Thomas & Betts Limitorque MX Device Net Field Unit manual Wiring Diagram

Page 41

Limitorque MX DeviceNet Field Unit  FCD LMENIM2328-00 – 11/05

10

Wiring Diagram

 

 

 

 

 

 

Figure 10.1 – Typical MX DeviceNet wiring diagram (18-499-0038-3)

 

 

 

 

 

 

 

 

 

PE

 

NOTES

 

 

 

 

 

 

 

 

L1

3 PHASE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L2

1.FUSES

 

 

 

 

 

 

 

 

SUPPLY

 

 

 

 

 

 

 

 

L3

 

FSI (PRIMARY)

600V AC, 1A, 200kA Int RATING,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

FS2 (PRIMARY)

FAST ACTING 10.3 x 38.1mm TUBE.

 

 

 

 

 

CLOSE

 

 

 

MOTOR

REVERSING

 

 

STOP

6

 

FS3 (SECONDARY) - 0.1A, 250V, TIME DELAY,

 

 

CONTACTOR

 

 

OPEN

7

 

5 x 20mm, GLASS TUBE

 

 

 

 

 

 

 

2.AUXILIARY INPUT

 

 

 

 

 

 

DIG COM #1-Ve

8

 

 

 

 

 

 

 

 

 

BACK-UP 24v DC UPS POWER MAY BE CONNECTED

 

 

 

 

 

 

 

 

 

 

 

 

 

REMOTE

 

INPUT 2

9

 

TO TERMINAL'S 37 AND 38. MAXIMUM CURRENT

 

 

 

 

INPUTS

 

 

DRAW IS 1 AMP. THIS POWERS ALL CONTROLS FOR

 

 

 

 

 

 

 

 

 

 

FS1

FS2

SEE NOTE 4

 

INPUT 1

10

 

LOCAL INDICATION AND CONFIGURATION. ANALOG OUTPUT AND ALARM

 

 

 

 

 

 

RELAYS SUPPLIED WILL BE POWERED FOR UNITS MANUFACTURED

 

 

 

 

DIG COM #2-Ve

51

 

SUBSEQUENT TO Q1/2003. REVERSING CONTACTOR WILL NOT

 

 

 

 

 

 

BE POWERED. CUSTOMER SHOULD SUPPLY EXTERNAL FUSE AS

 

 

 

 

 

 

 

21

 

REQUIRED BY LOCAL ELECTRICAL CODES.

 

 

 

 

 

 

INPUT 0

 

 

 

 

 

 

 

 

DIG COM #3-Ve

52

 

3.MAXIMUM EXTERNAL LOAD

 

 

 

 

 

 

 

 

 

 

 

 

FS3

 

 

0V AC

11

 

TERMINALS 13 AND 14 (24V DC) - 10W MAX. EXT. LOAD

 

 

 

 

110V AC

12

 

TERMINALS 11 AND 12 (110V AC) - 0V MAX EXT. LOAD

 

 

 

 

 

 

SUITABLE FOR DIGITAL INPUTS

 

 

 

 

 

 

 

 

 

 

 

CONTROL

24V DC +Ve

13

 

ONLY, PROTECTED BY FS3.

 

 

 

 

SUPPLY

 

0V DC

14

 

4.REMOTE INPUTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUXILIARY INPUT

24V DC +Ve

38

 

SIGNAL THRESHOLD - MINIMUM "ON" 19.2V AC/DC

 

 

 

 

37

 

 

MAXIMUM "OFF" 5.0V AC/DC

 

LIMIGARD

 

 

SEE NOTE 2

 

0V DC

 

 

MAX LOAD - 10 mA / 110V AC

 

 

 

 

 

 

 

 

 

2 mA / 24V DC

 

 

 

 

DEFAULT SETTING

 

 

INPUTS 0,1,2 ARE FIELD CONFIGURABLE (FIRMWARE VERSION 04\08.00 OR LATER)

 

 

STATUS FEEDBACK

 

 

FOR CLOSE INHIBIT, OPEN INHIBIT, CLOSE/OPEN INHIBIT, USER INPUT, OR ESD. IN

 

 

 

 

1

 

ADDITION, INPUT 2 MAY BE CONFIGURED FOR CSE REMOTE SELECTED INDICATION.

 

 

OUTPUT SWITCHES

 

AS1

 

 

 

SEE NOTE 6 AND 9

"CLOSE"

 

 

DEFAULT INPUT CONFIGURATION: INPUT 0 - ESD, INPUT 1 - OPEN INHIBIT, INPUT 2 -

 

 

 

2

 

CLOSE INHIBIT

 

 

 

 

 

 

POSITION

 

 

 

 

 

 

 

 

 

 

SEE INSTALLATION AND OPERATION MANUAL FOR CONFIGURATION PROCEDURES.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

POSITION

 

TORQUE

"OPEN"

AS2

 

 

 

 

 

 

SENSOR

 

SENSOR

 

4

 

 

 

 

 

 

POSITION

 

 

5.CONTROL SIGNAL DURATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31

 

REQUIRED CONTROL SIGNAL

 

 

 

 

 

"CLOSE"

AS3

 

 

DURATION = 250 - 350ms.

