Sunway NT 10000 user manual Error Causes

Page 66

Error

Causes

Remedies

Errors 031 to 033 Grid overvoltage > 10 %

The grid voltage of the injecting phase is too high. The Solar Inverter monitors the lower and upper admis- sible grid voltage limits.

If the voltage exceeds the

upper limit by 10 % (Umax = 253 V), the Solar Inverter

will automatically be discon- nected from the grid after 10 minutes (in compliance with E DIN VDE 0126-1-1).

The grid impedance of your grid connec- ting point is too high.

Ask your power supply company about the stability and design of the grid.

The cable cross-section of the AC supply line to the Solar Inverter is insufficient.

Your PV system injects elec- tricity into an insufficiently rated spur line.

Errors 034 to 036 The self-monitoring Solar

Control error Inverter has detected a con- trol fault.

Check the rating of your grid connection (power meter) or the grid injection point to your power supply company.

Ask your power supply company about the stability and design of the grid.

Please call the technical hotline. The phone number is on the back of the user manual.

150

Image 66
Contents Sunways Solar Inverter NT Solar Installation Safety InstructionsBasic Settings Sunways Solar InverterOperating the Display Configuration of the Solar InverterDismantling the Solar Inverter Internal Data MemoryTyco Solarlok Connectors Error DisplayError Diagnosis Abbreviations Technical Data NTGeneral information General Safety Instructions Opening the Device Sunways Solar Inverter NT Scope of DeliveryChecking the Consignment Page Standard Components of a PV System Standard components of the PV systemStructure of NT Page Error No Description Error DescriptionProtection Concept Page Installation Instructions Electrical Safety Mechanical SafetyCleaning Instructions Basic Settings Fixed voltage level 420 540Country Settings Page Ceiling 300 mm Min mm · Thermal Interaction · Protection from Moisture and Foreign ObjectsMechanical Installation Grid Connection DC+ USBThree-phase grid connection 25 aPage Connecting the PV Generator · Preparation · Connection Important InformationPage Communication Interfaces · RS485 Wiring · Connecting a cable to the spring-loaded terminalSpare RS485MATCH RS485GND Connecting the Alarm Relay · Important InformationParalleled alarm relays of several Solar Inverters Alarm relay terminal allocationConnecting the Insolation Temperature Sensor · Allocation of the cable terminal block Sensor pin nameSolar inverter pin name Start-up with DC main switch Commissioning the Solar InverterStarting-Up and Shutting-Down Solar Inverter Start-up without DC main switch Shut-down with DC main switchShut-down without DC main switch Operating Instructions · Setting Values · Menu Guide· Navigating with the Arrow Keys Page Page Configuring the Solar Inverter Internal Data Memory Sunways Monitor 2.0 Software Sunways Portal and Sunways Communicator Modem LinkInterface Cables Interface TransformerLink SunwaysMonitor Direct Monitor Local134 Modem Ad 5 Local Link for up to 99 Solar Inverters Spare RS485MATCH USBInverter 3 RS485 Ad 6 Remote Link for up to 99 Solar Inverters Finding the Jumper «RS485 MATCH» Solar InverterErrors 001 to Errors 004 toErrors 010 to Errors 007 toErrors 013 to ErrorErrors 017 to Errors 020 toErrors 023 to Errors 031 to Errors 028 toErrors 034 to Illustr. Operation indicator LED 143 Error Causes RemediesErrorCauses Remedies Error Causes ErrorCauses Error Causes Error Causes Error Causes 152 Appendix Tyco Solarlok Connectors Page LCD Designation Description MPPTechnical Data NT 10000 Model Solar Inverter NT159 Conformity and Safety Declarations 161 162 Terms and Conditions of Guarantee · Duration of Guarantee· Conditions · Exclusion of Liability General Exclusion of Liability All rights reserved. Sunways AGRegistered trademark Version 11/05