Sunway NT 10000 user manual Error Causes, Remedies

Page 60

3.8Error Diagnosis

You can look up error causes yourself in the following list. Select the occurred error, and read the «Remedies» to find out how to eliminate it.

Error

Causes

Errors 001 to 003

The maximum DC voltage

DC overvoltage

has been exceeded.

 

Too many modules are

 

connected in series.

Remedies

Check the rating of your PV generator.

Reduce the number of modules in the DC inlet concerned, and recommission the system.

Errors 004 to 006

The grid frequency is outsi-

Frequency fault

de the admissible range.

Errors 007 to 009 The maximum admissible

Overheating ambient temperature of 40°C has been exceeded.

The required air circulation was not considered during installation.

Ask your power supply company about the stability and design of the grid.

The installation site is not suitable. Please select a different installation site.

If contamination is blocking the cooling system, clean the Solar Inverter.

144

Image 60
Contents Sunways Solar Inverter NT Solar Safety Instructions Basic SettingsInstallation Sunways Solar InverterConfiguration of the Solar Inverter Dismantling the Solar InverterOperating the Display Internal Data MemoryError Display Error DiagnosisTyco Solarlok Connectors Abbreviations Technical Data NTGeneral information General Safety Instructions Opening the Device Sunways Solar Inverter NT Scope of DeliveryChecking the Consignment Page Standard Components of a PV System Standard components of the PV systemStructure of NT Page Error No Description Error DescriptionProtection Concept Page Installation Instructions Electrical Safety Mechanical SafetyCleaning Instructions Basic Settings Fixed voltage level 420 540Country Settings Page Ceiling 300 mm Min mm · Thermal Interaction · Protection from Moisture and Foreign ObjectsMechanical Installation Grid Connection DC+ USBThree-phase grid connection 25 aPage Connecting the PV Generator · Preparation · Connection Important InformationPage Communication Interfaces · RS485 Wiring · Connecting a cable to the spring-loaded terminalSpare RS485MATCH RS485GND Connecting the Alarm Relay · Important InformationParalleled alarm relays of several Solar Inverters Alarm relay terminal allocationConnecting the Insolation Temperature Sensor · Allocation of the cable terminal block Sensor pin nameSolar inverter pin name Start-up with DC main switch Commissioning the Solar InverterStarting-Up and Shutting-Down Solar Inverter Start-up without DC main switch Shut-down with DC main switchShut-down without DC main switch Operating Instructions · Setting Values · Menu Guide· Navigating with the Arrow Keys Page Page Configuring the Solar Inverter Internal Data Memory Sunways Monitor 2.0 Software Sunways Portal and Sunways Communicator Modem LinkInterface Cables Interface TransformerSunways Monitor DirectLink Monitor Local134 Modem Ad 5 Local Link for up to 99 Solar Inverters Spare RS485MATCH USBInverter 3 RS485 Ad 6 Remote Link for up to 99 Solar Inverters Finding the Jumper «RS485 MATCH» Solar InverterErrors 001 to Errors 004 toErrors 007 to Errors 013 toErrors 010 to ErrorErrors 017 to Errors 020 toErrors 023 to Errors 031 to Errors 028 toErrors 034 to Illustr. Operation indicator LED 143 Error Causes RemediesErrorCauses Remedies Error Causes ErrorCauses Error Causes Error Causes Error Causes 152 Appendix Tyco Solarlok Connectors Page LCD Designation Description MPPTechnical Data NT 10000 Model Solar Inverter NT159 Conformity and Safety Declarations 161 162 Terms and Conditions of Guarantee · Duration of Guarantee· Conditions · Exclusion of Liability General Exclusion of Liability All rights reserved. Sunways AGRegistered trademark Version 11/05