Limitorque MX DeviceNet Field Unit FCD
Table 4.32 – Continued
Attribute ID
Access Rule
Name
Data Type
Description
Semantics of Value
41 | RW | Valve_Type | USINT | Type of valve | 0 | = linear moving |
|
|
|
|
| valve, sliding valve | |
|
|
|
|
| (Default) 1 = rotary | |
|
|
|
|
| moving valve, part- | |
|
|
|
|
| turn 2 = rotary moving | |
|
|
|
|
| valve, | |
42 | RO | Actuator_Type | USINT | Type of actuator | 0 | = electropneumatic |
|
|
|
|
| 1 | = electric (default) |
|
|
|
|
| 2 | = electrohydraulic 3 |
|
|
|
|
| = others | |
43 | RO | Diagnostic_ Values_0 | UINT | Reserved | Engineering Use | |
44 | RO | Diagnostic_ Values_1 | UINT | Main Voltage | Engineering Use | |
45 | RO | Diagnostic_ Values_2 | UINT | Actuator Position | Engineering Use | |
46 |
| Diagnostic_ Values_3 | UINT | Analog input #1 | Engineering Use | |
47 |
| Diagnostic_ Values_4 | UINT | Analog Input #2 | Engineering Use | |
48 | RW | Tag_Name | SHORT- | Tag name for | String length is limited | |
|
|
| STRING | generic use | to 32 char. Default = 0 | |
|
|
|
|
| (empty) | |
49 | Get/Set | Comm_Loss_ | USINT | Actuator action | 0 | = No Action |
|
| Action |
| upon detection of | (Default) | |
|
|
|
| communication loss | 1 | = Open |
|
|
|
|
| 2 | = Close |
|
|
|
|
| 3 | = Stop |
|
|
|
|
| 4 | = Preset Position |
50 | Get/Set | Comm_Loss_ | UINT | Position to take | Range = 0 – 1000 | |
| Position |
| upon a communica- | Default = 0 | ||
|
|
|
| tion loss |
|
|
51 | Get/Set | Comm_Loss_ | UINT | Time to wait | Range = 0 – 4095 | |
| Timeout |
| after detection of | Default = 255 | ||
|
|
|
| communication loss | ||
|
|
|
| until actuator action |
|
|
|
|
|
| is taken |
|
|
52 | Get/Set | Deadband | UINT | Deadband | Range = 0 – 1000 | |
|
|
| percentage to use | Default = 2 | ||
|
|
|
| when positioning | ||
|
|
|
|
|
| |
53 | Get/Set | Proportional_ | UINT | Proportional band | Range = 0 – 1000 | |
| Band |
| percentage to use | Default = 8 | ||
|
|
|
| when positioning | ||
|
|
|
|
|
| |
54 | Get/Set | TQ_Switch_ | USINT | Percentage of full | Range = 0 – 100 % | |
| Adjust |
| torque to limit | Default = 0 (Disabled) | ||
|
|
|
| operation to | ||
|
|
|
|
|
| |
55 | RW | Actuator_Control_ | USINT | Configure actuator | 1 | = Analog |
|
| Mode |
| for open/close | (Positioning Mode) | |
|
|
|
| or positioning | 2 | = Digital (Open/ |
|
|
|
| operation | ||
|
|
|
| Close Mode) | ||
|
|
|
|
| ||
|
|
|
|
| Default = 2 |
NOTE: Attributes
Table 4.33 – Transducer Attribute – Scaled values attribute 3
Bit 7 - 5
Unused
28
Bit 4
DDC Offset 0 = 0 mA 1 = 4 mA
Bit 3 |
| Bit 2 |
ATT Polarity |
| Analog |
| ||
0 = high |
| Torque |
value 4 mA |
| Transmitter |
1 = high |
| (ATT) 0 |
value 20 mA |
| = ATT |
|
| Disabled 1 = |
|
| ATT Enabled |
Bit 1
APT Polarity 0 = high value 4 mA 1 = high value 20 mA
Bit 0
Analog
Position Transmitter (APT) 0
=APT Disabled 1 = APT Enabled