Hunter Fan R410A manual Error display, Control of 1 remote controller VS multiple units

Models: R410A

1 48
Download 48 pages 23.34 Kb
Page 20
Image 20
[Control of 1 remote controller VS multiple units

8

Error display :

e10

[Control of 1 remote controller VS multiple units

 

 

 

 

 

Excessive number of units (more than 17 units) ]

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

Outdoor unit

 

Red LED

 

Stays OFF

Red LED

 

Stays OFF

 

Green LED

 

Keeps flashing

Green LED

 

Keeps flashing

 

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

Are more

YES

 

than 17 units connected

Reduce to 16 units

to a remote

 

or less

controller?

 

 

 

NO

 

 

 

 

 

 

 

 

Defective indoor unit control PCB Excessive number of units (more than 17 units) ]

Replacement

9

Error display : e16

[Fan motor abnormalities]

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

Outdoor unit

Red LED

Stays OFF

Red LED

 

Stays OFF

Green LED

Keeps flashing

Green LED

 

Keeps flashing

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

SOnly case of FDTA501, 601 types

Abnormal data check with remote controller

After check reset, fan runs on weak.

White is GND.

CNM1

NO

1 and 3 (Red – White)

DC280V?

YES

3 is GND.

CNW9

NO

1 and 3 DC15V?

YES

(1)

DC 15VNO between CNW9- 3 and

CNM2 4 ?

Replacement indoor

unit power supply PCB

YES

Secondary

side of transformer

(red-red) 15V

or more

Error display : e16 NO

Replacement transformer

Replacement indoor

unit control PCB

NO

 

Fan ON?

 

 

YES

 

 

 

 

NO

Check the

Was it reproduced?

 

circumstances.

 

 

 

 

YES

When the

NO motor is turning, does the voltage at CNM2 2

fluctuate between

0 ~ 15 V?

YES

Replacement indoor

Note (1) CNW9- 3 is GND.

YES

Does the

fan motor turn NO [Fan motor abnormalities] Detective fan motor smoothly by

hand?

unit control PCB

YES

(2)

 

Is the voltage

YES

at CNM2 3 DC 1V

 

 

or higher?

 

Note (2) CNW9- 3 is GND.

NO

Replacement indoor

unit control PCB

Display conditions

If an indoor unit fan motor’s speed is detected to be less than 200 rpm continuously for 30 seconds, the fan motor stops for 2 seconds. After 2 seconds, it starts again, but this occurs 4 times within a period of 1 hour.

-18 -

Page 20
Image 20
Hunter Fan R410A manual Control of 1 remote controller VS multiple units, Error display e16, Fan motor abnormalities