 

 

 

 

 

 

POSITION

 

32

 

6.STATUS FEEDBACK OUTPUT SWITCHES

 

 

 

 

 

 

 

42

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

"OPEN"

AS4

 

 

THE ACTUATOR STATUS CONTACTS (AS) AND ALARM RELAYS (AR)

 

 

0% OPEN

 

POSITION

 

43

 

MAY BE INDIVIDUALLY CONFIGURED AS NORMALLY OPEN OR NORMALLY

 

 

STATUS OK

(YES)

 

 

 

 

CLOSED LATCHED CONTACTS OR AS BLINKER CONTACTS TO INDICATE

 

REMOTE

 

OPEN

 

 

 

 

ONE OF THE FUNCTIONS LISTED BELOW:

 

 

 

 

 

MONITOR RELAY

 

 

 

 

S

 

 

 

 

 

 

 

 

T

 

 

 

 

17

 

CLOSE

LOCAL STOP/OFF

CLOSE INHIBIT

 

O

 

 

SHOWN

 

 

P

 

 

18

 

CLOSING

MANUAL OVERRIDE

OPEN INHIBIT

 

 

 

 

WITH POWER

 

 

 

LOCAL

 

CLOSE

SUPPLY OFF

 

19

 

MID-TRAVEL

REMOTE SELECTED

ESD SIGNAL

 

 

 

(NO)

ANALOG INPUT

 

 

OPENING

VALVE JAMMED

NO ANALOG SIGNAL

 

 

 

 

 

 

 

 

 

 

+ve ANALOG INPUT-1

39

 

OPEN

MOTOR OVERTEMP

LOST PHASE

 

 

 

 

 

STOPPED

 

 

 

 

(MODUTRONIC)

 

 

OVERTORQUE

LIMIGARD ACTIVE

 

 

 

 

28

 

VALVE MOVING

 

 

 

 

-ve ANALOG COMMON

 

OPEN TORQUE SW

HARDWARE FAILURE

 

CONTROL PANEL

 

 

LOCAL SELECTED

 

 

 

 

40

 

CLOSE TORQUE SW

 

 

 

+ve ANALOG INPUT-2

 

 

 

 

 

 

 

 

 

 

 

CIRCUIT SHOWN WITH VALVE IN FULLY CLOSED POSITION AND WITH POWER OFF

 

 

 

7.CONTACT RATINGS

 

 

 

 

 

AS1,2,3 AND 4 - 5.0 AMPS AT 125V AC, 30V DC (250V AC-CENELEC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MONITOR RELAY - 5.0 AMPS AT 250V AC, 30V DC

 

SHIELD

48

8.EXACT END POSITION INDICATION

DEVICENET

 

NETWORK DATA (-)

 

 

 

15

BLU

 

 

 

ON TORQUE-SEATED VALVES THE LCD AND "AS"

 

 

 

 

 

 

 

 

 

 

16

 

 

 

 

CONTACTS, CONFIGURED AS END OF TRAVEL LIMITS,

BOARD

 

NETWORK DATA (+)

 

 

 

WHT

 

 

 

 

 

 

 

 

 

 

 

 

 

29

 

 

SEE NOTE 11

AUTOMATICALLY PROVIDE EXACT END OF POSITION

 

 

 

 

NETWORK 0V

 

 

BLK

 

 

INDICATION.

 

 

 

 

 

 

 

 

 

 

 

 

 

41

 

 

 

 

 

 

 

 

 

 

NETWORK +24V

 

 

RED

 

 

 

9.DEFAULT SETTING

 

 

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

EGND

 

 

 

 

 

 

ACTUATORS ARE NORMALLY SHIPPED WITH DEFAULT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SETTINGS AS SHOWN ON THIS DIAGRAM. THE "AS"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTACTS ARE SHOWN WITH VALVE IN FULLY CLOSED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POSITION. SEE CONTACT DEVELOPMENT BELOW.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUT SWITCH CONTACT DEVELOPMENT

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER TAPPING OPTIONS

 

 

VALVE POSITION

 

 

 

 

2

4

5

 

 

 

 

 

TYPE

TAPPING

TYPE

TAPPING

OUTPUT

FULL

FULL

FUNCTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SWITCH

CLOSE

OPEN

 

1 7

 

 

 

1

 

5 0

 

 

 

A

220V

B

115V

 

 

3 1

4 3

 

 

 

 

 

AS1

 

 

CLOSE LIMIT

 

 

 

 

 

 

 

 

 

3 0

 

 

380V

 

220V

 

 

1

 

 

 

 

5

 

4 9

4 1

 

 

 

AS2

 

 

OPEN LIMIT

1 8

3 2

 

 

 

 

 

415V

 

525V

 

 

 

 

 

4 4

2

 

