Error 027
· Grid overvoltage 3-phase
Your Solar Inverter is equipped with an intrinsically safe
Errors 031 to 033
· Grid overvoltage > 10 percent
If the voltage of the injecting phase has exceeded 253 V for more than ten minutes, the Solar Inverter will stop the injection and only try to restart when the grid voltage is within the admissible range again. The functioning method complies with E DIN VDE
Errors 028 to 030
· Surge fault
Your Solar Inverter continuously monitors the quality of the AC grid. If there are high voltage peaks in the grid, the Solar Inverter will stop the injection and try to restart.
If such a surge impulse is detected at energy unit 3, for example, «error 030» will be flagged.
Errors 034 to 036
· Control fault
Your Solar Inverter is equipped with a self- monitored micro controller as a standard feature. If a fault occurs in the control sequence, the Solar Inverter will stop the injection and will only restart when the fault has been eliminated. If a fault occurs in the control circuit board of the third energy unit (upper energy unit), for exam- ple, «error 036» will be flagged.