Thomas & Betts Limitorque MX Device Net Field Unit DIDiscUserInputChan, DIReadDiscOutputChan

Page 23

Limitorque MX DeviceNet Field Unit  FCD LMENIM2328-00 – 11/05

Table 4.20 – Possible values of DI_Actuator_Alarms_Chan

Value

 

Definition

0x01

 

Local ESD Active

 

 

 

 

0x02

 

Remote ESD Active

 

 

 

0x04

 

Open Inhibit Active

 

 

 

0x08

 

Close Inhibit Active

 

 

 

0x05

 

Local ESD Active + Open Inhibit Active

 

 

 

0x09

 

Local ESD Active + Close Inhibit Active

 

 

 

0x06

 

Remote ESD Active + Open Inhibit Active

 

 

 

0x0A

 

Remote ESD Active + Open Inhibit Active

 

 

 

0x0C

 

Open Inhibit Active + Close Inhibit Active

 

 

 

4.2.6DI_Disc_User_Input_Chan

Table 4.21

Bit 7

 

Bit 6

 

Bit 5

 

Bit 4

Discrete

 

Discrete

 

Discrete

 

Discrete

 

 

 

Input #8

 

Input #7

 

Input #6

 

Input #5

Bit 3

Discrete Input #4

Bit 2

Discrete Input #3

Bit 1

Discrete Input #2

Bit 0

Discrete Input #1

4.2.7DI_Read_Disc_Output_Chan

Table 4.22

Bit 7

 

Bit 6

 

Bit 5

 

Bit 4

 

Bit 3

Reserved

 

Relay

 

Relay

 

Relay

 

Relay

 

 

 

 

 

 

Discrete

 

Discrete

 

Discrete

 

Discrete

 

 

Output #7

 

Output6 #

 

Output #5

 

Output #4

 

 

 

 

 

 

 

 

 

Bit 2

Relay

Discrete

Output #3

Bit 1

Relay

Discrete

Output #2

Bit 0

Relay

Discrete

Output #1

4.2.8DO_Position_Chan

Table 4.23

Value

 

Definition

0x00

 

Stop

 

 

 

 

0x01

 

Open

 

 

 

0x02

 

Close

 

 

 

0x03

 

Reserved

– 0xFF

 

 

4.2.9DO_ESD_Chan (Read Only)

Table 4.24

Value

 

Definition

 

0x00

 

Disable Network ESD

 

 

 

 

 

 

 

 

0x01

 

Enable Network ESD

 

 

 

 

 

 

 

DO_ESD_Chan can’t be written directly via the DeviceNet network, it is Read-Only. The attribute

 

Enable_Broadcast_ESD_Ctrl defines if a device is part of the broadcast ESD control scheme from Bit-

 

Strobe Connection or not. The resulting DO_ESD_Chan is defined in the following table.

 

The MX allows the standard I/O connection to assert ESD, or the broadcast bit strobe connection to

23

assert ESD.

flowserve.com

Image 23
Contents User Instructions Disclaimer Contents EDS File Declaration of DeviceNet Conformance Odva Certification Declaration of Conformity to the DeviceNet SpecificationAbbreviations Introduction Purpose How to Use this ManualUser Safety User Knowledge DeviceNet System Capabilities and FeaturesGeneral Specifications MX Field Unit Specifications Network specificationsLimitorque MX System ComponentsIntroduction HardwareDeviceNet Field Unit DeviceNet Field UnitNetwork Cable Belden Cable SpecificationsHardware interface Network Cable Preparation Installation and ConfigurationSite and Network Cable Preparation Site PreparationCable Preparation Dnfu Installation Verification Installation VerificationNetwork Cabling Installation Verification Assembly Objects Object Model DiagramOutput Assembly Instance Output Assembly InstancesClass Instance Attribute Data Name Type Input Assembly Instance 11 Input Assembly Instance 10 Input Assembly Instance14 Possible values of DIPositionChan DIPositionandBusModeChanDIPositionChan 18 Possible values of DIActuatorFaults2Chan DIActuatorFaults2ChanDIActuatorAlarmsChan 16 Possible values of DIActuatorFaults1ChanDOPositionChan 20 Possible values of DIActuatorAlarmsChanDIDiscUserInputChan DIReadDiscOutputChanCtrlStatusChan DIActuatorFaults3ChanDIAlarms2Chan DORelayChanType Attribute Bit 7 Bit Reserved Low BatteryChannel Interface Object Name Data DescriptionName Data Type Description Semantics of Value Transducer Block ObjectName Data Type Description Semantics of Value Bit 7 33 Transducer Attribute Scaled values attributeDescription Semantics of Value Attribute Identity Object Instance Attributes35 Identity Object Instance Attributes Bit 15 Bit 10Event Source Description Behavior36 Behavior Name Data Description Semantics of Value Type Attribute DeviceNet Object Instance Attributes37 DeviceNet Object Instance Attributes Instance ID Channel Interface Object Source Discrete Input Point Object Class ID 8 08hex38 Discrete Input Point Object 39 Discrete Output Point Object Discrete Output Point Object Class ID 9 09hexAnalog Input Point Object Class ID 10 0Ahex Analog Output Point Object Class ID 11 0BhexOffline Connection Set Device Heartbeat Message Network ManagementMAC ID Baud Rate43 Format of the Device Shutdown Message Configuration ConfirmationDevice Shutdown Message Checking ConnectionsView DeviceNet Status View SettingsChecking the Normal Display EDS File TroubleshootingAccess Path to Object Associated DocumentsWorkmanship Regulatory Information How to Order PartsWiring Diagram Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 11/05 Flowserve.com Flowserve.com