Dnfu Installation Verification Installation VerificationNetwork Cabling Installation Verification Assembly Objects Object Model DiagramOutput Assembly Instance Output Assembly InstancesClass Instance Attribute Data Name Type Input Assembly Instance 11 Input Assembly Instance 10 Input Assembly Instance14 Possible values of DIPositionChan DIPositionandBusModeChanDIPositionChan DIActuatorAlarmsChan DIActuatorFaults2Chan16 Possible values of DIActuatorFaults1Chan 18 Possible values of DIActuatorFaults2ChanDIDiscUserInputChan 20 Possible values of DIActuatorAlarmsChanDIReadDiscOutputChan DOPositionChanDIAlarms2Chan DIActuatorFaults3ChanDORelayChan CtrlStatusChanChannel Interface Object Bit 7 Bit Reserved Low BatteryName Data Description Type AttributeName Data Type Description Semantics of Value Transducer Block ObjectName Data Type Description Semantics of Value Bit 7 33 Transducer Attribute Scaled values attribute35 Identity Object Instance Attributes Identity Object Instance AttributesBit 15 Bit 10 Description Semantics of Value AttributeEvent Source Description Behavior36 Behavior Name Data Description Semantics of Value Type Attribute DeviceNet Object Instance Attributes37 DeviceNet Object Instance Attributes Instance ID Channel Interface Object Source Discrete Input Point Object Class ID 8 08hex38 Discrete Input Point Object Analog Input Point Object Class ID 10 0Ahex Discrete Output Point Object Class ID 9 09hexAnalog Output Point Object Class ID 11 0Bhex 39 Discrete Output Point ObjectMAC ID Network ManagementBaud Rate Offline Connection Set Device Heartbeat MessageDevice Shutdown Message Configuration ConfirmationChecking Connections 43 Format of the Device Shutdown MessageView DeviceNet Status View SettingsChecking the Normal Display Access Path to Object TroubleshootingAssociated Documents EDS FileWorkmanship Regulatory Information How to Order PartsWiring Diagram Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 11/05 Flowserve.com Flowserve.com