(b)Display sequence of error, inspection display lamp

1)One kind error

Display corresponding to the error is shown.

2)More than one errors.

Section

 

Display section

 

 

Error code of remote controller

• Displays the error of higher priority (When plural errors are persisting)

 

···········

···········

Inspection LED (red) of indoor unit PCB

 

 

 

• Displays the present errors.

 

Inspection LED (red) of outdoor unit PCB

 

(When a new error has occurred after the former error was reset.)

 

 

 

3)Timing of error detection

Indoor unit side.

Error detail

 

 

 

Error code

 

Timing of error detection

 

 

 

 

 

 

 

 

 

 

 

 

Drain error (float switch motion)

 

 

 

 

 

 

 

 

 

Normally, 30 seconds after the power is turned ON.

 

 

 

 

 

 

 

 

 

 

 

 

Wrong connection between the indoor and

 

 

 

Wait

 

 

 

No communications even once with the outdoor unit.

outdoor units.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transmission error of remote controller

 

 

 

 

 

 

 

 

 

After 1 or more communications of the indoor unit with the remote controller

indoor unit

 

 

 

 

 

 

 

 

 

following power on, transmission errors cause an interruption for 2 minutes.

 

 

 

 

 

 

 

 

 

 

 

Transmission error between indoor/outdoor

 

 

 

 

 

 

 

 

 

After communications with the outdoor unit 1 or more times, communications

units

 

 

 

 

 

 

 

 

 

are abnormal continuously for 2 minutes.

 

 

 

 

 

 

 

 

 

 

 

 

The number of connected indoor units

 

 

 

 

 

 

 

 

 

 

 

exceeds the connection limit (when

 

 

 

 

 

 

 

 

 

Normally after the power is turned ON (during communications).

multiple units are control by a single remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controller).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Broken wire of indoor unit return air

 

 

 

 

 

 

 

 

 

When an input temperature of –50°C or lower is measured by the return air

 

 

 

 

 

 

 

 

 

thermistor is measured for 5 seconds or longer within 60 minutes after the

thermistor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

first detection.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Broken wire of heat exchanger thermistor

 

 

 

 

 

 

 

 

 

When an input temperature of –50°C or lower is measured by the heat

 

 

 

 

 

 

 

 

 

exchanger thermistor is measured for 5 seconds or longer within 60 minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

after the first detection.

Outdoor unit side.

Error detail

Error code

Timing of error detection

 

 

 

 

 

When a thermistor input temperature of –30°C or lower is measured for 5

Broken wire of outdoor air temperature

 

seconds or longer 3 times within 40 (60) minutes after the 1st detection

thermistor

 

between 2 minutes and 2 minutes 20 seconds after compressor operation

 

 

starts.

 

 

 

Broken wire of heat exchanger thermister

 

When a thermistor input temperature of –30°C or lower is measured for 5

 

seconds or longer 3 times within 40 (60) minutes after the 1st detection

 

 

between 2 minutes and 2 minutes 20 seconds after compressor operation

 

 

starts.

Broken wire of discharge pipe thermistor

 

When a thermistor input temperature of –10°C or lower is measured for 5

 

seconds or longer 3 times within 40 (60) minutes after the 1st detection

 

 

 

 

between 10 minutes and 10 minutes 20 seconds (between 2 minutes and 2

 

 

minutes 20 seconds) after compressor operation starts.

 

 

 

Broken wire of power transistor

 

When the under-dome thermistor input temperature of –10°C is measured for

 

5 seconds or longer 3 times within 40 minutes after the 1st detection between

thermistor

 

10 minutes and 10 minutes 20 seconds after compressor operation starts.

 

 

 

Notes (1) Values in ( ) show for the FDCA301~601 models.

(2) The power transistor temperature sensor is used in the FDCVA151~251 models only.

- 6 -