 

 

 

 

 

 

AS3

 

 

CLOSE LIMIT

2

 

 

 

 

 

 

 

4 0

2 9

1 6

 

460V

 

575V

AS4

 

 

OPEN LIMIT

1 9

3 3

4 5

 

 

4 8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

4

 

 

2 8

1 5

 

 

 

 

 

 

 

 

3

2 0

3 4

 

 

6

7

 

3 9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.ANALOG INPUT

 

 

 

 

 

3

 

3

3

3

 

 

1 4

 

 

 

 

 

 

4

 

 

5

 

6

7

8

 

2 7

 

 

 

 

STANDARD SIGNAL 4-20 mA

 

 

2 1

2

 

2

 

2

2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

3

 

4

5

6

 

1 3

 

 

 

 

INPUT IMPEDANCE = 250 OHMS

 

 

5

 

 

 

 

 

 

1

1

 

1

 

 

 

 

 

 

 

6

7

 

8

 

9

 

 

 

 

 

INPUT CAPACITACNE = 0.1uf±30%

 

 

 

 

 

0

1

 

2

 

 

 

 

 

 

 

 

L1

 

L2

 

L3

 

 

 

 

 

 

 

99% ACCURACY

 

 

 

 

 

 

 

 

 

 

 

 

 

CONFIGURABLE SCALING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GROUNDING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LUG

 

 

 

11.DEVICENET

 

 

 

VIEW OF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TERMINAL

 

 

 

 

 

 

 

 

 

 

 

 

 

RECOMMENDED DEVICENET CABLE IS BELDEN 3084A OR EQUAL.

BLOCK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120 OHM, 1/4W TERMINATION RESISTORS MUST BE CONNECTED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AT EACH SEGMENT END.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CUSTOMER IS REQUIRED TO CONNECT WIRE BETWEEN TERMINAL 30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AND CHASSIS GROUND FOR SURGE PROTECTION. PREFERRED NETWORK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIRING IS TO CONNECT SHIELD TO TERMINAL 48 FOR ONLY ONE UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON EACH SEGMENT. CONNECT REMAINING INDIVIDUAL NETWORK CABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHIELDS TOGETHER TO ENSURE PROPER SHIELDING OF ENTIRE NETWORK.

41

flowserve.com

Image 41
Contents User Instructions Disclaimer Contents EDS File Declaration of DeviceNet Conformance Odva Certification Declaration of Conformity to the DeviceNet SpecificationAbbreviations Introduction Purpose How to Use this ManualUser Safety User Knowledge DeviceNet System Capabilities and FeaturesGeneral Specifications MX Field Unit Specifications Network specificationsIntroduction System ComponentsHardware Limitorque MXDeviceNet Field Unit DeviceNet Field UnitNetwork Cable Belden Cable SpecificationsHardware interface Site and Network Cable Preparation Installation and ConfigurationSite Preparation Network Cable PreparationCable Preparation Dnfu Installation Verification Installation VerificationNetwork Cabling Installation Verification Assembly Objects Object Model DiagramOutput Assembly Instance Output Assembly InstancesClass Instance Attribute Data Name Type Input Assembly Instance 11 Input Assembly Instance 10 Input Assembly Instance14 Possible values of DIPositionChan DIPositionandBusModeChanDIPositionChan DIActuatorAlarmsChan DIActuatorFaults2Chan16 Possible values of DIActuatorFaults1Chan 18 Possible values of DIActuatorFaults2ChanDIDiscUserInputChan 20 Possible values of DIActuatorAlarmsChanDIReadDiscOutputChan DOPositionChanDIAlarms2Chan DIActuatorFaults3ChanDORelayChan CtrlStatusChanChannel Interface Object Bit 7 Bit Reserved Low BatteryName Data Description Type AttributeName Data Type Description Semantics of Value Transducer Block ObjectName Data Type Description Semantics of Value Bit 7 33 Transducer Attribute Scaled values attribute35 Identity Object Instance Attributes Identity Object Instance AttributesBit 15 Bit 10 Description Semantics of Value AttributeEvent Source Description Behavior36 Behavior Name Data Description Semantics of Value Type Attribute DeviceNet Object Instance Attributes37 DeviceNet Object Instance Attributes Instance ID Channel Interface Object Source Discrete Input Point Object Class ID 8 08hex38 Discrete Input Point Object Analog Input Point Object Class ID 10 0Ahex Discrete Output Point Object Class ID 9 09hexAnalog Output Point Object Class ID 11 0Bhex 39 Discrete Output Point ObjectMAC ID Network ManagementBaud Rate Offline Connection Set Device Heartbeat MessageDevice Shutdown Message Configuration ConfirmationChecking Connections 43 Format of the Device Shutdown MessageView DeviceNet Status View SettingsChecking the Normal Display Access Path to Object TroubleshootingAssociated Documents EDS FileWorkmanship Regulatory Information How to Order PartsWiring Diagram Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 11/05 Flowserve.com Flowserve.com